Figure 4 

O

PTIONAL 

T

HERMOSTAT 

H

OOK 

U

P

For heating applications, the Air Booster may also be operated by the use of a line voltage 
thermostatic switch which can be purchased from your local heating supply house or dealer. The 
thermostatic switch will operate the Air Booster only when the temperature of the air in the duct is 
above the per-set temperature. If a thermostatic switch is used, it is recommended it be located as 
close to the main truck line duct as possible, for the fastest response to the change of air temperature 
within the duct. (See Fig. 4.) However, follow the thermostatic switch manufacturer’s 
recommendations. NOTE: For air conditioning applications, a heating/cooling thermostatic switch with 
manual changeover must be used. 

1.  Gas or oil-fired central furnaces may include refrigerant cooling coils, however, it must be 

equipped with 120 VAC single phase blower motors. AIR BOOSTER SHOULD NOT BE 
WIRED IN PARALLEL WITH 240 VAC BLOWER MOTORS. 

2.  The basic furnace wiring and components should not be disturbed except for wiring 

interconnection of the Air Booster and furnace blower at a splice box in the furnace. 

3. 

The rating of the furnace blower motor controller must be adequate to control blower motor 
and Air Booster motor. The Air Booster motor is rated at 0.50 amps.

 

Important: 

Blower motor controller should not be a variable speed tap type, solid state speed 

control or any other type not suitable for dual motor control. 

UNIT WIRING INSTRUCTIONS 

1.  For electrical supply connections, use wires suitable for at least 90ºC when Booster is used on a 

heated duct system. 

2.  Electrical conduit must be routed away from warm air system ducts. Use adequate supports if 

necessary. 

3.  The two black motor lead wires that are interchangeable are connected to power source. The 

green wire is used for grounding purposes only. 

4.  The existing short circuit and ground fault protection for the furnace blower motor should be of a 

size and type which will adequately protect the Air Booster motor. Refer to Section 430-53 of the 
National Electrical Code. 

5.  The wiring from the furnace to the Air Booster must be 14 AWG and the furnace should be 

protected by over current protection (fuses or circuit breakers) rated 15 amperes or less (as 
applicable for 14 AWG conductors). 

Important: 

Refer to section 430-53 (d) and Table 310-16 for the National Electrical Code for additional limitations. 

Содержание 46011100

Страница 1: ...Air Booster Model AB 1 Instruction Manual Instructions D Installation Instrucciones de Instalación Page English 2 Français 5 Espanõl 8 ...

Страница 2: ...on the Air Booster is an accepted component of the listed fan unit by UL Inc This motor is designed as a normally HOT running motor and should feel hot to the touch Tests indicate that a normal 50 Watt household incandescent light bulb is considerably hotter than the maximum motor temperature of your Air Booster This motor temperature will not effect the performance of your Air Booster provided in...

Страница 3: ...ditioning systems it is recommended that the Air Booster be wired in parallel with the furnace blower motor for simultaneous operation see Fig 3 Figure 1 Figure 2 Figure 3 CAUTION Furnace physical wiring arrangements may differ from diagram To avoid fire or shock hazard all installations involving connection to existing furnace wiring must be made within furnace splice box ...

Страница 4: ... blower at a splice box in the furnace 3 The rating of the furnace blower motor controller must be adequate to control blower motor and Air Booster motor The Air Booster motor is rated at 0 50 amps Important Blower motor controller should not be a variable speed tap type solid state speed control or any other type not suitable for dual motor control UNIT WIRING INSTRUCTIONS 1 For electrical supply...

Страница 5: ...rouvent dans le haut du moteur Localiser l emplacement de ces trous avant l installation Si l AB 1 doit fonctionner de façon continuelle le moteur doit être lubrifié tous les trois mois NOTA Le moteur du pulvérisateur d air est une composante acceptée de l unité homologuée UL Inc Ce moteur est conçu comme ayant un fonctionnement normalement CHAUD et devrait être chaud au toucher Des tests indiquen...

Страница 6: ...NCTIONNEMENT Le pulvérisateur d air peut être opéré et contrôlé de plusieurs façons FONCTIONNEMENT AUTOMATIQUE Câbler en parallèle avec le moteur de ventilateur de la fournaise Pour les systèmes centraux de chauffage climatisation il est recommandé de câbler le pulvérisateur d air en parallèle avec le moteur de ventilateur de la fournaise pour un fonctionnement simultané Voir le Schéma 3 Schéma 1 ...

Страница 7: ...eur de la fournaise 3 La puissance nominale du contrôleur de moteur de ventilateur de la fournaise doit être assez élevée pour contrôler le moteur de ventilateur ainsi que le moteur du pulvérisateur d air Le moteur du pulvérisateur d air est classé à 0 50 A IMPORTANT Le contrôleur de moteur de ventilateur ne devrait pas être de type dérivation à vitesse variable à réglage de vitesse transistorisé ...

Страница 8: ...arga del motor lubríquelo dos veces al año con SÓLO ALGUNAS GOTAS de aceite SAE 20 Existen dos orificios de lubricación sobre el motor y se encuentran marcados para este propósito Sírvase la ubicación de estos orificios de lubricación antes de la instalación Si se hiciera funcionar constantemente el AB 1 el motor debe ser lubricado cada tres meses NOTA El motor que se usa en el Intensificador de A...

Страница 9: ...era necesario doble los salientes laterales figuras 1 y 2 para que se adapten al tamaño y forma particulares de su conducto FUNCIONAMIENTO Se puede hacer funcionar y controlar del Intensificador de Aire de varias maneras FUNCIONAMIENTO AUTOMÁTICO Instálelo en paralelo con el motor del ventilador de la calefacción Se recomienda que en los sistemas centrales de calefacción aire acondicionado el Inte...

Страница 10: ... monofásicos EL INTENSIFICADOR DE AIRE NO DEBE INSTALARSE EN PARALELO EN MOTORES DE 240 V CA 2 La instalación eléctrica básica de la calefacción y sus componentes no deben ser alterados excepto para la interconexión del Intensificador de Aire y el motor del ventilador de la calefacción en la caja de empalmes que se encuentra en la calefacción 3 El régimen nominal del control del motor del ventilad...

Страница 11: ... Nacional 5 La instalación eléctrica que va desde la calefacción al Intensificador de Aire debe ser de 14 AWG y la calefacción debe estar protegida con protegida por un dispositivo de protección contra las sobretensiones fusibles o disyuntores con un régimen nominal de 15 amperios o menos según corresponda a los conductores de 14 AWG IMPORTANTE Consulte la Sección 430 53 d Y LA Tabla 310 16del Cód...

Страница 12: ...Page 12 P N 46011100 Rev A 7 99 ...

Отзывы: