Connecting the Air Sampling Pipe

The input and output ports are designed to accept standard one inch pipe (25 
mm) OD. The input ports are tapered to provide fast, easy, push-fit connection 
of the sampling pipe to the unit. Perform the following procedure to connect 
the air sampling pipe to the unit.

1.   Square off and de-burr the end of the sampling air pipe. Ensure that the pipe 

is free from any particles that might interfere with the pipe connection.

2.   Remove the input plug from the input port being used (either the top or 

bottom of the unit).

3.   Insert the sampling air pipe into the input port, ensuring a snug fit.  

DO NOT glue these pipes.

Mounting the Detector to the Bracket

Once the mounting plate is attached, the unit is ready to be mounted onto the 
plate. Perform the following procedure to mount the unit.

1.   Before installing the unit onto the bracket, remove the appropriate con-

duit cap from the top or bottom-left side of the unit to match the orienta-
tion of the wiring. See Figure 14 for location of the wiring access plugs. 

2.   Line up the unit with the four mounting clips and the mounting studs on 

the left side.

3.   Push the unit down onto the mounting clips and secure it with the sup-

plied washer and nut on at least one of the two mounting studs protrud-
ing through the mounting slots shown in Figure 2.

Exhaust Pipe

The device should always be exhausted into the space that it is monitoring. 
There are some circumstances when it may be necessary to connect a pipe to 
the exhaust port to divert the exhaust away from the location of the unit. The 
output ports are tapered the same as the input ports, to provide fast, easy, 
push-fit connection of an exhaust pipe to the unit. Perform the following pro-
cedure to connect the exhaust pipe to the unit.

1.   Square off and de-burr the end of the exhaust pipe. Ensure that the pipe 

is free from any particles that might interfere with the pipe connection.

2.   Remove the exhaust plug from the output port being used (either the top 

or bottom of the unit).

3.   Insert the exhaust pipe into the output port, ensuring a snug fit. DO NOT 

glue these pipes.

WIRING

WARNING

Before working on the FAAST system, notify all required authorities that the 
system will be temporarily out of service. Make sure all power is removed 
from the system before opening the unit. All wiring must be in accordance 
with local codes.

Power Cables

Use the power ratings of the unit to determine the required wire sizes for each 
connection. Use the power ratings of the connected products to determine 
proper wire size.

Conduit Usage

If electrical conduit is used for system wiring, terminate the conduits at the cable 
entry ports on the top or bottom of the unit, using the appropriate conduit con-
nectors.

1.   Run all wiring, both power and alarm, through the conduit and into the 

left side of the unit enclosure, as shown in Figure 3.

2.   Attach the appropriate wires to the supplied Euro connector. Follow ap-

propriate local codes and electrical standards for all cabling.

3.   Plug the appropriate connector into the mating connector on the unit.

Power and Alarm

Connections

ASP16-01

FIGURE 3.  POWER AND ALARM CONNECTION CONNECTOR BLOCK

Содержание 68-140

Страница 1: ...Aspiration Sensing Technology INSTALLATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION SCOPE OF THIS MANUAL 2 DESCRIPTION FEATURES 2 ITEMS INCLUDED WITH UNIT 2 INSTALLATION PIPE INSTAL...

Страница 2: ...n for increased filter life Electronic filter life monitoring Ultrasonic air flow sensing Field service access door Easy access filter maintenance door Event service and trend logs Pipe modeling softw...

Страница 3: ...e circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit The output ports are tapered the same as the input ports to prov...

Страница 4: ...the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitoring the FAAST system at a Fire Alarm Control Panel FACP SYSTEM POWERING...

Страница 5: ...the current air flow is to either of these thresholds During normal operation two adjacent indicators are green and correspond to the current air flow entering the detector When airflow is at a balan...

Страница 6: ...een a specified minimum and maximum sensitivity programmed by the user For the first 24 hours of opera tion the device monitors its environment After the initial 24 hour period the device adjusts the...

Страница 7: ...r by illuminating the par ticulate bar graph to the appropriate number of segments for each digit as shown in Figure 11 The example shown in Figure 11 shows that the 5th number of the IP address is 6...

Страница 8: ...ystem is equipped with internal memory that can be configured to log detector events Up to 18 000 events can be stored Events that are tracked include alarms faults and user actions Event tracking dat...

Страница 9: ...dically thereafter Testing methods must statisfy the authority having jurisdiction Systems of fer maximum performance when tested and maintained in compliance with NFPA 72 and or CAN ULC S536 dependin...

Страница 10: ...n number send defective units postage prepaid to System Sensor Returns WARRANTY Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspe...

Отзывы: