QCP INSTALL]
REV. 03.15.19
Filtrine Mfg. Co. • 15 Kit St. Keene, NH 03431 USA
800-930-3367 • 603-352-5500 • FAX 603-352-0330
WEB www.filtrine.com • EMAIL [email protected]
FILTRINE IS ISO 9001:2015 CERTIFIED
PRODUCT LINE APPROVED MARK AVAILABLE
MADE IN USA
FILTER MAINTENANCE
The filter is a bag type. Using a 50 micron
bag, the pressure drop is less than 5 p.s.i.
when new. The filter should be changed
if the pressure drop across the unit ex-
ceeds 12 p.s.i. A spare filter should be
kept on hand at all times.
Study the flow path of Mode 4 op-
eration in the chart to the right
. This
configuration allows the replacement
of the filter element while delivering
uninterrupted flow to the medical
equipment. This will probably be the first
routine maintenance performed on the
QCP. Since the system is a closed loop,
the coolant will eventually be cleaned
of all contamination and filter changes
will become rare.
If repeated city water operation is
actuated, filter contamination is likely.
The filter element should be changed
when the pressure drop across the unit
is greater than 12 p.s.i.g.
FILTRINE QCP – QUICK CONNECT PANEL
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
QCP OPERATION MODES: O=OPEN / C=CLOSED
NORMAL
FULL BY-PASS
SERVICE FLOW METER
SERVICE FILTER
CITY WATER BACK-UP
*
VALVE
1
2
3
4
5
A
O
O
O
C
O
B
O
O
O
C
O
C
C
C
C
O
C
D
C
O
C
O
C
E
C
C
O
C
C
F
O
O
C
O
O
G
C
O
O
C
C
H
O
O
C
O
O
I
O
C
O
C
O
J
O
C
O
O
O
*Optional equipment for QCP-AS
T
P
S
M
F
T
P
S
F
S
P
BALL VALVE
BACKFLOW PREV.
SOLENOID
PRESSURE GAUGE
TEMP. GAUGE
CITY
WATER
IN (OPT.)
A
I
B
C
D
E
F
G
H
J
QCP PLUMBING SCHEMATIC
T
M
FILTER
1/2" DRAIN VALVE
FLOW METER
CHECK VALVE
IN-LINE CK VALVE
Y-STRAINER
LEGEND
TO
CHILLER
FROM
CHILLER
Provided by
installing
contractor
CITY WATER
DRAIN (OPT)
FROM
EQUIP
TO
DRAIN
TO