Zone
Programming
FCP-75 Manual —
P/N:LS10147-003FK-E:A 3/17/2021
87
Heat Detector Sensitivity
Use this feature to set the temperature at which high temperature detectors will respond. All detectors in the zone will respond in the same
way. The range for the FIK-5351HT heat detector is from 135°F to 190°F.
The FIK-5351HT heat detector are absolute temperature devices. This means that they respond to an alarm immediately if the temperature in
the zone goes above the programmed temperature.
2.
Enter the temperature at which the heat detector will respond. Or use the up or down arrow keys to scroll through the range. Then press
ENTER.
Smoke Detector Sensitivity
All detectors in the zone will respond as programmed in this Menu location.
* Automatic drift compensation is always in effect for all detectors. See Section 10.4.1 for information about how to check
if a detector is in compliance.
3.
Use the up or down arrow to scroll through the options, then press ENTER.
Zone Accessory Options
1.
Do steps 1 through 5 of Section Section 9.3.1.
2.
Press 3 to edit the Zone’s Accessory options.
Single or Multi-Station cadence pattern. (Choose from Patterns 00 to 02, 23.) See “Cadence Patterns” on page 141.
CO Single and Multi station Cadence. (Choose from Cadence Patterns 00 to 02, 23.)
Local Zone (choose Y or N, for Yes or No).
9.3.2 View Zone Points
To view the points in a zone, follow these steps:
1.
Enter the Installer Code. The panel will automatically go to the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 2 to enter Zone Menu.
4.
Press 2 to view zone points.
PAS-Positive Alarm
Sequence
This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds, giving on-site
personnel a chance to investigate the alarm. If the acknowledge switch is not activated within 15 seconds, an alarm
occurs automatically.
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:
• The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the acknowledge
switch.
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into alarm.
• If the operator presses the acknowledge switch within 15 seconds, a 180-second time-frame will begin
counting down. This time-frame allows the operator to investigate the cause of the alarm.
• If the operator performs a reset within 180 seconds, the alarm will not occur.
• If the operator does not perform a reset within 180 seconds, an alarm will occur automatically.
• The P.A.S. feature will be overridden if another alarm occurs.
SNGL ILOCK
See Section 10.7.1 for single interlock releasing operation.
DBL ILOCK
See Section 10.7.2 for double interlock releasing operation.
Note: FIK-FC351 and other CO detectors can only be installed in a 1 count zone; they will operate as a 1-count point regardless of the
programmed zone type (i.e. Alarm Verification, 2 count etc.).
Type of Delay
Description
Table 9.2 Alarm Delay Types (Continued)
NOTE:
Drift compensation is automatic for all smoke detectors (photoelectric and ionization). The feature is always in effect, no programming
is required. See Section 10.4.1 for information about how to check if a detector is in UL compliance.
Type of Smoke
Detector
Choices
Comments
FIK-2351,
&
FIK-2351T
Low (3.5% obscurity)
If the day/night sensitivity option is selected, you can have
different sensitivity settings during the day and at night. You can
determine the days of the week that Day/Night Sensitivity will
automatically adjust. You can also designate specific days as
Holidays. Holiday and weekend days use night sensitivity for the
entire day
Medium (2.5% obscurity)
High (1.5% obscurity)
DNR with
FIK-2351R or
FIK-2351
Low (2.5% obscurity)
Medium (2.0% obscurity)
High (1.5% obscurity)
Table 9.3 IDP Detector Sensitivity Choices*
NOTE:
The B200S-WH / IV Sounder base provides the recommended CO cadence pattern.