 GENISYS DESCRIPTION   

The  Genisys  driver  allows  the  transfer  of  data  to  and  from  devices  over  RS-232  Genisys  protocol.    Vital  Harmon 
Logic  Controller  (VHLC)  supports  Genisys  protocol.    IM-188  VHLC  GENISYS  SOFTWARE  MANUAL  100188-008 
AB0.PDF  is  the  basis  of  the  Genisys  driver.    The  FieldServer  can  be  configured  as  a  Client.  Limited  Server  side 
functionality has been implemented for FieldServer’s quality assurance requirements only. 

Max Nodes Supported 

FieldServer Mode 

Nodes 

Comments 

Client 

Only 1 virtual client per port allowed on multidrop systems. 

Server 

255 

Maximum device addresses pollable by Client – protocol limitation. 

 

2

 

DRIVER SCOPE OF SUPPLY 

2.1

 

Supplied by FieldServer Technologies for this driver  

FieldServer Technologies PART #  Description 
FS-8915-10 

UTP cable (7 foot) for RS-232 use 

FS-8917-04 

RJ45 to DB25F connector adapter 

FS-8700-133 

Driver Manual. 

 

Содержание Genisys FS-8700-133

Страница 1: ...r Company APPLICABILITY EFFECTIVITY Effective for all systems manufactured after January 2009 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 133 Genisys Driver Version 1 01 Document Revision 1 ...

Страница 2: ... 4 4 DATA ARRAY PARAMETERS 5 5 CONFIGURING THE FIELDSERVER AS A GENISYS CLIENT 6 5 1 Client Side Connection Descriptions 6 5 2 Client Side Node Descriptors 7 5 3 Client Side Map Descriptors 8 5 3 1 FieldServer Related Map Descriptor Parameters 8 5 3 2 Driver Related Map Descriptor Parameters 8 5 3 3 Timing Parameters 8 5 4 Map Descriptor Example Read Indications 9 5 5 Map Descriptor Example Write ...

Страница 3: ...100188 008 AB0 PDF is the basis of the Genisys driver The FieldServer can be configured as a Client Limited Server side functionality has been implemented for FieldServer s quality assurance requirements only Max Nodes Supported FieldServer Mode Nodes Comments Client 1 Only 1 virtual client per port allowed on multidrop systems Server 255 Maximum device addresses pollable by Client protocol limita...

Страница 4: ...2269 Toll Free 888 509 1970 email support fieldserver com 3 HARDWARE CONNECTIONS The FieldServer is connected to the VHLC as shown in the following connection drawing Port C VHLC RS 232 Interface Module DB25F 7 3 2 8 7 6 5 4 3 1 VHLC Server RJ45 FieldServer 2 Tx GND Rx FS 8915 10 8917 04 FieldServer RJ45 Connect to one of the RS 232 Ports on the FieldServer P1 1 8 ...

Страница 5: ... storage of the relevant data Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format FLOAT BIT UInt16 SInt16 Packed_Bit Byte Packed_Byte Swapped_Byte Data_Array_Length Number of Data Objects Must be larger than the data storage area re...

Страница 6: ... the destination device addresses need to be declared in the Client Side Nodes section and the data required from the Servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional parameter with the bold legal value being the default 5 1 Client Side Connection Descriptions Section Title Connections C...

Страница 7: ...isys Connection Specify which port the device is connected to the FieldServer P1 P8 1 Genisys_Check_Controls If OFF the FieldServer configures VHLC to apply controls from the FieldServer without verification If ON the FieldServer configures VHLC to verify controls supplied by the FieldServer before applying OFF ON Genisys_Intra_Poll_Delay Specify time that FieldServer should wait before sending AC...

Страница 8: ...al Values Node_Name Name of Node to fetch data from One of the Node names specified in Client Node Descriptor above Data_Type Bit each byte of Indication statuses will be stored in 8 consecutive locations in the Data Array Similarly while writing Control byte will be composed from 8 consecutive locations of the Dara Array Byte each byte of Indication statuses will be stored as an 8 Bit Integer at ...

Страница 9: ...e is Byte any location in Data Array will hold one indication word from VHLC If Data_Type is Bit eight consecutive locations in Data Array will hold one indication word from VHLC Also see Appendix A 1 Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Scan_Interval Data_Array_Name Data_Array_Offset Function Node_Name Data_Type Address Length CMD_01 1 00s DA_COS_01 0 COS_Poller Genisys...

Страница 10: ...HLC Data at 8 consecutive locations would be considered as one control word Also see Appendix A 1 Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Scan_Interval Data_Array_Name Data_Array_Offset Function Node_Name Data_Type Address Length CMD_01b DA_8O_01 0 Wrbx Genisys_01 Byte 0 32 CMD_02 DA_DO_01 0 Wrbx Genisys_02 Bit 0 256 Name of one of the Data Arrays defined in Data_Array sect...

Страница 11: ...t Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 6 CONFIGURING THE FIELDSERVER AS A GENISYS SERVER The Server side has been implemented only for FieldServer s quality assurance requirements ...

Страница 12: ...e 888 509 1970 email support fieldserver com Appendix A Useful Features Appendix A 1 Storage Structure for Data Type Bit and Byte LSB bit in Indication Control Byte is the1 st status control value If the Data_Type is Byte and only the 1 st and 2 nd indication status values are 1 out of 8 statuses all others being zero the Driver will store a numeric value of 3 in the Data Array ...

Страница 13: ...ith function COS_Poller has been declared for a Node but the COS_Read Map Descriptor required to store the data is missing Edit configuration file and add Map Descriptor with COS_Read function GENISYS 3 FYI MD s length required d now Only d statuses will be stored The COS_Read Map Descriptor is of insufficient length to store all indication words from VHLC If all indication words need to be stored...