background image

01

06

02

07

03

08

04

09

05

10

   

Pressure (bar)

   

Pressure (pounds/in

2

)

    Pressure (kilopascals or Megapascals)

   

Negative Pressure (inches of mercury)

    Negative Pressure (cm of mercury)

    

Subcooling 

    T2 Direct

    Liquid Saturation Temperature

    Outdoor Dry Bulb

   

Vacuum Stopwatch

 Hours:Minutes or Minutes:Seconds

   

Battery Life       

 Connection Strength

   

Auto Power Off Enabled

    Wireless Signal Lost

   

Selected Refrigerant of System

Quick Start

1  Power on your SMAN4 by holding the ON/

OFF button for 1 second.

2  Select desired units (English or Metric or a 

combination) by holding ENTER for 1 second.

3 Calibrate temperature and/or pressure as 

needed. See calibration sections for more 

details.

4  Connect to the system.

5  Press the circular button to select between 

Actual Superheat and Subcooling, Target 

Superheat, Direct Temperature Display (T1 T2 

Direct) or  Saturation Temperature Display.

Certifications

  

  

 

 

FCC ID:  VEARF915

 

 

C-Tick (N22675)

  

 

CE

 

 

RoHS Compliant

Description

Your SMAN4 is the first true wireless-

enabled digital refrigerant 4-port manifold and 

vacuum gauge for HVACR service. Use optional 

wireless transmitters to receive temperature 

measurements over-the-air for real-time 

target superheat calculations. Your SMAN4 can 

wirelessly send data to the HG3 HVAC Guide 

for more extensive analysis, data logging, or 

printing reports for your customers.

Your SMAN4 combines high precision, 

absolute pressure manifold gauges, a superheat/

subcooling calculator, true micron gauge for 

vacuum, and dual temperature measurements 

into one easy-to-use instrument. Your SMAN4 

calculates and simultaneously displays target 

superheat and actual superheat to ensure 

proper charging of a unit. Your SMAN4’s  4-port 

manifold has a large 3/8” vacuum port and 3/8” 

bore throughout the block for quicker recovery 

and evacuations. 

Your SMAN4 is designed to meet the demands 

of the HVACR technician with a ruggedized 

rubber boot for durability, a strong metal 

hanger for easy storage and a form fitting, water 

resistant, padded nylon pouch.

   

Pressure (bar)

   

Pressure (pounds/in

2

)

    Pressure (kilopascals or Megapascals)

   

Negative Pressure (inches of mercury)

    Negative Pressure (cm of mercury)

    

Superheat 

    T1 Direct

    Vapor Saturation Temperature

    Indoor Wet Bulb

    Micron Reading Has Stabilized

   

Set Mode 

    Alarm Mode

    

High Alarm 

   

Low Alarm

    Vacuum (Microns of Mercury)

  T1 thermocouple - T2 thermocouple

  Target Superheat

Fieldpiece

4-Port Wireless 

Manifold & Vacuum 

Gauge

OPERATOR'S MANUAL

Model SMAN4

 

Controls

 

1  Insert K-type thermocouple plugs here.

2  Temperature calibration pots.

3  Press to zero atmospheric pressure.

4  Press to calibrate to refrigerant tank.  

(See Advanced Pressure Calibration section.)

5  Press to turn on backlight. Hold when    

powering on to toggle Auto Power Off.

6  Press/hold to cycle through refrigerants.

7  Hold 1 second to toggle power on/off. 

8  Press up or down arrow to adjust values.

9  Press to confirm selection.  

Hold 1 second to adjust units.

10 Press to turn on/off the Hi/Lo vacuum  

alarms and hold to change alarm settings.

11 Press to toggle through temperature tests.

12 Hold 1 second to Sync to a wireless enabled partner device.

13 Turn clockwise to close High side port.

14 Turn clockwise to close Low side port. 

15 Turn clockwise to close 3/8" Vacuum port.

16 Turn clockwise to close Refrigerant port. 

Functions

Superheat and Subcooling

1   Press circular button to cycle through temperature modes until 

SH and SC are shown.  The SMAN4 can calculate and display both 

superheat and subcooling simultaneously. 

2   Select the appropriate refrigerant using the REFRIGERANT button.

3   Connect EPA approved refrigerant hoses to low and high side on 

SMAN4. Plug K-type thermocouple pipe clamps into T1 and T2. 

4   Connect your SMAN4 to the system:

 

Superheat: 

 Hand tighten low side hose to suction line service 

port. Place the T1 pipe clamp thermocouple on the suction line  

between the evaporator and compressor, no closer than 6 inches 

to compressor. 

 

Subcooling:

  Hand tighten high side hose to liquid line service 

port. Attach the T2 pipe clamp thermocouple on the liquid line 

between the condenser and expansion valve (TXV), as close to the 

service port as possible.

5   After turning the system on or making any adjustments to 

the system wait 15 minutes before charging by superheat or 

subcooling to ensure that the system is running normally. 

6  To add or remove refrigerant connect a refrigerant or recovery 

tank to the REF port on SMAN4. Follow charging or recovery 

practices from manufacturer. Use the low side, high side, and REF 

valves on SMAN4 to charge or recover refrigerant as needed. Let 

system stabilize again for 15 minutes.

T1 T2 Direct

1  Press circular button until T1 and T2 are shown.

2  Plug in any K-type thermocouple into T1 and/or T2.

3  Read the temperature directly from the display.

4  T1-T2 is displayed in the lower left corner of the display.

Saturation

Shows vapor (VSAT) and liquid (LSAT) saturation temperatures 

calculated from the pressures measured and the refrigerant selected.

Target Superheat

 

Target Superheat is only used for charging fixed orifice 

air conditioning systems.  Your SMAN4 allows you to receive 
real-time indoor wet bulb (IDWB) and outdoor dry bulb 
(ODDB) temperatures wirelessly to calculate target superheat. 
These values can also be entered manually or input directly by 
connecting the included wet and dry bulb thermocouples to T1 
and T2 respectively. 

Receive IDWB and ODDB temperatures wirelessly

1  Press circular button until you’ve entered Target SH mode.

2  Press UP or DOWN ARROW. 

IDWB

 icon will begin blinking.

3  Hold SYNC on SMAN4 until a beep is heard (>1 sec).

4  Attach an accessory head (like ARH5, ARH4, or AAT3) capable of 

measuring indoor wet bulb temperature to a Fieldpiece wireless 

transmitter (sold seperately). Ready accessory head to measure 

indoor wet bulb temperature and place at the return of the 

evaporator between the filter and the coil. 

5  Select transmit mode on Fieldpiece wireless transmitter and hold 

SYNC until wireless partner searching begins. Once SMAN4 is 

connected with transmitter, the real-time wet bulb temperature 

measurement will display on SMAN4. The ODDB icon will begin 

blinking.

Note:  The SMAN4 and Fieldpiece wireless transmitter must be within 

10 feet (3m) for initial sync to occur. Once synced, the wireless 

range is 100 feet (30m).

6  Repeat steps 3 -5 for outdoor dry bulb measurements (ODDB). For 

outdoor dry bulb measurement, place the accessory head onto 

the side of the condenser. For accurate results, keep it shaded 

from direct sunlight.

7  Real-time target superheat is calculated and displayed in lower 

left corner of display when SMAN4 is receiving real-time indoor 

wet bulb and outdoor dry bulb measurements from the wireless 

devices.

Note:  If the indoor wet bulb or outdoor dry bulb measurements are 

out of calculating range, "

OL

" or "

-OL

" will display in the lower 

left corner.

Note:  Retrieval of IDWB and ODDB wireless measurements will be 

temporarily disabled for 30 seconds (nSG will display) if SMAN4 

loses communication with the HG3. The wireless tower ( ) will 

blink and "NoSignal" will be displayed on SMAN4 display until 

HG3 re-connects or 30 seconds has elapsed. At this time, IDWB 

and ODDB measurements will be enabled again.

Input temperatures with K-type thermocouples

1  Press circular button until Target SH is shown on the bottom, 

center of display.

2  Plug ATWB1 Wet bulb K-type thermocouple into T1 and ATA1 Dry 

bulb K-type thermocouple into T2. Both are included with your 

SMAN4.

3  Press UP or DOWN ARROW to toggle between 

IDWB

 or 

ODDB

 

input. The icons will begin blinking. Press ENTER to select which 

temperature you want to input first, either 

IDWB

 or 

ODDB

. The 

real-time temperature from the thermocouple will be displayed.

4    For IDWB input, wet the sock of the ATWB1. Clip it to the return 

of the evaporator between the filter and coil. When the wet bulb 

temperature reaches its lowest point and stabilizes, press ENTER 

to lock the reading. If the inputted temperature is above or below 

the wet bulb range, "OL" or “-OL” will blink and a beep will be 

heard. Retake the measurement if this occurs.

5  For ODDB input, clip the ATA1 thermocouple to the side of the 

condenser. Once reading is stable, press ENTER. If the inputted 

temperature is above or below the dry bulb range, "OL" or “-OL” 

will blink and a beep will be heard. Retake the measurement if 

this occurs. For accurate results, keep the ATA1 shaded from direct 

sunlight.

6  Once both IDWB and ODDB are locked in, the Target Superheat 

will show in the lower left corner of the display. If the Target 

Superheat calculated from the IDWB and ODDB temperatures is 

outside the range in which air conditioning is recommended then 

“OL” is displayed. Usually, raising the indoor temperature will 

bring the conditions within manufacturer’s recommendations. If 

your target superheat is out of the recommended range, re-take 

your measurements.

7  To re-take either IDWB or ODDB, press UP or DOWN ARROW until 

the icon (

IDWB

 or 

ODDB

) you wish to re-take is blinking. Press 

ENTER. Re-do the measurement and press ENTER to lock it in. The 

newly calculated target superheat will be displayed.

Input temperatures manually

1  Press circular button until Target SH is shown at the bottom, 

center of display. 

Unplug thermocouples

 from T1 and/or T2.

2  Press UP or DOWN ARROW to toggle between 

IDWB

 or 

ODDB

 

input. The icons will begin blinking. Press ENTER to select which 

temperature you want to input first, either 

IDWB

 or 

ODDB

. The far 

left digit of 

IDWB

 or 

ODDB

 will begin blinking indicating manual 

input mode is ready. 

3  Press the UP or DOWN ARROW to change values and press ENTER 

to lock in each digit. Once the last digit for 

ODDB

 or 

IDWB

 is 

locked in, the calculated target superheat will show in the lower 

left corner of the display.

  Note:  When pressing ENTER to lock in the last digit for 

IDWB

 or 

ODDB

, if the inputted temperature is below or above the wet bulb 

or dry bulb range, "OL" or “-OL” will flash once and a beep will be 

heard. In both instances you must re-input the measurement.

1

1

2

2

3

14

16

4

5

8

9

11

10

12

6

7

13

15