Arming / Disarming The System
To Arm the system:
1.
After the system has been fully tested and restored to Normal operation, reset the IVO following
the instructions provided on the Impulse Valve Operator component sheet,
P/N 06-492.
2.
Connect the Impulse Valve Operator (Figure 7) to the suppression container as detailed on the
Impulse Valve Operator component sheet, P/N 06-492.
Figure 7 – Impulse Valve Operator
The EOL Assembly Part # 17-0143 is housed in the DIN Connector, see figure 6.
The maximum cable length between the IVO and the IRM must not exceed 3 metres.
Note:
A discharge pressure switch (P/N 02-12534) must be installed on the discharge piping for
each IVO container equipped with a manual release actuator (required as per
EN12094-1 Section 4.18 option with requirements).