FS-8700-103_ATMI_TGM_Serial
Manual
Page
14
of
28
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-9042
Toll_Free
: 888-509-1970
Appendix A.2. Malfunction Table
When an event is reported in the Incident Report (QIR) then the driver compares the event
description to text in the table below. If the text matches an an entry in the ‘Malfunction’
column (and is preceeded by the string MALFUNC) then the Data Array element at the
specified offset is set to 1. If the text matches the ‘Return to Normal’ text then the
malfunction is considered as cleared and the Data Array element is set to zero.
The Data Array elements are all set to zero when
Event 19 reports ” ALARM RESET “
or
Event 37 reports “ALL MALFUNCTIONS CLEAR”
The Malunction text strings generated by the TGM unit are not the same for all units. They
can be customized in theTGM’s config.dat file. For this reason, this driver allows the strings
in the table below to be customized too – see Appendix B.5. In addition to allowing this
table to be customised in the configuration file, the driver can use a config.dat file to directly
customise the table – see Appendix B.7
Offset
Malfunction
Return to Normal
20
BASELINE OUT OF RANGE
BASELINE BACK TO NORMAL
22
IGNITER SWITCH IS ON
IGNITER SWITCH IS OFF
24
FLAME IGNITION DISABLED
FLAME IGNITION ENABLED
26
LOW VACUUM
VACUUM BACK TO NORMAL
28
FLAMEOUT RESTART
FLAMEOUT BACK TO NORMAL
30
LINE LEAK TEST MALFUN
LINE LEAK BACK TO NORMAL
32
POWER FAILURE
POWER RESTORED
38
FAILED TO LOAD PROGRAM
39
DPM TIMEOUT
DPM BACK TO NORMAL
41
RELAY FILE ERROR
OPERATIONS CHECK DONE
45
CHECK I/O AND FUSES
I/O AND FUSES OK NOW
47
TGM IN DEBUG MODE
48
DISK NEARLY FULL
ADEQUATE DISK STORAGE NOW
50
FLAMEOUT CONDITION
RETURN FROM FLAMEOUT
52
FAILED FLAME TEST
FLAME TEST OK NOW
54
FAILED RESPONSE TEST
RESPONSE TEST OK NOW
56
FAILED BLOCK LEAK CHECK
BLOCK LEAK CHECK OK NOW
58
ANALOG SUBSYSTEM FAILURE
ANALOG SUBSYSTEM NORMAL
60
ANALOG CHANNEL FAILURE
ANALOG CHANNEL NORMAL
62
PRINTER OFF LINE
PRINTER BACK TO NORMAL
64
REMOTE OFF LINE
REMOTE BACK TO NORMAL
66
DISK READ/WRITE ERR
DISK BACK TO NORMAL
68
LAN READ/WRITE ERROR
LAN BACK TO NORMAL
70
DISK FULL - DATA LOST
DISK NO LONGER FULL
75
HIGH SAMPLE VARIANCE
SAMPLE VARIANCE OK NOW
80
COUS SENSOR TIMEOUT
COUS TIMEOUT CORRECTED
82
COUS GETTER INOPERATIVE
COUS GETTER OK NOW
84
ACOUSTIC SENSOR FAILURE
ACOUSTIC SENSOR RECOVERD
86
GETTER TEMPERATURE LOW
GETTER TEMPERATUR OK NOW
88
LOW SAMPLE FLOW
SAMPLE FLOW OK NOW
90
TGM HYDROGEN LEAK
HYDROGEN LEAK REPAIRED