98
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Programming
System Options
Strobes Active when Silenced
When “SYNC Strobe:” is selected as Y (Yes), the strobes will continue to flash when the System is silenced and will stop flashing when the
System is reset.
5.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
6.
Press right arrow key or ENTER to make your selection and move to the next programming option.
Auto Display Events
When this feature is programmed Y (Yes), the highest priority event of the System in control will automatically display on the control panel
and the remote annunciators, after there has been no activity on any system touch pad for two minutes.
7.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
8.
Press right arrow key or ENTER to make your selection and move to the next programming option.
9.6.6 Daylight Saving Options
To edit Daylight Savings:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 6 for Daylight Savings.
Automatic Daylight Saving Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. If this feature is not enabled (set to
No
), the Daylight
Saving Time change is not made to the system clock.
To enable or disable DST adjustment, continue programming:
5.
Select Y (enabled) or N (disabled) by pressing the up or down arrow, then press ENTER.
Daylight Saving Time Start and End
This option lets you to adjust the week and month Daylight Saving Time (DST) starts and ends. For this feature to work, you must enable (set
to
Yes
) the Automatic Daylight Savings Adjustment option under Daylight Savings Options. The default values for the DST Start and End
are:
DST Start: The second Sunday in March
DST End: The first Sunday in November
To set the start and end for Daylight Saving Time:
6.
Press the up or down arrow to select the week (1st, 2nd, etc.) Daylight Saving Time starts, then press ENTER to make your selection
and move to the month setting.
7.
Press the up or down arrow to select the month (January – December) Daylight Saving Time starts, then press ENTER to make your
selection and move to the DST End option.
8.
Press the up or down arrow to select the week (1st, 2nd, etc.) Daylight Saving Time ends, then press ENTER to make your selection and
move to the month setting.
9.
Press the up or down arrow to select the month (January – December) Daylight Saving Time ends, then press ENTER two times to
make your selection and exit.
9.6.7 Edit Banner
The banner is the message that displays on the panel LCD when the system is normal, that is, when no alarms or troubles exist and no one is
currently using system Menus. You can create a customized message, which can be up to 40 characters, two lines of 20 characters each.
If you do not create a customized message, the system will use the internal banner. You cannot change the internal banner.
To customize the banner display message:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 7 for Edit Banner.
5.
Select each character of a word by pressing the up or down arrow, then press the right arrow key to move the cursor to the next
character.
6.
When the word or sentence is complete, press ENTER to move the cursor to line two of the custom banner.
NOTE:
The “SYNC Strobe:” only functions with outputs that use a synchronized output pattern.
NOTE:
For UL installations, the alarm verification time can not be less than 60 seconds.
NOTE:
See Appendix B for a instructions on how to edit the banner