FS-8700-41 Simplex 4100 Driver Manual 

 

 

 

 

 

 

Page 33 of 48 

FieldServer Technologies

 1991 Tarob Court Milpitas, California 95035 USA   

Web

: www.fieldserver.com 

Tel

: (408) 262 2299   

Fax

: (408) 262 2269   

Toll Free

: (888) 509 1970   

email

[email protected] 

Keyword 

Description 

Function 

Show 

Each type of Simplex device reports a different set of attributes 
and  attribute  states/values.    Refer  to  Appendix  A.2.1  for  more 
information.    The  driver  analyses  the  response  from  the  poll.  
When an attribute is recognized, the attribute state is evaluated.  
If this is recognized then the driver stores a value, corresponding 
to the attribute state, at an array location corresponding to the 
attribute.  Appendix  A.2  provides  additional  information.    The 
driver can only recognize attributes and attribute states that it is 
programmed to recognize. 
The length of the Map Descriptor must be set equal to the array 
position of the highest attribute. 
Ensure  that  Map  Descriptors  using  this  function  do  not  use 
overlapping areas of the Data Arrays.  See example in  Appendix 
A.4.8. 

RDBC 
Specify c-p-s in the Map Descriptor. 

Setd 

This command allows the user to manipulate the status and/or 
priority of a control point 
The  port  access  level  must  be  set  appropriately  in  the  Simplex 
device otherwise the device returns an error. 

WRBC 
Specify c-p-s in the Map Descriptor. 

Seta 

This command allows the user to: 
Manipulate the status and/or priority of a control point 
Modify the value of an analog pseudo point. 
Set the sensitivity of a TrueAlarm sensor 
Set the rate-of-rise threshold of a TrueAlarm heat sensor 
Select the audio channel of a speaker circuit 

WRBC 
Specify c-p-s in the Map Descriptor. 

Xpoint 

This  is  an  unsolicited  message  sent  automatically  by  a  Simplex 
device  to  report  a  change  in  point  status.    The  card-point-sub 
address format is used to calculate an offset into the associated 
Data  Array  as  described  in  Appendix  A.1.    The  state  being 
reported  determines  the  value  being  written  into  the  Data 
Array. Refer to  Appendix B.4 for more information.. 

Passive 
Specify c-p-s in the Map Descriptor. 

Disable 

Not Implemented 

 

Restart 

Not Implemented 

 

Time 

This  command  sets  and  displays  the  time  and  date  in  "user" 
format.   
As  a  command  it  sets  the  hour  minute  second  of  the  Simplex 
device by getting the values from the Data Array associated with 
the  Map  Descriptor.  The  first  element  contains  the  hour,  the 
second the minute and the third contains the second.  A 24 hour 
clock is assumed. 
As  a  query,  the  data  is  unpacked  into  the  Data  Array  in  the 
format described above. 

RDBC (Query) or WRBC (Set) 
Do not specify c-p-s in the Map Descriptor. 

Ctime 

As  a  command  it  sets  the  hour  minute  second  of  the  Simplex 
device by getting the values from the Data Array associated with 
the  Map  Descriptor.  The  first  element  contains  the  hour,  the 
second  the  minute,  the  third  element  contains  the  second, the 
4th  contains  the  day of  the  week,  the  5th  contains the  month, 
the  6th  contains  the  day  of  the month  and  the  7th  element  of 
the array contains the year (value 01 indicates 2001).  A 24 hour 
clock is assumed. 

RDBC (Query) or WRBC (Set) 
Do not specify c-p-s in the Map Descriptor. 

Содержание FS-8700-41

Страница 1: ...A Sierra Monitor Company APPLICABILITY EFFECTIVITY Effective for all systems manufactured after December 2009 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 41 Simplex Time Recorder Company 4100 Computer Port Protocol ...

Страница 2: ... 3 2 Driver Specific Map Descriptor Parameters 12 5 3 3 Card Point Sub Addressing Map Descriptor Parameters 12 5 3 4 Timing Parameters 13 5 3 5 Map Descriptor Example 1 Read Panel Time 14 5 3 6 Map Descriptor Example 2 Write Panel Time 14 5 3 7 Map Descriptor Example 3 Panel Revision Information 14 6 Configuring the FieldServer as a Simplex Time Recorder Company 4100 Computer Port Protocol Server ...

Страница 3: ... Write Through and Store point status from Unsolicited Messages 29 Appendix B Troubleshooting 30 Appendix B 1 Address Errors 30 Appendix B 2 Driver Limitations 30 Appendix B 3 Resolving Network Addresses above 255 30 Appendix B 4 Simulation of the Xpoint command 31 Appendix B 5 Simplex Port Vectoring 31 Appendix C Reference 32 Appendix C 1 Simplex Address Formatting Specific Keywords 32 Appendix C...

Страница 4: ...devices The driver is also capable of polling for point and panel status data and some additional data such as the panel s time and revision information In addition the driver is capable of setting some control points in the panel acknowledging and resetting alarms and writing data where permitted to some analog and discrete points This is a client only driver and is not capable of emulating a Sim...

Страница 5: ... cable with 25 pin male connector 4100u Panels SPA59132 RS 485 connection adapter 2 2 Provided by Supplier of 3rd Party Equipment To enable the 4100 Protocol the 4100 system supplied by the user must have a free RS 232 port dedicated for use with the computer device In most cases this is not included in the base configuration of the product provided by Simplex Time Recorder Company and must be add...

Страница 6: ...Bits 1 1 or 2 3 2 Sim4100U Panel Setting Default Options Baud Rate 9600 75 110 134 5 300 600 1200 1800 2000 2400 4800 9600 19200 Parity NONE 1 ODD EVEN MARK SPACE NONE Data Bits 8 7 or 8 Stop Bits 1 1 or 2 The following are the Simplex recommended connections to be used in cabling between the 4100 and the FieldServer device For the computer device the standard EIA signal description and the 25 pin...

Страница 7: ...269 Toll Free 888 509 1970 email support fieldserver com 3 3 Connection to a Simplex 4020 4100 Panel 3 3 1 Communication Board 3 3 2 Serial Connection 1 4 8 FS 8917 16 FieldServer P1 1 8 Pinouts FS X40 Function From Simplex Panel Terminal Block Rx RJ45 01 XMIT 6 Tx RJ45 08 RCV 8 GND RT45 04 GND 10 Card 4020 RS 232 2120 modem ready assembly Terminal Block Port A 1 5 Port B 6 10 ...

Страница 8: ...eb www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 3 4 Connection to a Simplex 4100U Panel FS 8717 07 Port B RS 232 Card Sim4100U Panel FieldServer P1 1 8 8917 07 FieldServer Part 8915 10 UTP cable Port B Port A Front of 4100U Panel Pin 2 White Pin 3 Blue Pin 7 Green ...

Страница 9: ...orrect storage of the relevant data Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format FLOAT BIT UInt16 SInt16 Packed_Bit Byte Packed_Byte Swapped_Byte Data_Array_Length Number of Data Objects Must be larger than the data storage a...

Страница 10: ...Port Protocol communications the driver independent FieldServer buffers need to be declared in the Data Arrays section the destination device addresses need to be declared in the Client Side Nodes section and the data required from the servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be found below Note that in the tables indicates an optional par...

Страница 11: ... Node_Name Provide name for Node Up to 32 alphanumeric characters Node_ID n a This parameter is IGNORED Keywords used to define the card sub point c p s are described in Appendix A 1 Protocol Specify protocol used Sim4100 Port Specify which port the device is connected to the FieldServer P1 P8 R1 R2 PLC_Type 4020 4100 panels with firmware version 9x or earlier 4100U panels with firmware version 10...

Страница 12: ... described in section 0 sim4100_func A keyword which controls the function being performed or the type of data being polled written Further notes on these keywords are provided in Appendix C 1 Ackall Setd Disable Restart Clistall Clist Time Ctime Ack Xpoint Seta Super Show Earths Value ClearAll 5 3 3 Card Point Sub Addressing Map Descriptor Parameters The Simplex Time Recorder Company 4100 Compute...

Страница 13: ...logies 1991 Tarob Court Milpitas California 95035 USA Web www fieldserver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 5 3 4 Timing Parameters Column Title Function Legal Values Scan_Interval Rate at which data is polled 0 1s ...

Страница 14: ... does not send a write message to the panel Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name sim4100_func Scan_Interval Length Time_Mapdesc DA_TIME 0 Wrbc Node_A CTime 30s 7 Time_Mapdesc DA_TIME 0 Wrbc Node_A Time 30s 7 5 3 7 Map Descriptor Example 3 Panel Revision Information Define the DA_REV_INFO array as format BYTE and if using RUINET to monitor this Data Array change ...

Страница 15: ... CONFIGURING THE FIELDSERVER AS A SIMPLEX TIME RECORDER COMPANY 4100 COMPUTER PORT PROTOCOL SERVER The driver contains some server side functionality which has been developed to meet FieldServer s continuous quality assurance efforts However the server side functions are not documented or supported for customer use If you have a strong requirement for this functionality then please contact the Sal...

Страница 16: ...ained in the table below Subpoints point Calculated Offset Sim4100_sub 0 1 2 3 4 5 6 1 s per p implies s 0 every time c 0 0 c 1 0 c 2 0 c 3 0 c 4 0 c 5 0 c 6 0 2 s per p implies s 0 1 for each p c 0 0 c 0 1 c 1 0 c 1 1 c 2 0 c 2 1 c 3 0 5 s per p implies s 0 1 2 3 4 for each p c 0 0 c 0 1 c 0 2 c 0 3 c 0 4 c 0 5 c 1 0 x s per p implies s 0 1 x 1 c 0 0 c 0 1 c 0 2 c 0 3 c 0 4 c 0 5 c 0 6 Thus the o...

Страница 17: ...se messages and converts the data to numbers which can be sent to Client devices using another protocol The driver performs the following tasks in analyzing the response On a line by line basis from the left it searches for an attribute against a table of attribute strings If an attribute string is found processing continues Otherwise the line is discarded The attribute number is used to determine...

Страница 18: ... 7 2 CURRENT DEVICE 8 1 DEVICE 9 1 TEST STATE 10 1 PRESENT SENSITIVITY SELECTED 11 2 PRESENT SENSITIVITY SELECTED 11 2 AVERAGE VALUE 14 3 AVERAGE VALUE 14 3 AVERAGE 14 2 AVERAGE 14 2 AVERAGE 14 2 VALUE 17 2 VALUE 17 2 PEAK 20 2 PEAK 20 2 TROUBLE THRESHOLD 23 1 OUTPUT STATE 24 1 OUTPUT STATUS 25 1 DETECTOR SOUNDER 26 1 Attribute Array Position Method ALARM TEMPERATURE SELECTED 27 2 DETECTOR RELAY 3...

Страница 19: ...r recognizes Physical State as attribute 2 and uses method 1 to evaluate the rest of the line The attribute state SHORT has a value of 8 The number 8 is stored at location 2 in the Data Array VALUE 77 0 OF ALARM 1 0 SMOKE The Driver recognizes VALUE as attribute 17 and uses method 2 to evaluate the rest of the line The Driver stores the values 77 0 and 1 0 in three consecutive locations starting a...

Страница 20: ...ate value for storage in the Data Array 1 2 3 May not be zero Appendix A 3 2 Show Response Attribute States Driver Table Column Title Function Legal Values Protocol Specify protocol used Sim4100 sim4100_Attr_State_Name Use this parameter to extend this list of predefined attribute states Define a state word such as Normal and associate a value using the value parameter sim4100_Attr_State_Value Thi...

Страница 21: ...Read Point Status This Map Descriptor can be used to poll for the status of a particular point When the response is obtained the driver sets the value of one Data Array element to a number indicating the point s status The values are described in One Map Descriptor is required for every point polled Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Length Scan_Interval sim41...

Страница 22: ...quired for storage of Xpoint messages from each card For a given card the driver uses a mapping function based on the point subpoint address to determine the array location to store the state for the c p s Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name sim4100_func sim4100_card sim4100_point sim4100_sub Length A1 DA_AI3 0 Passive Node_A xpoint 1 0 10 1000 The Data extract...

Страница 23: ...alarm 4th ack P Priority 2 5th ack S Supervisory 6th ack T Trouble Set the array element to 1 to initiate the command The FieldServer clears the value on completion Appendix A 4 5 Acknowledge a specific point One Map Descriptor is required for each c p s combination requiring specific acknowledgements The driver checks the array location corresponding to the Map Descriptor If the value is non zero...

Страница 24: ...card 3 reports information then the driver uses array elements 6 7 to store information for this card Obtain the array location by multiplying the card number by two If the card reports positive and negative earth data then the driver stores the positive earth data at location 6 and the negative earth data at location 7 If the card reports earth ground state information without the keywords Positi...

Страница 25: ... Map Descriptor by setting the length to 100 Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Length Scan_Interval sim4100_Func Sim4100_Card Sim4100_Point Sim4100_Sub Show_mapdesc1 DA_SHOW 0 Rdbc Node_A 100 1 0s Show 1 2 3 By way of example assume that point 1 2 3 is a Heat Detector and the response to the show query is as follows 40 Character Custom Label Mx y 2 HEAT DETEC...

Страница 26: ...ponse is analysed because the attributes corresponding to these locations were not reported in the response to the query 3 RAW STATE 4 ACTIVE STATE 5 ARMED STATE 6 ENABLED STATE 11 Enabled 1 7 UNVERIFIED 0 1 8 CURRENT DEVICE 4 Correct Device 1 9 DEVICE 12 On_Line 1 10 TEST STATE 3 Self test normal 1 11 PRESENT SENSITIVITY SELECTED 14 AVERAGE 17 VALUE 0 1 18 41 1 19 Room for up two three numbers fo...

Страница 27: ...pseudo points Analog Psuedo points Map Descriptor Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Sim4100_Func Sim4100_Card Sim4100_Point Sim4100_Sub Protocol Length Fire Alarms DA_C_144 0 Rdbc Simplex_01 value 144 0 0 sim4100 1 Supervisory Alarms DA_C_144 1 Rdbc Simplex_01 value 144 1 0 sim4100 1 Troubles DA_C_144 2 Rdbc Simplex_01 value 144 2 0 sim4100 1 Excessively Dirt...

Страница 28: ... 0 through C 2 255 points 257 to 512 Refer also to Appendix B 3 Appendix A 6 Synchronizing the FieldServer with the Panel Appendix A 6 1 Using the Xpoint Function When using the Xpoint function to store point states each time the panel does a warm start it sets all point states to normal and then starts evaluating each one Thus the FieldServer will receive Xpoint messages from the panel for every ...

Страница 29: ... the point is not a read only point and the Panel s access level has been set appropriately When an unsolicited message is received from the panel it would normally be stored using a Map Descriptor with the Xpoint function See section Appendix A 4 3 However if polling for the status of that point using a Clist Map Descriptor with Store_Unsolicited set to yes then omit the Xpoint Map Descriptor as ...

Страница 30: ...ons Other than being able to write through a Map Descriptor where the sim4100_func clist write throughs are not supported by this driver Port expansion is not supported Appendix B 3 Resolving Network Addresses above 255 The Standard format for addressing a simplex point is c p s Card Point Subpoint Each of these components in the address supports a maximum value of 255 However when using an NDU Ne...

Страница 31: ...m4100_func xpoint keyword is used to parse unsolicited point status change messages sent by Simplex devices For simulation purposes a Wrbc version of this function has been implemented to test the response parsing ability of the slave portion of the driver Appendix B 5 Simplex Port Vectoring The 4100 panels do not automatically send event messages xpoint messages to the serial port card An explici...

Страница 32: ...ptor Ack This command allows the user to acknowledge a single point The specified Data Array is inspected and the value of the single element is used to determine which device state s are ack d Refer to Appendix A 4 5 WRBC Specify c p s in the Map Descriptor Clist This command returns the current point status for one point Refer to Appendix A 6 2 RDBC Specify c p s in the Map Descriptor Earths 5 T...

Страница 33: ...do point Set the sensitivity of a TrueAlarm sensor Set the rate of rise threshold of a TrueAlarm heat sensor Select the audio channel of a speaker circuit WRBC Specify c p s in the Map Descriptor Xpoint This is an unsolicited message sent automatically by a Simplex device to report a change in point status The card point sub address format is used to calculate an offset into the associated Data Ar...

Страница 34: ...in the Map Descriptor Errors Use this keyword to define a Map Descriptor which tells the driver where to store error messages received from the Simplex device The most recent message is stored in the Data Array specified Make sure that the Data Array length is long enough to store enough meaningful information A length of 200 is recommended Passive Do not specify c p s in the Map Descriptor If usi...

Страница 35: ...chnologies Sim4100 10 Invalid point status s v a Hex x x x c c c Please report his message to FieldServer Technologies noting the values in braces Sim4100 11 Error Array too short rqd d max d act d MapDesc s Data Abandoned Subsequent msgs suppressed Check the CSV file Data Array lengths Sim4100 12 Error Incoming data is being abandoned Subsequent message supressed Check the CSV file there was no m...

Страница 36: ...nt that you mention seeing this message in the Error Buffer when reporting the problem Sim4100 20 FYI Data abandoned Array too short MapDesc s Check the CSV file Data Array lengths Sim4100 21 Error Data abandoned Array too short c p s d d d Check the CSV file Data Array lengths Sim4100 22 FYI Polling Inhibited Polling is disabled until the port supervision message has been received This message ca...

Страница 37: ...nologies for additional support Sim4100 48 FYI User added SHOW attr state s value d Sim4100 49 Err No space Driver rejects SHOW attr state s value d No space is available in internal driver table Contact FieldServer Technologies for additional support Sim4100 50 Err Duplicate Driver rejects SHOW attr state s value d Duplicate found in internal driver table Contact FieldServer Technologies for addi...

Страница 38: ... of messages and they are not being processed by the driver fast enough A panic is printed immediate after this message The driver will clear the buffer and start capturing new bytes as they arrive Messages may have been lost We advise that you re synch the panel This error has only been seen once It occurred when a panel was connected to the driver with the wrong connection settings Appendix C 3 ...

Страница 39: ... store 13 SIM4100_STAT_XPOINT_QUALIFIER The Qualifier from most recent xpoint store 14 SIM4100_STAT_XPOINT_QUALIFIER_AS_ENUM The Qualifier from most recent xpoint store stored as an enumeration See Note1 for bit states 15 SIM4100_STAT_XPOINT_STATE The reported state from most recent xpoint store State value 0 FALSE Normal 1 TRUE Abnormal 16 SIM4100_STAT_XPOINT_ACK_STATE The reported ack state from...

Страница 40: ...reporting smoke Every Simplex system has a number of default pseudo points programmed into the firmware supplied with the panel These default points depend only on the firmware revision number and are generally unaffected by the configuration programmed for a particular site Although the 4100 card number can range from 0 250 in theory only the following ranges are presently used in the system Card...

Страница 41: ...GROUP 1 ACTIVE UTILITY 128 25 0 P26 CODING GROUP 2 ACTIVE UTILITY 128 26 0 P27 CODING GROUP 3 ACTIVE UTILITY 128 27 0 P28 CODING GROUP 4 ACTIVE UTILITY 128 28 0 P29 CODING GROUP 5 ACTIVE UTILITY 128 29 0 P30 CODING GROUP 6 ACTIVE UTILITY 128 30 0 P31 CODING GROUP 7 ACTIVE UTILITY 128 31 0 P32 COLD START TROUBLE 128 32 0 P33 WARM START TROUBLE 128 33 0 P34 CITY DISCONNECT TROUBLE 128 34 0 P35 MANUA...

Страница 42: ...BLED TROUBLE 128 71 0 P72 WALK TEST GROUP 2 ENABLED TROUBLE 128 72 0 P73 WALK TEST GROUP 3 ENABLED TROUBLE 128 73 0 P74 WALK TEST GROUP 4 ENABLED TROUBLE 128 74 0 P75 WALK TEST GROUP 5 ENABLED TROUBLE 128 75 0 P76 WALK TEST GROUP 6 ENABLED TROUBLE 128 76 0 P77 WALK TEST GROUP 7 ENABLED TROUBLE 128 77 0 P78 ALARM SILENCE ALARM CUTOUT PSEUDO UTILITY 128 78 0 P79 RESET SPKRS WHEN AUDIO CODING COMPLET...

Страница 43: ...P122 ALL SPEAKERS CHANNEL 3 LED UTILITY 128 122 0 P123 LOCAL SPEAKER EVAC ON UTILITY 128 123 0 P124 LOCAL SPEAKER EVAC OFF UTILITY 128 124 0 P125 LOCAL SPEAKER EVAC LED UTILITY 128 125 0 P126 LOCAL SPEAKER ALERT ON UTILITY 128 126 0 P127 LOCAL SPEAKER ALERT OFF UTILITY 128 127 0 P128 LOCAL SPEAKER ALERT LED UTILITY 128 128 0 P129 ALL SPEAKERS TALK ON UTILITY 128 129 0 P130 ALL SPEAKERS TALK OFF UT...

Страница 44: ...G WHEN MICROPHONE KEYED UTILITY 128 167 0 P168 MICROPHONE TO EVAC IN EFFECT UTILITY 128 168 0 P169 MICROPHONE TO ALERT IN EFFECT UTILITY 128 169 0 P170 MICROPHONE TO TALK CHANNEL 3 IN EFFECT UTILITY 128 170 0 P171 BACKGROUND MUSIC RELAY CHANNEL 1 UTILITY 128 171 0 P172 BACKGROUND MUSIC RELAY CHANNEL 2 UTILITY 128 172 0 P173 BACKGROUND MUSIC RELAY CHANNEL 3 UTILITY 128 173 0 P174 VTG 1 CODE S PRECO...

Страница 45: ...RITY 2 ALARM DETECT UTILITY 128 215 0 P216 PRIORITY 2 ALARM RESET REQUEST UTILITY 128 216 0 P217 NETWORK SIGNAL SILENCE UTILITY 128 217 0 P218 UNACKNOWLEDGED PRIORITY 2 ALARM EXISTS UTILITY 128 218 0 P219 MASTER PRIORITY 2 ALARM ACK KEY UTILITY 128 219 0 P220 NETWORK PRIORITY 2 RESET UTILITY 128 220 0 P221 SIGNALS ACTIVE OFF ON SILENCE UTILITY 128 221 0 P222 REMOTE DOWNLOAD ENABLED TROUBLE 128 222...

Страница 46: ...OG 144 23 0 A24 FIRE ALARM CUTOUT TIMER TIMER 144 24 0 A25 FIRE ALARM CUTOUT TIMER SETPOINT ANALOG 144 25 0 A26 FIRE ALARM CUTOUT SILENCE PULSE TIMER TIMER 144 26 0 A27 TROUBLE REMINDER CYCLE TIMER TIMER 144 27 0 A28 TROUBLE REMINDER OFF TIME SETPOINT ANALOG 144 28 0 A29 TROUBLE REMINDER ON TIME SETPOINT ANALOG 144 29 0 A30 DOOR HOLDER ALARM DROP TIMER TIMER 144 30 0 A31 DOOR HOLDER ALARM DROP TIM...

Страница 47: ...2 ROUTING PRIORITY ANALOG 144 71 0 A72 CHANNEL 3 ROUTING PRIORITY ANALOG 144 72 0 A73 LOCAL SPEAKER ROUTING PRIORITY ANALOG 144 73 0 A74 AUDIO SUPERVISION PULSE TIMER VTG1 TIMER 144 74 0 A75 AUDIO SUPERVISION PULSE TIMER VTG2 TIMER 144 75 0 A76 ENABLE DISABLE STATISTIC GROUP ANALOG 144 76 0 A77 ENABLE DISABLE STATISTIC OUTPUT PORT ANALOG 144 77 0 A78 5 SEC TIMER FOR REMOTE MASTER PHONES TIMER 144 ...

Страница 48: ...E SETPOINT ANALOG 144 111 0 A112 GROUND TROUBLE COUNTER COUNTER 144 112 0 A113 PAGING CHANNEL ANALOG 144 113 0 A114 TRUEALARM MODIFICATION COUNTER COUNTER 144 114 0 A115 EXCESSIVELY DIRTY OUT OF RANGE ANALOG 144 115 0 A116 DIRTY SENSOR COUNTER COUNTER 144 116 0 A117 ALMOST DIRTY COUNTER COUNTER 144 117 0 A118 ALARMS SILENCED DELAY TIMER TIMER 144 118 0 A119 NUMBER OF LOCAL SYSTEM POINTS TROUBLES C...

Отзывы: