4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node. The driver
uses the Node name to establish a
connection with the Server if the
Node_ID is non-zero.
If the Node_ID is zero then the driver
ignores the Node name when logging
onto the PLC and logs on using a
Null name. Thus by setting the
Node_ID to zero you can allow the
driver to log onto a Node whose
name is not known.
Up
to
32
alphanumeric
characters
Node_ID
The parameter is used to control how
the driver logs onto the PLC. Read
the notes above (Node_Name)
0,1
Protocol
Specify protocol used
SNP
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
2
Example
// Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Port
PLC 1,
1,
SNP,
P8
4.4.
Client Side Map Descriptors
4.4.1.
FieldServer Related Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up
to
32
alphanumeric
characters
Data_Array_Name
Name of Data Array where
data is to be stored in the
FieldServer
One of the Data Array names
from “Data Array” section
above
Data_Array_Offset
Starting location in Data Array
0 to maximum specified in
“Data Array” section above
Function
Function
of
Client
Map
Descriptor
RDBC, WRBC, WRBX
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.