Execute the Traverse

1.

Determine the appropriate measurement 

points by measuring either the diameter of 

the duct or the width and height. Then use the 

appropriate table (See table 1 and 2) to calculate 

the insertion depth where each of the point 

measurements should be recorded.

2.

Insert the probe of the STA2 into the duct and 

use the flat edges of the probe to position the 

probe tip so air flows directly past the sensor. 

Check that the direction of airflow is at 90° to the 

probe by making sure that the wand itself is at a 

right angle to the side of the duct.

90°

90

85

80

90°

90

85

80

3.

Use the laser etched ruler on the side of the 

probe to measure the insertion depth and find 

the locations you determined in step 1. 

4.

Press the ENTER button to record a point 

measurement at each of the locations 

determined in step 1. 

5.

Press the Average button to display the 

calculated average of all recorded points. Then 

use the arrow buttons to cycle display between, 

average temperature, velocity and airflow. 

Proper Measurement

Points for Rectangular/

Square Ducts

TABLE 1

Traverse locations using log-Tchebycheff rule in a rectangular duct

Length of Side

# of Traverse Lines

Distance from Inner Wall in % of Length of Side

< 30 in (76 cm)

5

7.4%, 28.8%, 50%, 71.2%, 92.6%

30-63in (76-160cm)

6

6.1%, 23.5%, 43.7%, 56.3%, 76.5%, 93.9%

>63in (160cm)

7

5.3%, 20.3%, 36.6%, 50%, 63.4%, 79.9%, 94.7%

Proper Measurement

Points for Round Ducts 

TABLE 2

Log linear rule for traverse points on two diameter for a round duct

Diameter

# of points per diameter

Distance from inner wall in % of diameter

<10in (25.4cm)

6

3.2%, 13.5%, 32.1%, 67.9%, 86.5%, 96.8%

≥ 10in (25.4cm)

10

1.9%, 7.7%, 15.3%, 21.7%, 36.1%, 63.9%

 

Specifications

Accuracy: 

Stated accuracy @ 73°F±9°F (23°C±5°C), 

<90%RH

Temperature coefficient:

  0.1 x (specified accuracy) 

per °C for 0°C to 18°C, 28°C to 50°C (32°F to 64°F, 

82°F to 122°F)

Operating environment:

 -4°F to 122°F (-20°C to 

50°C) at <75%RH

Storage temperature:

 -4°F to 140°F (-20°C to 60°C), 

0 to 80% RH (with battery removed)

Battery:  

9V

Battery life:

  20-35 hours approx. (alkaline)

Battery indication:

  

 is displayed when the 

battery voltage drops below the operating level.

Auto Power off: 

after 15 minutes of inactivity if APO 

is active.

Over range:  

"OL" or "-OL" is displayed

Dimensions:

 7.2 in (H) x 2.5 in (W) x 1.3 in (D) 

[185mm (H) x 65mm (W) x 35mm (D)]

Weight:

 12 oz. (340g) including battery

Velocity

Sensor type:  

Micro-glass bead thermistor.

Resolution: 

1 fpm (0.01 m/s)

Range:  

40-3960 fpm (0.20-20.00 m/s)

Accuracy:

 ± (5%+1 dgt) reading or ± (1%+1dgt) 

full scale 

Units:

 fpm, m/s, km/hr, mph

Temperature

Sensor type:  

Thermistor

Range: 

-4°F to 140°F (-20°C to 60°C)

Resolution: 

0.1°C, 0.1°F

Accuracy: 

±1.0°F for 32°F to 113°F

±2.0°F for -4°F to 32°F, 113°F to 140°F

±0.5°C for 0°C to 45°C

±1.0°C for -20°C to 0°C, 45°C to 60°C

Maintenance

Clean the exterior with a dry cloth.  

Do not use liquid.

Battery Replacement

When the meter displays 

 the 

battery should be replaced.  Turn your 

STA2 off and replace with 9V battery.

Protecting the Sensor

The STA2 uses a delicate glass bead 

thermistor sensor. When not in use it 

is best to protect this sensor with the 

vinyl slip cover included with the STA2 

and keep it stored in the provided 

blow molded case. 

Optional Accessory

RCONE1 being used 

to hold the STA2 

probe in place in 

round duct.

Limited Warranty

This meter is warranted against 

defects in material or workmanship 

for one year from date of purchase. 

Fieldpiece will replace or repair the 

defective unit, at its option, subject to 

verification of the defect.

This warranty does not apply 

to defects resulting from abuse, 

neglect, accident, unauthorized repair, 

alteration, or unreasonable use of the 

instrument.

Any implied warranties arising 

from the sale of a Fieldpiece product, 

including but not limited to implied 

warranties of merchantability and 

fitness for a particular purpose, are 

limited to the above. Fieldpiece shall 

not be liable for loss of use of the 

instrument or other incidental or 

consequential damages, expenses, or 

economic loss, or for any claim of such 

damage, expenses, or economic loss. 

State laws vary. The above limitations 

or exclusions may not apply to you.

For Service

In the USA, call Fieldpiece 

Instruments for one-price-fix-all out of 

warranty service pricing. Send check or 

money order for the amount quoted. 

Send the meter freight prepaid to 

Fieldpiece Instruments. Send proof 

of date and location of purchase for 

in-warranty service. The meter will be 

repaired or replaced, at the option of 

Fieldpiece, and returned via least cost 

transportation. Outside of the USA, 

please visit www.fieldpiece.com for 

service contact information.

6.

If the above steps were followed, the average 

flow number on your STA2 will be an accurate 

representation of the airflow through the 

traverse location you selected. 

7.

(Optional) More is better. If the traverse location 

you have selected is not ideal for any of the 

reasons listed above, it may be beneficial to 

conduct multiple traverses at different locations.

90°

(<10”)

(>10”)

W

H

0.032D

0.135D

0.321D

0.679D

0.865D

0.968D

0.019D

0.077D

0.153D

0.217D

0.361D

0.639D

0.061W

0.235W

0.437W

0.563W

0.765W

0.939W

0.926H

0.712H

0.500H

0.288H

0.074H

0.783D

0.847D

0.923D

0.981D

90°

(<10”)

(>10”)

W

H

0.032D

0.135D

0.321D

0.679D

0.865D

0.968D

0.019D

0.077D

0.153D

0.217D

0.361D

0.639D

0.061W

0.235W

0.437W

0.563W

0.765W

0.939W

0.926H

0.712H

0.500H

0.288H

0.074H

0.783D

0.847D

0.923D

0.981D

90°

(<10”)

(>10”)

W

H

0.032D

0.135D

0.321D

0.679D

0.865D

0.968D

0.019D

0.077D

0.153D

0.217D

0.361D

0.639D

0.061W

0.235W

0.437W

0.563W

0.765W

0.939W

0.926H

0.712H

0.500H

0.288H

0.074H

0.783D

0.847D

0.923D

0.981D

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

STA2

UNITS

CLEAR DATA

RECORD MODE

PRESS FOR

1 SECOND

In-Duct

Hot Wire

Anemometer

DUCT

ON/OFF

ENTER

HOLD

AVERAGE

MAX/MIN

AUTO-OFF

actoolsupply.com

actoolsupply.com

Отзывы: