background image

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the 
event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
2.   Set the desired address on the sensor address switches, see Figure 1.
3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control panel and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

FIGURE 2. WIRING DIAGRAM

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

UL Listed Compatib

le

Control P

anel

CAUTION: Do not loop wire under 

terminal 1 or 2.  Break wire run to 

supervise connections.

CLASS A OPTIONAL WIRING

Remote 

Annunciator

(–)
(+)

RA

+

+

RA

+

+

RA

+

+

 

C0129-10

TAMPER-RESISTANCE

Photoelectric and temperature sensors include a tamper-resistant capability 
that prevents their removal from the base without the use of a tool. Refer to 
the base manual for details on making use of this capability.

TESTING

Before testing, notify the proper authorities that the system is undergoing 
maintenance, and will temporarily be out of service. Disable the system to 
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. 

UL 268 listed for Open Air Protection 
UL268A listed for Duct Applications
UL 521 listed for Heat Detectors
This sensor must be installed in compliance with the control panel system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with the National Fire Protection Association (NFPA); 
see NFPA 72. 

GENERAL DESCRIPTION

Models FIK-2351T is a plug-in type multi-sensor smoke sensor that combines 
a photoelectronic sensing chamber and 135°F (57.2°C) fixed temperature heat 
detector across addressable-analog communications. The sensors transmit an 
analog representation of smoke density over a communication line to a control 
panel. Rotary dial switches are provided for setting the sensor’s address. (See 
Figure 1.) The intelligent photoelectric and temperature sensors also transmit 
an alarm signal due to heat at 135°F (57.2°C) per UL 521.

FIGURE 1. ROTARY ADDRESS SWITCHES

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator  
(P/N RA100Z). 
Fike panels offer different feature sets across different models. As a result, cer-
tain features of the photoelectric and temperature sensors may be available on 
some control panels, but not on others. These devices support Fike IDP mode 
systems. The possible features available if supported by the control panel are:
1.   The sensor’s LEDs can operate in three ways—on, off, and blinking–and 

they can be set to red, green, or amber. This is controlled by the panel. 

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

3.   Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the UL listed control panel for spe-
cific operation. The photoelectric and temperature sensors require compatible 
addressable communications to function properly. Connect these sensors to 
listed-compatible control panels only. 

SPACING

Fike recommends spacing sensors in compliance with NFPA 72. In low air 
flow applications with smooth ceilings, space sensors 30 feet apart (9.1 m). 
When using the photoelectric and temperature sensors as a heat detector in 
FM3210 compliant applications, space sensors 20 feet apart (6 m). For specific 
information regarding sensor spacing, placement, and special applications, 
refer to NFPA 72 or the System Smoke Detector Application Guide, available 
from System Sensor.

I56-6633-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

R

 704 SW 10th Street

 Blue Springs, MO 64015

 Phone: 816.229.3405; Fax: 816.228.9277 

www.fike.com

 

FIK-2351T  

Intelligent Photoelectric and  

Temperature Sensors

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Operating Current @ 24 VDC:   200 uA (one communication every 5 sec. with green LED blink on communication)
Maximum Alarm Current:  

2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)

Maximum Current:  

4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range:  32°F to 115°F (0°C to 47°F)
Air Velocity: 

0 to 4000 ft./min. (0 to 1219.2 m/min.) 

Height: 

2.0˝ (51 mm) installed in B300-6 Base

Diameter: 

6.2˝ (156 mm) installed in B300-6 Base; 4.1˝ (104 mm) installed in B501 Base

Weight: 

3.4 oz. (95 g) 

Isolator Load Rating:  

0.0063*

*Please refer to your isolator base/module manual for isolator calculation instructions. 

http://www.fike.com/06-912

For system/product documentation including 

installation, operation, and maintenance, 

scan QR code or enter URL provided. 

  

I56-6633-000 

 

 1/15/2021

Отзывы: