c)

 

Where dust, dirt or moisture accumulates on the window, first clean the window with a soft optical cloth 
and detergent, and then rinse with a clean soft cloth, cotton swab, or tissue. 

5.4

 

Troubleshooting  

In case of problem in the operation of the detector, please consult with the following table before calling for 
help:  

 

Problem 

 

Possible Cause 

 

Corrective Action 

 

LEDs Off   
Fault Relay is open   
Current output at 0mA  

No power to the unit  

• 

Check that the power is 
connected to the detector.  

• 

Check power polarity.  

• 

Check wiring in the detector.  

Yellow LED constantly on 
Fault Relay is open   
Current output at 0mA  

Power problems  

 

Check the voltage between the 

“24VDC (+)” and “24VDC (

-

)” 

terminals to verify that it is in the 
allowed range (see section 6.2) 

Yellow LED constantly on 
Fault Relay is open   
0

20mA at 2mA  

BIT Fault   

• 

Clean detector window.  

• 

Restart the detector (by turning 
the power off and then back on).  

Red LED constantly on  

Detector is in alarm 
latch mode 

Restart the detector (by turning the 
power off and then back on). 

Alarm Relay closed and 
current output is at 20mA 

Detector is exposed 
to a flame  

• 

Check cause of alarm.  

• 

If 

caused by “friendly fire”, re

-

position the detector so that it is 
not affected by it.  

 

 

 

 

Содержание FlameSpec IR3-H2

Страница 1: ...FlameSpec IR3 H2 User Manual Doc No F150V0020 04 590 W Central Ave Suite K Brea CA 92821 USA T 1 714 671 8500 www fg detection com support fg detection com FlameSpec IR3 H2...

Страница 2: ...or transmitted for commercial purposes such as selling copies of this publication or for providing paid for support services The Fire Gas Detection Technologies logo is a trademark of Fire Gas Detect...

Страница 3: ...stallation 5 2 3 Required Tools 5 2 4 Certification Instructions 5 2 5 Installing the Tilt Mount 7 2 6 Installing the detector 8 3 Configuration options 10 3 1 Sensitivity 10 3 2 Ultra Fast Detection...

Страница 4: ...Specifications 19 6 1 Fire Detection 19 6 2 Electrical Specifications 19 6 3 Outputs 19 6 4 Mechanical Specifications 20 6 5 Environmental Specifications 20 6 6 Label Figures 21 6 7 Approvals 22 6 8 E...

Страница 5: ...Figure 2 Tilt mount base Side View 8 Figure 3 Detector on Tilt Mount Side View 9 Figure 4 Source 4 Wire Scheme 13 Figure 5 Sink 4 Wire Scheme 13 Figure 6 Source 3 Wire Scheme 14 Figure 7 Sink 3 Wire S...

Страница 6: ...l means to study the cause and development of fire events 1 1 Key Features High immunity to false alarm Ultra fast detection mode detection within 40 milliseconds for Hydrogen fireballs or explosions...

Страница 7: ...tor performs self tests of its optics electronics and software These include a periodic BIT Built In Test in which the sensors and window cleanliness are tested Any detected fault is indicated as show...

Страница 8: ...have to the extent that is required an unobstructed view of the protected area Whenever possible the detector face should be tilted aimed down at an angle to prevent the accumulation of dust and dirt...

Страница 9: ...inhibited during welding operations in situations where the possibility of a false alarm cannot be tolerated Gas welding requires a system inhibit since the gas torch is an actual fire Arc welding rod...

Страница 10: ...ngs or labels for the wiring You may use 12 to 22 AWG 2 5 2 to 0 3 2 wires for the site wiring The selection of wire gauge should be based on the number of detectors used on the same line and the dist...

Страница 11: ...checks as part of routine inspections or establishing from the material s data sheet that it is resistant to specific chemicals 2 4 1 Specific conditions for use The equipment is not intended to be re...

Страница 12: ...method However with a designated adapter the tilt mount can hold the detector from above Other designated adapters may be used to connect the detector to some other vendors tilt mounts useful when rep...

Страница 13: ...c Secure the detector by using the two provided screws and spring lock washers Items 3 and 4 d Release the locking screws Items 5 and 6 in such a way that enables you to rotate the detector e Point th...

Страница 14: ...cal support 1 714 671 8500 support fg detection com 9 Figure 3 Detector on Tilt Mount Side View ITEM NO ITEM NAME 1 TILT MOUNT ASSEMBLY 2 HOLDING PLATE 3 4 MOUNTING HEX SCREWS M8 AND LOCK WASHERS 5 HE...

Страница 15: ...30 seconds 0 seconds no delay Alarm Latch Disabled Enabled Disabled Window Heater Disabled Enabled Enabled Modbus address 1 247 1 Manual BIT Alarm Output Test Disabled Enabled Disabled Note Medium se...

Страница 16: ...after a flame is no longer detected To return the detector outputs to normal mode the detector must be powered down and restarted 3 5 Window Heater The detector is equipped with a heater to prevent co...

Страница 17: ...20 mA current output 4 0 20mA out 5 Fault Relay A normally open SPST contact relay that is energized closed when the detector is in normal operation and opens in case of fault 6 Fault Relay COM 7 Alar...

Страница 18: ...an be 3 wire or 4 wire connected The following drawing shows how to wire the detector to act as a current source isolated transmitter 4 wire connection FIGURE 4 SOURCE 4 WIRE SCHEME The following draw...

Страница 19: ...wire the detector to act as a current sink non isolated transmitter 3 wire connection FIGURE 7 SINK 3 WIRE SCHEME 4 3 RS 485 Communication Network Using the RS 485 network capability of the detector a...

Страница 20: ...up to 247 on the same 4 wires Using the RS 485 network it is possible to read each detector s status fault alarm and to initiate a BIT to each detector individually The detector communicates via RS 48...

Страница 21: ...reen the 0 20mA indicates 4mA and the fault relay is closed Detector configuration settings can be changed as described in section 3 To restart the detector turn off and then turn on the power 5 1 Out...

Страница 22: ...0mA current output will be set to 20mA 3 The alarm relay will close WARNING Make sure to disable all fire extinguishing actions or alarms connected to the detector when the manual BIT is initiated and...

Страница 23: ...Check that the power is connected to the detector Check power polarity Check wiring in the detector Yellow LED constantly on Fault Relay is open Current output at 0mA Power problems Check the voltage...

Страница 24: ...ion including window heater Cable Entries 2x conduit entries 3 4 14NPT or M25x1 5 Wiring 12 20AWG 2 5 0 35mm2 6 3 Outputs Relays Volt free contacts rated 2A at 30 VDC o Alarm Normally open o Fault2 No...

Страница 25: ...fications Size 5 51 x 3 54 3 54 140 90 90mm Weight o Detector Stainless Steel 316 6 6 lbs 3 kg o Tilt mount Stainless steel 316 3 3 lbs 1 5 kg 6 5 Environmental Specifications Temperature Range o Oper...

Страница 26: ...FlameSpec IR3 H2 User Manual F150V0020 04 For more information Technical support 1 714 671 8500 support fg detection com 21 6 6 Label Figures 6 6 1 Ex db 6 6 2 Ex db eb...

Страница 27: ...a 75 C Ex db IIC T4 Gb 50 C Ta 85 C FM FMC Class I Div 1 Groups B C D T4 Class I Zone 1 AEx Ex db IIC T4 Gb T4 50 C Ta 85 C T5 50 C Ta 5 C Performance o ANSI FM 3260 o EN 54 10 pending Functional safe...

Страница 28: ...red in transit from the factory or other damage due to abuse misuse improper installation lack of maintenance or Act of God which are above and beyond its control FIRE GAS DETECTION TECHNOLOGIES INC w...

Страница 29: ...s for different fire scenarios Each table lists results for a different sensitivity setting For liquid fires the size of fire refers to the size of the pan filled with the fuel For gas fires the lengt...

Страница 30: ...eflected No Alarm No Alarm Incandescent frosted glass light 300W 2 0 5 No Alarm 2 0 5 No Alarm Fluorescent 70W 3x23 3W 2 0 5 No Alarm 2 0 5 No Alarm Electric arc 3 1 No Alarm 3 1 No Alarm Arc welding...

Отзывы: