FieldServer Modbus Plus FS-8700-02 Скачать руководство пользователя страница 4

FS-8700-02 Modbus Plus 

       

Driver Manual 

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042 

Visit our website: www.fieldserver.com          E-mail:  

[email protected]

 

Page  2 

Address   Switches 6--1  

Address   Switches 6--1  

Address   Switches 6--1 

14 

0 0 1 1 0 1 

36 

1 0 0 0 1 1  

58 

1 1 1 0 0 1 

15 

0 0 1 1 1 0 

37 

1 0 0 1 0 0 

59 

1 1 1 0 1 0 

16 

0 0 1 1 1 1 

38 

1 0 0 1 0 1 

60 

1 1 1 0 1 1 

17 

0 1 0 0 0 0 

39 

1 0 0 1 1 0 

61 

1 1 1 1 0 0 

18 

0 1 0 0 0 1 

40 

1 0 0 1 1 1 

62 

1 1 1 1 0 1 

19 

0 1 0 0 1 0 

41 

1 0 1 0 0 0  

63 

1 1 1 1 1 0 

20 

0 1 0 0 1 1 

42 

1 0 1 0 0 1 

64 

1 1 1 1 1 1 

21 

0 1 0 1 0 0 

43 

1 0 1 0 1 0 

 

 

22 

0 1 0 1 0 1 

44 

1 0 1 0 1 1 

 

* = default 

 

Table 2: Summary of Modbus Data Access Commands  
Function Code (Decimal) 

Command Name  

Read Discrete Output Status (0xxxx) 

Read Discrete Input Status (1xxxx) 

Read Output Register (4xxxx) 

Read Input Register (3xxxx) 

Force Single Coil (0xxxx) 

Preset Single Register (4xxxx) 

15 

Force Multiple Coils (0xxxx) 

16 

Preset Multiple Registers (4xxxx) 

 

Modbus Plus Card Indicators

 

 
The Modbus Plus card has an indicator that flashes a repetitive pattern to show its network 
communication status, plus two indicators which identify communication errors on the two 
Modbus Plus cable paths.  Note that one error indicator will be lit normally in single -cable 
installations, showing that a second cable does not exist. 
 

Table 3: Modbus Plus Active Indicator Patterns  

Indicator Pattern (Green) 

Status  

Six flashes/second 

Normal operating state.  All nodes on a healthy 
network flash this pattern 

One flash/second 

The node is off-line.  After being in this state for 5 
seconds, the node attempts to go to its normal 
operating state. 

Two flashes, then OFF for 2 
seconds 

The node detects the network token being passed 
among other nodes, but it never receives the 
token. 

Three flashes, then OFF for 
1.7 seconds 

The node does not detect any token passing on the 
network. 

Four flashes, then OFF for 
1.4 seconds 

The node has detected another node using the 
same address. 

 

 

 

 

 

Содержание Modbus Plus FS-8700-02

Страница 1: ...LITY EFFECTIVITY Effective for all systems manufactured after May 1 2001 Instruction Manual Part Number FS 8700 02 Version 1 00 Revision 1a 5 24 2002 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 02 Modbus Plus ...

Страница 2: ...2 FieldServer as a Modbus Plus Client 3 2 1 Hardware Connections 3 2 2 Configuration File Structure 3 2 2 1 Data Arrays 3 2 2 2 Client Side Connections 3 2 2 3 Client Side Nodes 3 2 2 4 Client Side Map Descriptors 4 3 FieldServer as a Modbus Plus Server 5 3 1 Hardware Connections 5 3 2 Configuration File Structure 5 3 2 1 Data Arrays 5 3 2 2 Server Side Connections 5 3 2 3 Server Side Nodes 5 3 2 ...

Страница 3: ...erver FieldServer Technologies PART DESCRIPTION FS 8915 01 Adapter Card Modbus Plus Single Port User must supply Modbus Plus cables and connectors including termination connectors as documented by Group Schneider Modicon Provided by user PART DESCRIPTION Refer to the Drawings in section 3 1 Modbus Plus Client e g Wonderware Intellution FIX GE Cimplicity etc 2 1 If FieldServer used as Modbus Plus C...

Страница 4: ...l 0xxxx 6 Preset Single Register 4xxxx 15 Force Multiple Coils 0xxxx 16 Preset Multiple Registers 4xxxx Modbus Plus Card Indicators The Modbus Plus card has an indicator that flashes a repetitive pattern to show its network communication status plus two indicators which identify communication errors on the two Modbus Plus cable paths Note that one error indicator will be lit normally in single cab...

Страница 5: ... PRIMSERV CSV and SECDSERV CSV files Note that indicates an optional parameter with the bold legal value being the default 2 2 1 Data Arrays Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Format Provides data format INT16 INT32 BIT FLOAT Data_Array_Length Number of Data Objects 1 10 000 2 2 2 Client Sid...

Страница 6: ...Data Array names from Data Array section above Data_Array_Offset Starting location in Data Array 0 to maximum specified in Data Array section above Function Function of Client Map Descriptor RDBC Node_Name Name of Node to fetch data from One of the node names specified in Client Node Descriptor above Address Starting address of read block 40001 30001 etc Length Number of items to read 1 125 Data_A...

Страница 7: ...ut in the configuration file For convenience a few example parameters already exist in the supplied PRIMSERV CSV and SECDSERV CSV files Note that indicates an optional parameter with the bold legal value being the default 3 2 1 Data Arrays SectionTitle Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Format Provides da...

Страница 8: ...tems to read 1 125 Data_Array_Low_Scale Scaling zero in Data Array 32767 to 32767 default 0 Data_Array_High_Scale Scaling max in Data Array 32767 to 32767 default 100 Node_Low_Scale Scaling zero in Connected Node 32767 to 32767 default 0 Node_High_Scale Scaling max in Connected Node 32767 to 32767 default 100 3 3 Examples of FieldServer setup for typical clients MSTR Example Modbus Plus Node This ...

Страница 9: ... Plus Driver Manual FieldServer Technologies 1991 Tarob Court Milpitas California 95035 408 262 2299 fax 408 262 9042 Visit our website www fieldserver com E mail support fieldserver com Page 7 MSTR in Modbus Plus Node ...

Отзывы: