Fike 203-0003 Скачать руководство пользователя страница 4

26-0350 Issue 11

 

 

Technical Data 

 

Dimensions:

  

 

 

Diameter   

 

 

105mm 

 

Depth     

 

 

62mm  

Operating temperature:  

 

 

 

 

-10

o

C to +50

o

Voltage Range:  

 

 

 

 

 

 

24 to 42V DC 

LED Indication: 

 

 

Normal   

 

 

50ms on / 20s interval 

 

 

 

 

Fault 

 

 

 

0.1ms on / 5s interval 

 

 

 

 

Fire 

 

 

 

50ms on / 400ms interval 

Flammability 

 

 

 

 

 

 

UL94-V2

 

IP Rating 

 

 

 

 

 

 

IP 21C

 

 

System Compatibility:

  

MPS - Sita200plus V2.00 onwards. 

  

  

 

 

MP -   Sita200plus V2.30 onwards. 

 

 

 

 

Duonet and Quadnet V1 onwards. 

 

PRODUCT DESCRIPTION 

VOLUME LEVEL (dB) 

 

 

Type 

Product 

Code 

Name 

Low 

Medium 

High 

 

 

 

 

MP 

203 0003 

Multipoint Mk3 (25/11/09 Onwards) 

 

 

MPS 

203 0001 

Multipoint with Sounder Mk3 (25/11/09 Onwards) 

65+ 

83 

88 

 

 

 

 

 

 

 

 

 

 

  

LOOP CURRENT (mA) 

Type 

Product 

Code 

Name 

Quiescent 

SP0 - Off 

Low 

Medium 

High 

MP 

203 0003 

Multipoint Mk3 (25/11/09 Onwards) 

0.12 

0.96 

MPS 

203 0001 

Multipoint with Sounder Mk3 (25/11/09 Onwards) 

0.12 

1.00 

1.48 

4.03 

5.84 

 

 

 

 

 

 

 

 

  

BATTERY CURRENT (mA) 

Type 

Product 

Code 

Name 

Quiescent 

SP0 - Off 

Low 

Medium 

High 

MP 

203 0003 

Multipoint Mk3 (25/11/09 Onwards) 

0.12 

2.00 

MPS 

203 0001 

Multipoint with Sounder Mk3 (25/11/09 Onwards) 

0.12 

2.00 

3.01 

8.37 

12.04 

 

 

 

 

 

 

 

 

  

DLU RATING 

 

Type 

Product 

Code 

Name 

SP0 - Off 

Low 

Medium 

High 

 

 

MP 

203 0003 

Multipoint Mk3 (25/11/09 Onwards) 

 

MPS 

203 0001 

Multipoint with Sounder Mk3 (25/11/09 Onwards) 

1.5 

4.5 

 

 

N.B.

 All specified volume and current readings, unless otherwise stated are taken using sound pattern SP3. 

 
Technical Support 

 

Contact your supplier for technical support on this product. 

Due to the complexity and inherent importance of a life risk type system training on this equipment is essential, and 
commissioning  should  only  be  carried  out  by  competent  persons.  Fike  cannot  guarantee  the  operation  of  any 
equipment unless all documented instructions are complied with, without variation. This unit complies with the EMC 
directive. 

 

Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is 
reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of 
publication, Fike shall be under no liability whatsoever in respect of such contents. E&OE. 

Отзывы: