background image

TERMINAL 

BLOCK

T1

External Power – Powers Aspirating Smoke Detector

T2

SLC power – Powers SLC Interface Circuit. Isolated from  
External Power

T3

RS 485 Rx

Rx and Tx can be wired in a half duplex configuration

T4

RS 485 Tx

Rx and Tx can be wired in a half duplex configuration

T5

Alert Relay – Maintains state on loss of power

T6

Action1 Relay – Maintains state on loss of power

T7

Action2 Relay – Maintains state on loss of power

T8

Fire1 Relay – Maintains state on loss of power

T9

Fire2 Relay – Maintains state on loss of power

T10

Fault Relay – Maintains state on loss of power

CABLING REQUIREMENTS

The FAAST XT system provides a series of Euro style pluggable terminals, 
located behind the left side door of the unit. Refer to Table 1 for the proper 
electrical connections to the unit. Refer to Table 2 for a typical connection for 
monitoring the FAAST XT system at a Fire Alarm Control Panel (FACP).

TABLE 1. TERMINAL DESIGNATIONS

SYSTEM POWERING

The following procedure describes how to initially power up the FAAST XT system.

 

1.  Unplug the unit’s power connector to the unit before turning on the 

power.

 

2. Turn on the power.

 

3.  Check the voltage at the connector. Make sure it is within the required 

voltage range.

 

4.  If the voltage is within the proper range, reconnect the power connec-

tor to the unit. Do not connect the SLC at this point in order to enable 
configuration.

 

5.  Connect a computer, with PipeIQ installed, to the unit using either the 

USB connection on the front of the device, or the Ethernet port located 
in the left side wiring door. (See the ‘Connecting to FAAST XT’ for 
detailed connection instructions.)

 

6.  Use the PipeIQ software to set up the unit configuration required for 

the particular application.

 

7.  The PC may now be disconnected unless a permanent networked con-

nection is desired. 

 

8. Connect to SLC

 

9.  Verify the system fan starts up and air begins to flow out of the ex-

haust port. The user interface will provide the device status.

 

10.  The device will establish an airflow baseline during the first five min-

utes of operation. After five minutes, the airflow level display will 
provide the true measured airflow status. The device will give visual 
indication of the baselining period on the LCD screen.

FK-600-000  3 I56-4223-001

FIGURE 3. POWER AND ALARM CONNECTION BLOCK

To Next SLC Device   –

From FACP or Previous Device   –

From FACP or Previous Device   +

To Next SLC Device   +

SLC

Connection

To Next Device   +

24V External

Power

From Power Supply or Previous Device   +

From Power Supply or Previous Device   –

To Next Device   –

ASP114-02