FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual 

 

This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of 
FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual                     Page

 

8

 

To  reduce  the  recharge  time,  the  IU  recharge  method  can  be  used  with  a  maximum  voltage  of  2.30 
V/cell at 68-77° F for 24 hours. Current should not be over 25% of nominal capacity, especially in sites 
where  temperature  may  exceeds  86°  F  to  avoid  thermal  runaway,  overheating  or  overcharging  of  the 
batteries.  
 
For very deep cyclic applications recharge voltage should not be higher than 2.30 V/cell for 16 to 24 hrs 
after every discharge. 
 

Temperature compensation of the float voltage 

 

To optimize FIAMM 

FLX

 battery life and performance over the normal operating temperature range, the 

float voltage should be adjusted in accordance with table 4. 
 
In environments where temperature fluctuations are very limited, float voltage can be adjusted manually 
as needed.  For most sites without a climate control systems it is advisable to have batteries connected 
to a charger with a built-in temperature compensation circuit.  
 
Temperature sensor needs to be positioned on or over the batteries and not in the charger. 
 

 
Ripple 

Excessive ripple currents can cause battery overheating, which will lead to shorter life expectancy and 
reduced product performance. It is recommended that voltage regulation across the system (including 
the  load,  but  with  battery  disconnected),  under  steady  state  conditions,  should  be  better  than 

±

  1% 

through 5% to 100% load. Transient and other ripple type excursions can be accommodated provided 
that, with the battery disconnected but the load connected, the system peak to peak voltage, including 
the  regulation  limits,  falls  within 

±

  2.5%  of  the  recommended  float  voltage  of  the  battery.  Under  no 

circumstances should the current flowing through the battery, when it is operating under float conditions, 
reverse into the discharge mode. 

 

4  STORAGE AND REFRESH CHARGING 

Storage 

Batteries are delivered filled and charged ready for installation. If they cannot be installed immediately, 
batteries need to be kept in fresh, clean dry rooms.  
 

 
Refreshing charge procedure 

During storage batteries will lose part of their capacity due to self-discharge (2% per month at 77° F). A 
freshening charge is recommended at least every 6 months (at 77° F storage temperature).  
 
Batteries should be refreshed, even if kept in storage at 77° F, when the cell voltage drops below the 
values listed in table 5. A freshening charge could be carried out by charging at 2.4 V/cell for about 24 
hours at 77° F (boost). If the charging system can not meet the above requirement (lower than 2.4 Vpc, 
it  is  necessary  to  extend  the  charging  time  24  hrs  for  every  0.03V/cell  lower  than  2.30V/cell,  for 
example, 120 hours at 2.28 V/cell).  
 

 

 Table 5 – OPEN CIRCUIT VOLTAGE VALUES REQUIRING A RECHARGE (WHEN STORAGE AT 77° F) 

 

 

RANGE 

OPEN CIRCUIT VOLTAGE (PER CELL) 

FLX 

2 months 

2.120 

4 months 

2.105 

6 months 

2.095 

 

Содержание FLX

Страница 1: ......

Страница 2: ...distributed routed or made available solely with written permission of FIAMM FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page 1 TABLE OF CONTENTS PAGE 1 OPERATING CHARACTERISTICS 2 2 INSTALLATION 4 3 CHARGING 6 4 STORAGE AND REFRESH CHARGING 8 5 MAINTENANCE AND TESTING 9 6 SAFETY 10 7 APPLICABLE STANDARDS 10 8 RECORDS DATA 10 ...

Страница 3: ...ains shall be distributed routed or made available sole ge or revise without notice any information or detail given in this m CHARACTERISTICS voltage peres per hours Ah Nominal capacity is usually 1 75 volt per cell at 77 F for different applications an be discharged to a lower voltage using highe circuit current ort circuit current of a battery are functions of its tes separator material electrol...

Страница 4: ...nsistent feed back from field applications but also from extensive accelerated thermal testing Operation at temperatures higher than 77 F reduces the performance life expectancy of a battery Service life of the battery is also affected by the float voltage chosen for battery charging as showed in figure 2 FIG 2 EXPECTED SERVICE LIFE VS FLOAT VOLTAGE RANGE Capacity in relation to the temperature Th...

Страница 5: ...r of strings in parallel should be reasonable in terms of layout and application If strings are properly cabled with equal voltage losses for each string multiple strings can be connected in parallel safely to reach required total capacity 2 INSTALLATION Unpacking and inspection Upon receiving a shipment of batteries it is important to check it carefully against related packing list Even though ea...

Страница 6: ...as close as possible to the top to prevent any hydrogen accumulation in an abusive situation Cabinets should be placed fastened steadily to the floor Installation procedure For a proper installation clean the blocks with a soft dry antistatic cloth or soft water moistened cloth Place each cell block at their correct position according to the electrical layout Start with the lowest shelf to ensure ...

Страница 7: ...at voltage recharge boost charge The IU recharge method also known as the modified constant voltage recharge has been used for many years and in a variety of applications This method combines the need to have the battery quickly recharged while ensuring maximum battery life With this method recharge starts at a constant current rate The voltage increases up to a pre set value The pre set voltage i...

Страница 8: ... the first 12 months from initial installation Recharge following discharge for standby use and boost charge At the first installation or soon after a discharge the recommended recharge method is to use a constant voltage equal to the float charge voltage with a maximum charge current of 25 of nominal capacity To reduce the recharge time the IU recharge method can be used with a higher voltage of ...

Страница 9: ... shorter life expectancy and reduced product performance It is recommended that voltage regulation across the system including the load but with battery disconnected under steady state conditions should be better than 1 through 5 to 100 load Transient and other ripple type excursions can be accommodated provided that with the battery disconnected but the load connected the system peak to peak volt...

Страница 10: ...tainer and lid Voltage checks All voltage measurements should be made when the entire battery has stabilized on float at least 7 days after battery installation or after a discharge cycle Measure and record individual block voltages on float once a year It is normal to have a spread of block voltages up to 250 mV battery particularly in the first year of operation No corrective action is required ...

Страница 11: ...try to remove the battery cap to add water or acid into the cell s Do not touch non insulated terminals or connectors as there is a risk of electric shock Do not allow naked flames hot objects or sparks near the battery Do not smoke near the battery or in the battery room The electrolyte diluted sulphuric acid is extremely corrosive Any contact with eyes can cause severe and permanent damage Conta...

Страница 12: ......

Страница 13: ...F Time String voltage V Charge current A Block No Volt Block No Volt 1 31 2 32 String Discharged Date Duration Date Duration String Equalized Date Duration Date Duration Remarks 3 33 4 34 5 35 6 36 7 37 8 38 9 39 10 40 11 41 12 42 13 43 14 44 15 45 16 46 17 47 18 48 19 49 20 50 21 51 22 52 23 53 24 54 25 55 26 56 27 57 28 58 29 59 30 60 Blocks temperature 01 12 24 Blocks temperature 36 48 60 Readi...