Field Controls DUO-11/24V Скачать руководство пользователя страница 1

www.fi eldcontrols.com

Please retain these instructions after installation.

This device MUST be installed by a qualifi ed agency in accordance with the manufacturer's installation instructions. The defi nition of 
a qualifi ed agency is: any individual, fi rm, corporation or company which either in person or through a representative is engaged 
in, and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the 
precautions required, and has complied with all the requirements of the authority having jurisdiction.

This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or condition nor for 
use in the mitigation, treatment, or prevention of any disease or condition.

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

Installation Date:

Installed By:

Phone:

Models: DUO-11/24V, DUO-14/24V, PCUV-16UA

The Duo 24V models produce germicidal UVC Band light rays, which sterilize and reduce airborne 
microorganisms and reduce Volatile Organic Compounds (VOC’s) by a photocatalytic chemical reaction as 
air passes through a heating or air conditioning system.  It is installed in the main supply or return duct and 
operates continuously to automatically purify the air in the home 24 hours a day.

This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or 

condition, nor for use in the mitigation, treatment, or prevention of any disease or condition.

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY 

BEFORE PROCEEDING WITH THE INSTALLATION.

 

  WARNING: For use with 24V ONLY! Do not exceed voltage rating. Severe damage to device and or fi re  

 

  could result.  Verify proper voltage.

ITEMS INCLUDED IN KIT:

1-24Volt UV-Aire Ballast Assembly
1-Photo-Catalytic Duct Insert
1-UVC Germicidal Lamp
4-Sheet Metal Mounting Screws
1-Instruction Sheet
1-Duct Board Mounting Bracket
1-24V Transformer 
2-Fork Terminals
2-Wire Nuts

PHOTO-CATALYTIC AIR PURIFIER SYSTEMS

Содержание DUO-11/24V

Страница 1: ... 11 24V DUO 14 24V PCUV 16UA The Duo 24V models produce germicidal UVC Band light rays which sterilize and reduce airborne microorganisms and reduce Volatile Organic Compounds VOC s by a photocatalytic chemical reaction as air passes through a heating or air conditioning system It is installed in the main supply or return duct and operates continuously to automatically purify the air in the home 2...

Страница 2: ...do not touch lamp or other contents in carton Close carton and return to seller immediately In case of accidental exposure to internal contents of lamp wash hands and any other affected skin area with mild detergent Remove affected clothing immediately If skin surface is pierced seek medical attention immediately NOTE If you touch the glass of the lamp you should wipe the glass clean with isopropy...

Страница 3: ...ctboard when installed using the included Ductboard Adapter Plate see Figure 1 2 Install the Duo 24V unit a Hold or temporarily tape the included Ductboard Adapter Plate in the location chosen for installation and using the plate as a template mark the mounting surface using the outermost slots in the plate see Figure 1 Alternatively a 5 3 8 square may be marked on the mounting surface b Cut out t...

Страница 4: ...a downward air flow direction note that the round sight glass hole will be upstream of the ballast when properly installed f Insert the UVC lamp pins into the ballast socket see Figure 3 Note the lamp has one long pin that must be aligned with the recessed terminal in the ballast socket D o NOT directly touch the bulb lamp glass section with bare hands Wear oil free cotton type gloves when han dli...

Страница 5: ... annually The lamp should operate continuously for maximum lamp life and light effectiveness 3 Ensure that power has been disconnected to the circuit that will provide power to the 24V transformer and install the transformer as directed in the installation instructions included with the transformer WARNING MAKE SURE POWER IS DISCONNECTED TO THE CIRCUIT TO BE USED TO PROVIDE POWER TO THE DUO 24V UN...

Страница 6: ... ballast against the mounting base Rotate the ballast assembly clockwise until it stops and is locked in place See Figure 8 9 After assembly is firmly in place reconnect power to transformer Check lamp operation by looking through the viewport hole A blue glow should be seen in the duct 10 After replacing the lamp make sure to install the Lamp Replacement Label Print the date on the label and appl...

Страница 7: ...ngaged 4 If lamp does not light up remove the ballast from the base and re install it onto the base ensuring that the finger projecting from the base engages into the safety switch slot in the ballast Repeat step 3 5 If lamp does not light up after performing Steps 3 and 4 replace lamp REPLACEMENT PARTS LIST For replacement parts contact Field Controls at Phone 252 522 3031 Fax 252 522 0214 Email ...

Страница 8: ...46648100 06 15 The health aspects associated with the use of these products and their ability to aid in disinfecting of environmental air have not been investigated by UL Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com warranty ...