FS-8700-123 MetOne Particle Counter Driver Manual
Page 20 of 22
FieldServer Technologies
1991 Tarob Court Milpitas California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
Message
Description
MET1:#08a
Err.
Invalid
time
string=%s
MET1:#08b
Err.
Invalid
time
string=%s
Printed by the Server side of the driver. See notes for #4.
MET1:#09a Err. Met1_Function=%d
is unknown. MD=%s
The reported Map D has a Met1 function not recognized by the driver. This
should never happen. Take a log and send a copy of the log and your
configuration to Tech Support. The FieldServer web site provide tools and
instructions for taking logs
Met1:#10 FYI. No place to store
label data. Label=%s MD=%s
This messages is printed a maximum of 15 times and then suppressed.
Where the label method is being used to store data. (See section 5.12) then
this message is printed if the driver can’t find an Map Descriptor with a
label which matches the reported label found in the message from the field
device.
The message is printed simply to alert users to what count labels are being
returned. Passive Map Descriptors can be created to store the reported
data or the message could be ignored.
MET1:#11a Err. Diagnostic 6
MET1:#11b Err. Diagnostic 1
MET1:#11c Err. Diagnostic 4
MET1:#11d Err. Diagnostic 2
MET1:#11e Err. Diagnostic 7
Printed by the Server side of the driver. These are printed when internal
diagnostics are triggered. This should never be the case in an operational
system. Take a log and contact Tech Support. The FieldServer web site
provide tools and instructions for taking logs
MET1:#12 FYI. Use an Array called
<%s> to expose diagnostic info.
This message can be ignored. For more information read Appendix B.2
MET1:#13 Err. Node=%d cant be
selected because not defined in
config.
The reported device could not be selected because there isnt a node
descriptor whose Node_ID matches the reported device.
3
"Met1:#14
FYI
Poll_Delay
overridden to %d
The driver has set the default poll delay to the reported value. This setting
can be overridden in the configuration file.
3
Met1:#15 Err. Set MD Length=%d
The driver has determined that the Length parameter is too small. The
reported length is the driver suggestion.
3
Met1:#16 Err. Set MD Length
The parameter called Length must be specified for each Map Descriptor. It
tells the FieldServer how much Data Array space to reserve. Review the
Map Descriptor examples in this manual.
3
MET1:#17 Err. MD too long Max=%u
Review the Map Descriptor examples in this manual.
3
MET1:#18 Err. Invalid Port=%d. Valid
Range=0-63
Invalid entry for port.
3
MET1:#19
Err.
Invalid
SubDevice=%d. Valid Range=1-64
Invalid entry for SubDevice
3
MET1:#20 Err. Met1_Function not
specified
The parameter “Met1_Function’ must be specified for every Map
Descriptor. Refer to Section 5.3.2 as well as Map Descriptor examples
provided in Chapter 4.
3
MET1:#21 Err. Met1_Function='%s'
not recognized
3
Update the configuration file download the modified configuration file and reset the FieldServer for the changes to take effect