5. 

Configuring the FieldServer as a Honeywell Zellweger IR-148 Server 

For  a  detailed  discussion  on  FieldServer  configuration,  please  refer  to  the  FieldServer 
Configuration Manual.  The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files 
provided with the FieldServer). 

This section documents and describes the parameters necessary for configuring the FieldServer 
to report sensor data to Honeywell Zellweger IR-148 Client.  As a Server this driver sends Gas 
value, Alarm, Trouble and Lock point messages.  The driver can be locked to send data for only 
one particular sensor.

 

The configuration file tells the FieldServer about its interfaces, and the routing of data required. 
In  order to  enable the  FieldServer for  Honeywell  Zellweger IR-148  communications,  the  driver 
independent  FieldServer  buffers  need  to  be  declared  in  the  “Data  Arrays”  section,  the 
FieldServer  virtual  node(s)  needs  to  be  declared  in  the  “Server  Side  Nodes”  section,  and  the 
data  to  be  provided  to  the  Clients  needs  to  be  mapped  in  the  “Server  Side  Map  Descriptors” 
section.  Details on how to do this can be found below. 

Note  that  in  the  tables,  *  indicates  an  optional  parameter,  with  the  bold  legal  value  being  the 
default. 

5.1. 

Server Side Connection Descriptors 

Section Title 

Connections 

Column Title 

Function 

Legal Values 

Port 

Specify  which  port  the  device  is 
connected to the FieldServer 

P1-P8 

(with 

232/485 

converter), R1-R2

2

 

Protocol 

Specify protocol used 

InfraTox or Infra-Tox 

Baud* 

Specify baud rate 

110  –  115200,  standard 
baud rates only 

9600 

Parity* 

Specify parity 

Even,  Odd, 

None, 

Mark, 

Space 

Data_Bits* 

Specify data bits 

7, 

8

 

Stop_Bits* 

Specify stop bits 

Handshaking* 

Specify hardware handshaking 

RTS, RTS/CTS, 

None

 

 

Example 

 

//    Server Side Connections 
 
Connections 
Port, 

Protocol, 

Baud, 

Parity, 

Data_Bits 

R1, 

InfraTox, 

19200, 

None, 

 8 

 

                                                 

2

 

Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 

manual for details of the ports available on specific hardware.

 

Содержание Honeywell Zellweger IR-148 FS-8700-102

Страница 1: ...PLICABILITY EFFECTIVITY Effective for all systems manufactured after May 1 2001 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 102 Honeywell Zellweger IR 148 Manual Driver Version 1 01 Document Revision 9 ...

Страница 2: ...ent Side Connection Descriptors 7 4 3 Client Side Node Descriptors 7 4 4 Client Side Map Descriptors 8 4 4 1 FieldServer Related Map Descriptor Parameters 8 4 4 2 Driver Related Map Descriptor Parameters 8 4 4 3 Map Descriptor Example 9 5 CONFIGURING THE FIELDSERVER AS A HONEYWELL ZELLWEGER IR 148 SERVER 10 5 1 Server Side Connection Descriptors 10 5 2 Server Side Node Descriptors 11 5 3 Server Si...

Страница 3: ...s and depending on the IR 148 operational mode e g Locked mode may never contain information other than for one sensor As a Server The Server side of this driver has been developed primarily to test the Client side driver as part of FieldServer s QA program The driver sends messages reporting the state of the samples The Server driver can also be locked to report the status value of one particular...

Страница 4: ...2 2299 Fax 408 262 9042 Toll_Free 888 509 1970 email support fieldServer com 2 Driver Scope of Supply 2 1 Supplied by FieldServer Technologies for this driver FieldServer Technologies PART Description FS 8917 16 RJ45 to terminal connector cable FS 8700 102 Driver Manual 2 2 Provided by the Supplier of 3rd Party Equipment 2 2 1 Required 3rd Party Hardware Part Description NONE ...

Страница 5: ...he FieldServer is connected to the Honeywell Zellweger IR 148 Device as shown in connection drawing Configure the device according to manufacturer s instructions BASE NAME FILE NAME VisioDocument Honeywell Zellweger IR 148 Device FieldServer Connection Diagram DATE 03 07 07 BY MC 408 262 2299 FS 8917 16 G OR OTHER DEVICES INFRATOX UNIT FS X20 Serial G INFRATOX UNIT FS X40 ORANGE WHITE BROWN BLUE W...

Страница 6: ...of data required In order to enable the FieldServer for Honeywell Zellweger IR 148 communications the driver independent FieldServer buffers need to be declared in the Data Arrays section the destination device addresses need to be declared in the Client Side Nodes section and the data required from the Servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this...

Страница 7: ...ndor limitation Example Client Side Connections Connections Port Protocol Baud Parity Stop_Bits R1 InfraTox 19200 None 1 4 3 Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for node Up to 32 alphanumeric characters Node_ID Irrelevant for this driver as long as only one Node is connected Otherwise the Node ID should be the number of points ...

Страница 8: ...s Map Descriptor Up to 32 alphanumeric characters Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Data Array section above Data_Array_Offset Starting location in Data Array 0 to maximum specified in Data Array section above Function Function of Client Map Descriptor Passive_Client 4 4 2 Driver Related Map Descriptor Parameters Colum...

Страница 9: ...me Data_Array_Name Data_Array_Offset Function Node_Name Length CMD1 DA_R1 0 Passive Client DEV1 100 One of the Data Arrays declared in the Data_Array section 4 1 The Data from the Node Dev1 will be stored in this Data Array The Driver stores Data from device DEV1 with this memory location as the starting point and onward in Data Array DA_R1 This means that the FieldServer cannot poll the target de...

Страница 10: ...le the FieldServer for Honeywell Zellweger IR 148 communications the driver independent FieldServer buffers need to be declared in the Data Arrays section the FieldServer virtual node s needs to be declared in the Server Side Nodes section and the data to be provided to the Clients needs to be mapped in the Server Side Map Descriptors section Details on how to do this can be found below Note that ...

Страница 11: ...ng Node status information 1 255 Protocol Specify protocol used InfraTox Infra Tox Port Specify at which port the device is connected to the FieldServer Ports P1 P8 can be used with 232 485 converter P1 P8 with 232 485 converter R1 R2 Example Server Side Nodes Nodes Node_Name Node_ID Protocol Port DEVR1 1 InfraTox R1 5 3 Server Side Map Descriptors 5 3 1 FieldServer Specific Map Descriptor Paramet...

Страница 12: ...ray This memory location will be checked every time if the user has locked a sensor If this parameter is not specified the driver will use the Data_Array_Offset value 1 Maximum of Data Array length Infra_Func For quality assurance this parameter is used to send a message to a Client from a Map_Descriptor_Name ini file With the use of this function Data_Array_Offset value will be used as line numbe...

Страница 13: ... DA_CTL_R1 the driver will only send data for that particular sensor To disable the lock insert an invalid 0 or 8 number Server Side Map Descriptors Map Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Length Da_Byte_Name Da_Byte_Oset SMD1 DA_R1 0 wrbc DEV1 100 DA_CTL_R1 0 Driver will look into this data array to send Zellweger message to Zellweger 8 Channel Cli...

Страница 14: ...ctive of the contents The line may contain up to 2000 characters Server Side Map Descriptors Map Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Length Infra_Func SMD1 ini Dummy 2 wrbc DEV1 1 INFRA_SIMULATION Data Array Offset which indicates the line number to send by this Map Descriptor to send Node DEV1 This wrbc function makes this Server an Active Server T...

Страница 15: ...iver can be configured to store data in one of two ways a Default One Set of consecutive Data Array elements is used for each Honeywell Zellweger IR 148 8 8 Channel Unit One set per point sensor Offset Sensor Contents Description 0 1 Alarm or Trouble Set non zero if alarm or a trouble has been reported Set to zero if neither are currently being reported 1 1 Alarm Type 0 None 1 Caution 2 Warning 3 ...

Страница 16: ...State 0 Enabled 1 Disabled 8 1 Gas Value Valid 1 Gas Value updated with most recent message 0 Gas Value not updated 9 1 Gas Value Age In seconds since last update Initial and max value 0xffff 10 1 Sensor Data Age Age since last message containing data from this sensor in seconds Initial and max value 0xffff 11 1 I O State 255 unknown 0 Warm up 1 Ready 2 Trouble 3 Cal Setup 12 1 Alarm Latched Statu...

Страница 17: ...larm messages reported 3 INFRA_GAS_VALUE_MSG_RECV Number of Gas Value messages reported 4 INFRA_GAS_VALUE_WITH_ALARM_MSG_RECV Number of Gas value as well as Alarm messages reported 5 INFRA_LOCK_MSG_RECV Number of Lock messages reported 6 INFRA_BLANK_MSG_RECV Number of Blank messages reported 10 INFRA_ST_0xB1_49_RECV_DISC Number of discarded messages starting with 0xB1 with length 49 bytes 11 INFRA...

Страница 18: ...figured Infra 4 Err Test file s not found In Simulation mode the driver can send messages from files indicated by the Map Descriptor name Check that the required file exists and that it is not in use by another application or change the mode from simulation to operation by deleting the parameter INFRA_SIMULATION from the CSV file INFRA 11 Err Illegal MD Function for Md s ψ Set Map Descriptor s fun...

Страница 19: ...hannel Manual Page 19 of 19 FieldServer Technologies 1991 Tarob Court Milpitas California 95035 USA Web www fieldServer com Tel 408 262 2299 Fax 408 262 9042 Toll_Free 888 509 1970 email support fieldServer com THIS PAGE INTENTIONALLY LEFT BLANK ...

Отзывы: