ECS Series Manual —
P/N LS10262-001FK-E:A 3/3/2021
10
Section 2: Agency Listings, Approvals, and Requirements
2.1 Federal Communications Commission (FCC)
1.
The following information must be provided to the telephone company before the FACP can be connected to the phone lines:
2.
This device may not be directly connected to coin telephone or party line services.
3.
This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the installing company or return to:
Fike Corporation
704 SW 10th Street
Blue Springs, MO 64015
+1-816-229-3405
www.fike.com
4.
If the FACP causes harm to the telephone network, the telephone company will notify the user in advance that temporary
discontinuance of service may be required. If advance notice is not practical, the telephone company will notify the user as soon as
possible. Users have the right to file complaints, if necessary, with the Federal Communications Commission.
5.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the
equipment. If this happens, the telephone company will provide advance notice to allow you to make the necessary modifications to
maintain uninterrupted service.
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for addi-
tional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on). See the Operation Mode Behavior Section of the manual for information on
releasing operations.
1.
All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2.
Use the addressable smoke detectors specified in the device installation section of the FACP installation manual and or conventional
detectors listed in the FACP manual’s compatibility chart.
3.
Use UL listed notification appliances compatible with the FACP from those specified in the FACP manual.
4.
A full system checkout must be performed any time the panel is programmed.
Restricted Options
•
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 3 hours. For UL certified installations this
number must be set from 1 to 3 hours.
•
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications whereby
a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
•
The system allows the Alarm Verification time to be set from 60 to 255 seconds. For UL certified installations the setting must be a
minimum of 60 seconds.
•
The system allows the Auto-resound time to be set to 24 or 4 hours. For UL certified installations that are utilizing SWIFT devices, the
value must be set to 4 hours.
•
Call forwarding shall not be used.
•
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
•
P.A.S (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
1.
Use both phone lines. Enable phone line monitors for both lines.
2.
You must program a phone number and a test time so that the FCP-300/ECS shall automatically initiate and complete a test signal
transmission sequence to its associated receiver at least once every 6 hrs. The AC Loss Hours option must be set from 1-3 hours.
3.
If using wired Ethernet, you must program the corresponding account/subscriber ID and a test time so that the FACP shall automatically
initiate a test signal transmission sequence to its associated receiver at least once every 6 hrs.
A
Manufacturer:
Fike
B
Model Number:
FCP-300ECS, FCP-2100ECS
C
FCC registration number:
AC6USA-34758-AL-E, AC6USA-23901-AL-E or
AC6AL11B6820
Ringer equivalence:
0.8B
D
Type of jack:
RJ31X
E
Facility Interface Codes:
Loop Start: 02LS2
F
Service Order Code:
9.0F
!
WARNING: FCC PART 15
THIS DEVICE HAS BEEN VERIFIED TO COMPLY WITH FCC RULES PART 15. OPERATION IS SUBJECT TO THE
FOLLOWING CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE RADIO INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.