26
FCP-75 Manual —
P/N LS10147-003FK-E:A 3/17/2021
Control Panel Installation
FIK-RA100 Remote Annunciator Installation
The total worst case current is calculated as follows:
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
4.4.2 Wiring Configurations
Figure 4.8 illustrates Class B configuration.
Figure 4.8 SBUS Class B Wiring
4.5 FIK-RA100 Remote Annunciator Installation
The optional Model FIK-RA100 Remote Annunciator, is shown in Figure 4.9. The FIK-RA100 can be surface or flush mounted. Up to 8
FIK-RA100s can be added to the FCP-75 system in any combination.
Figure 4.9 Model FIK-RA100 Remote Annunciator, Front View
FIK-RA100 Current Draw
= 2 x .100 amps
= .200 amps
FIK-5496 Current Draw
= 1 x .010 amps
= .010 amps
FIK-5865 Current Draw
= 1 x .200 amps
= .145 amps
FIK-5824 Current Draw
= 1 x .040 amps
= .040 amps
Total Worst Case Current Draw
= .395 amps
Table 4.5 Wiring Distance Calculations
supervised
power-limited