SBPC-21-PB CUSTOMER INSTRUCTION MANUAL 

 

 

 
 

________________________________________________________________________________________________________________ 
 
12-20-2002 

Figure Sheet 1-851-A 

Page 9

 

 

 

2  

F

IFE

N

ET 

T

HEORY

 

• • • • • •

 

 

FifeNet Time Slices 

Data on FifeNet is divided into time intervals called time slices.  The FifeNet protocol runs in fixed 
repeating cycles.  Each time slice can transmit a single 16-bit value.  All time slice values are updated 
every cycle.  
 

Multiplexed Time Slices 

FifeNet devices can send a single 16-bit value in one or more time slices.  This is acceptable for 
values that require high performance such as guiding.  The penalty for this performance is the usage 
of one time slice per value sent.  With limited time slices available, network bandwidth can be 
consumed quickly.  If some variables are not needed at a high rate, FifeNet offers a way to “multiplex” 
a single time slice to carry multiple data words.  There are two multiplex options available in the 
CDP-01 permitting a single time slice to carry 16 words or 64 words.  Multiplexing works by inserting 
the specified data words in a sequential repeating cycle.  The receiving SBPC-21-PB synchronizes 
with the multiplexed data to extract it.  This method trades data update speed for higher data quantities 
(up to 64 words per time slice).  Any combination of real-time or multiplexed data can exist on FifeNet.   
 

Figure 2-1:  Multiplexed Data Time Slices 

 

 
 
 
 

T0 

   T1 

      T2 

           T3 

 

−−−−−−−−−−−−−−−−−

 

 

−−−−−−−−−−−−−−−−−

 

 

−−−−−−−−−−−−−−−−−

 

 

−−−−−−−−−−−−−−−−−

 

D1      D5                                 D1    D5                                 D1   D5                                   D1  D5 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 
 

D1 ACTIVITY 

D1 is real-time.  This data 
is updated every cycle. 

D5 ACTIVITY 

Tn   TS Contents 
T0   - Edge Right Sensor 
T1   - Line Edge Sensor 
T2   - CDP Key Pressed 
T3   - Status Register Common 
T4   - Drive 1 Mode 
T5   - Drive 1 Sensor Mode 
T6   - Drive 1 Encoder 
T7   - Drive 1 Status Reg 0 
T8   - Drive 2 Mode 
T9   - Drive 2 Sensor Mode 
T10  - Drive 2 Encoder 
T11  - Drive 2 Status Reg 0 
T12  - Drive 3 Mode 
T13  - Drive 3 Sensor Mode 
T14  - Drive 3 Encoder 
T15  - Drive 3 Status Reg 0 

MULTIPLEXING 

D5 is multiplexed or switched to a 
different variable every cycle. 
After the last variable is sent, the 
process repeats continuously. 

Содержание SBPC-21-PB PROFIBUS DP

Страница 1: ...6508 Oklahoma City OK 73126 U S A Phone 405 755 1600 Fax 405 755 8425 www fife com E mail fife fife com 2002 Fife Corporation All rights reserved SBPC 21 PB FifeNet to Profibus Gateway Customer Instru...

Страница 2: ......

Страница 3: ...on Manual is subject to change without notice We have compiled this Instruction Manual with the greatest possible care and attention However the possibility of error cannot be completely excluded Fife...

Страница 4: ......

Страница 5: ...eNet Time Slices 9 Multiplexed Time Slices 9 FifeNet Master 10 SBPC 21 PB Data Flow 10 CONFIGURATIONS 13 Hardware Configuration Single CDP 01 13 Hardware Configuration Multiple CDP 01 s 14 Software Co...

Страница 6: ......

Страница 7: ...C 21 PB Profibus is a shielded copper cable consisting of a twisted pair The baud rate for the bus is between 9 6K baud to a maximum 12M baud The Profibus DP network is able to carry 126 nodes and the...

Страница 8: ...e cleared Stop only master master functions are possible Synchronization Enables synchronization of the inputs and or outputs of all DP slaves Sync Mode Outputs are synchronized Freeze Mode Inputs are...

Страница 9: ...tocouplers Profibus DP Ccommunication IC SPC3 Chip from Siemens Producer Consumer Model The Producer Consumer Model allows the exchange of information between a sending device producer and many receiv...

Страница 10: ...two jumpers should always be installed as they select half duplex FifeNet communication Terminated Not Terminated The 7 segment LED is used to display errors or exceptions During normal operation the...

Страница 11: ...it s 1 5 Mbit s 12 Mbit s Connection to FifeNet is accomplished using the standard FifeNet connector Configuration is also downloaded using this connection LED indicators provide feedback for network...

Страница 12: ...Module is not ONLINE OFFLINE LED State Meaning Red Indicates that the module is OFFLINE and no data exchange is possible Off Module is ONLINE FAULTS LED State Meaning Off No faults present Flashing Re...

Страница 13: ...E Unable to write to queue F0F Console I O error Errors that begin with F are unrecoverable faults The SBPC cannot participate in FifeNet or Profibus operations In the default configuration the SBPC w...

Страница 14: ...________________________________________________________________________________________________________________ 12 20 2002 Figure Sheet 1 851 A Page 8...

Страница 15: ...ords There are two multiplex options available in the CDP 01 permitting a single time slice to carry 16 words or 64 words Multiplexing works by inserting the specified data words in a sequential repea...

Страница 16: ...time slice boundaries were located This would create problems when they are trying to send and receive data This is one of the primary functions of the FifeNet Master in this case that would be the SB...

Страница 17: ...ore 64 16 bit data words This is the maximum amount of data that appears on a FifeNet multiplexed time slice These data words are referenced by their order of reception in the multiplexed sequence wit...

Страница 18: ...________________________________________________________________________________________________________________ 12 20 2002 Figure Sheet 1 851 A Page 12...

Страница 19: ...B connection diagram is shown below As you can see this allows a single CDP 01 at FifeNet address 1 and an SBPC 21 PB at FifeNet address 10 The SBPC 21 PB default Profibus node address is 2 but can be...

Страница 20: ...drives a configuration has been created to match the parameters present in each drive configuration This prevents inefficient use of Profibus bandwidth for data that is inapplicable The three configu...

Страница 21: ...apabilities on Data Words 2 through 6 provide for custom applications using state machine interpretation Table 4 1 PROFIBUS TO FIFENET DATA SINGLE DUAL AND TRIPLE DRIVE CDP 01 Matrix 100246 02X Single...

Страница 22: ...INT Edge Right Sensor Value Sensor signal 8 INT Line Center Sensor Value Sensor signal 9 INT Line Edge Sensor Value Sensor signal 10 WORD SM Command Feedback Reserved for state machine control 11 WOR...

Страница 23: ...or state machine control 12 WORD Common Status Register CDP 01 status 13 WORD Key Pressed Current key pressed on CDP 01 panel 14 WORD Drive 1 Operation Mode Drive 1 status 15 WORD Drive 1 Sensor Mode...

Страница 24: ...n Mode Drive 1 status 15 WORD Drive 1 Sensor Mode Drive 1 status 16 WORD Drive 1 Fault Register Drive 1 fault status 17 WORD Drive 1 Encoder Register Drive 1 encoder status 18 WORD Drive 1 Alarm Regis...

Страница 25: ...or safety reasons This command is EXTERNAL LOCK Even though the CDP 01 matrix has the parallel inputs mapped to a FifeNet time slice the EXTERNAL LOCK command is still activated by the matrix shown be...

Страница 26: ...ETUP 30 DRIVE 1 RGPC SHIFT LEFT 18 DRIVE 1 RGPC SHIFT RIGHT 28 DRIVE 1 RGPC RESET 38 DRIVE 1 SENSOR EDGE LEFT 14 DRIVE 1 SENSOR EDGE RIGHT 24 DRIVE 1 SENSOR EDGE CENTER 34 DRIVE 1 SENSOR LINE CENTER 1...

Страница 27: ...LINE CENTER 1C DRIVE 1 SENSOR LINE EDGE 2C DRIVE 1 SENSOR LINE E C 3C DRIVE 2 AUTOMATIC 05 DRIVE 2 MANUAL 09 DRIVE 2 SERVO CENTER 0D DRIVE 2 JOG LEFT 11 DRIVE 2 JOG RIGHT 21 DRIVE 2 AUTO SETUP 31 DRIV...

Страница 28: ...Mode 1 2 LED 10 Edge Right Sensor Mode 2 3 LED 9 Edge Left Sensor Mode 3 4 LED 17 Polarity 4 5 LED 16 Gain 5 6 LED 15 Guide Point 6 7 LED 14 Auto Setup 7 8 8 LED 3 Manual Key 9 9 LED 2 Servo Center Ke...

Страница 29: ...32 767 DW12 Common Status Register COMMON STATUS REGISTER DW12 Data Word Bit No 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Description 0 0 Drive 1 Panel Active 0 1 Drive 2 Panel Active 1 0 Drive 3 Panel A...

Страница 30: ...W13 Data Word Bit No Key 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Hex Value ASC 0 0x07FF F3 0 0xBFFF F2 0 0xDFFF F1 0 0xEFFF Sensor 0 0xF7FF Automatic 0 0xFBFF Servo Center 0 0xFDFF Manual 0 0xFEFF Drive...

Страница 31: ...Description 0 0 1 Automatic 0 1 0 Servo Center 1 0 0 Manual 0 0 1 Jog Left 0 1 0 Jog Right 1 0 0 0 Setup Auto or Man is Also Set DW15 DW21 DW27 Drive Specific Sensor Selection and Temperature Fault D...

Страница 32: ...or Drive Power Supply 1 Fault Motor Overcurrent 1 Fault 12V Power Supply 1 Fault 12V Power Supply 1 Fault Analog Ground 1 Fault A D Converter Initialization 1 Fault Overtemperature DW17 DW23 DW29 Driv...

Страница 33: ...1 Web Measurement Alarm 1 Loss of Null 1 ASC Automatic Sensor Control Active 1 Fault Serial Power 1 Drive Centered 1 Drive in Shutdown 1 Counterclockwise Maximum Motor Speed 1 Clockwise Maximum Motor...

Страница 34: ...________________________________________________________________________________________________________________ 12 20 2002 Figure Sheet 1 851 A Page 28...

Страница 35: ...eys are pressed on your panel The CDP 01 responds with the key code representing which key or keys are currently pressed Normally the FifeNet Master then issues a command back to the CDP 01 with the k...

Страница 36: ...ity to lock out the CDP 01 keypad If local keypad operation was needed concurrently with network control the command should be maintained until the correct feedback is obtained Feedback is obtained by...

Страница 37: ...ate We have to look a little deeper to understand how to use this capability Since there are 31 LED s on the CDP 01 panel the information has to use the multiplexed mode to send all the LED states The...

Страница 38: ...________________________________________________________________________________________________________________ 12 20 2002 Figure Sheet 1 851 A Page 32...

Страница 39: ...ve Profibus to FifeNet 15 Network 13 Switch Jumper 4 Connections FifeNet 5 Network 1 Consumer See Producer Consumer Model Control Matrix Dual Drive 20 Single Drive 19 Triple Drive 21 Data Flow 10 Data...

Страница 40: ...Selection 25 DW22 Drive 2 Fault Register 26 DW23 Drive 2 Encoder Register 26 DW24 Drive 2 Alarm Register 27 DW25 Drive 2 Encoder Value 27 DW26 Drive 3 Operating Mode 25 DW27 Drive 3 Sensor Selection 2...

Страница 41: ......

Отзывы: