FS-8700-73 BACnet MSTP Driver Manual
Page 30 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]
CMD RPM 4
, Device
, Max_Info_Frames , Passive_Client , DA RPM
, 1
, N1 1
, 1
, 1
, -
, CMD RPM
CMD RPM 2
, AO
, -
, Passive_Client , DA RPM
, 2
, N1 1
, 8
, 4
, -
, CMD RPM
CMD RPM 1
, AO
, -
, Passive_Client , DA RPM
, 6
, N1 1
, 4
, 3
, -
, CMD RPM
Notes:
For the Present_Value property it is permissible to set a Map Descriptor length >1. This will cause a read of the Present_Value property of consecutive BACnet objects of
the type defined by this Map Descriptor
The number of properties that can be read or written at once is limited by the maximum APDU message length.
Message segmentation is not supported.
These map descriptors form part of the read transaction defined by
Map Descriptor CMD RPM above