FK-600-000  1 I56-4223-001

SPECIFICATIONS

Electrical Characteristics

External Supply Voltage  

18 – 30 VDC

Average SLC Operating Current 

300 µA

Power Reset  

1 sec

Relay Contact Ratings  

3.0A @ 30VDC, 0.5A @125VAC

Environmental Ratings

Operating Temperature  

32F (0C) to 100F (38C)

Sampled Air Temperature  

-4F (-20C) to 140F (60C)

Humidity  

10 to 95% non-condensing

IP Rating  

IP30

68-302 FAAST
Fire Alarm Aspiration Sensing Technology

®

INSTALLATION AND MAINTENANCE INSTRUCTIONS

I56-4223-00

1

The purpose of this document is to provide practical information for mount-
ing and connecting to FAAST XT. For full product information, which includes 
installation guidelines, instructions for safe use, and warranty and safety 
information, refer to the FAAST XT Comprehensive User Guide available at  
systemsensor.com/68-302userguide or by scanning the QR code.

ITEMS INCLUDED WITH UNIT

•  FAAST XT (68-302) unit

•  Mounting bracket and hardware

•  Installation and Maintenance Instructions

•  USB interface cable
•  PipeIQ software, comprehensive manual, and other helpful documents 

may be downloaded at systemsensor.com/faast

CONNECTING TO FAAST XT

FAAST XT requires a configuration download from PipeIQ in order to initialize. 
This connection can be achieved using either the USB port located on the front of 
the device, or the Ethernet port located inside the wiring cabinet.

CONNECTING TO FAAST XT VIA USB

NOTE: In order to connect your computer to the FAAST XT using a USB con-
nection, a USB driver must first be installed. The driver installation occurs 
during the installation of PipeIQ version 2.0 or later. Once the driver is in-
stalled, connect to the device using the following steps.

1. Launch PipeIQ.
2. Create a new project and select FAAST XT device, or open an existing project
3. Expand the tree view in the left side navigation pane to reveal the device
4. Right click on the device and select ‘Connect Device’
5.  Select USB, The USB combo box should already be populated with FAAST 

XT (Com Port Number).

6.  Select Read only/Administrator(requires password – default is ‘password’) 

mode Click Connect.

CONNECTING TO FAAST XT VIA ETHERNET

Default Device IP Configuration
IP Address:  

192.168.1.10

Subnet Mask:  

255.255.255.0

Default Gateway:  

192.168.1.1

Primary DNS:  

0.0.0.0

Secondary DNS:  

0.0.0.0

CONFIGURE YOUR PC

Your PC will need to be sitting on the same local area network as the FAAST XT device 
in order to establish communication. Change your PC’s IP address to 192.168.1.15 by:

 

1. Accessing your network setting in your PC’s control panel

 

2. Open ‘Local Area Connection’ settings and select ‘Properties’

 

3. Select ‘Internet Protocol Version 4 (TCP/IPv4) and then select ‘Properties’

 

4.  Select ‘Use the following UP address and enter 192.168.1.15. If the 

subnet mask does not automatically populate, enter 255.255.255.0 
into the subnet mask field.

 

5. Hit OK and close out of the network menus.

(Important Note: Before changing your PC’s IP address, be sure to take note of 
whether your IP is currently dynamically set, or is a static IP address. If your PC 
is assigned a static IP address, make note of the IP address and subnet mask so 
that you can change back to the proper settings after the FAAST XT is configured.)

CONNECT USING PIPEIQ

 

1.  Launch PipeIQ. (PipeIQ may be downloaded from systemsensor.com/faast)

 

2. Create and save a new project, or open an existing project

 

3.  Expand the tree view in the left side navigation pane to reveal the device

 

4. Right click on the device and select ‘Connect Device’

 

5.  Change the User field to ‘Administrator’ and enter the password – the 

default password is ‘password’ – then hit ‘Connect’

 

6.  Upon connection, a green check will appear next to the device in the  

navigation tree

INSTALLATION

This equipment must be installed in accordance with all local and national 
codes and regulations.

PIPE INSTALLATION

The pipe layout is designed using the PipeIQ software package. Refer to the 
Comprehensive Instruction Manual to design the pipe network. All pipe must 
be installed in accordance with local and national codes and regulations. The 
pipe network should be complete before proceeding with the physical and 
electrical system installation.

PHYSICAL UNIT INSTALLATION

WARNING

Make sure that there are no pipes or electrical wires within the wall before 
drilling any mounting holes

SECURING THE MOUNTING BRACKET

The typical mounting location for the FAAST XT unit is on the wall. The unit 
is mounted to the wall using the enclosed mounting plate. Figure 1 shows the 
wall mounting plate. For easier access to the FAAST XT unit, it is preferred to 
position the mounting plate in an easily accessible location.

 

1.  Place the mounting bracket on the wall in the desired location and use 

it as a template to locate the necessary mounting holes.

 

2.  Mark the hole locations and remove the bracket. It is recommended to 

secure the bracket using the 4 outer mounting holes.

 

3.  Using a drill and the proper size bit for your mounting hardware, drill 

the necessary holes.

 

4.  Use appropriate fasteners to accommodate the mounting surface and 

FAAST XT device weight.

 

5. Secure the bracket to the wall.