Specifications
6.1
Fire Detection
•
Detection time and distance:
o
40ms
-
for fast fire burst or explosion
o
1.5s -
for 32″ (0.8m) hydrogen fire at 0–
100 ft. (0
–
20m)
o
4
s for 32″ (0.8m) hydrogen fire at
66
–
100 ft. (20
–
30m)
•
Field of view: 90° Horizontal, 75° Vertical
•
Time Delay: 0-30 seconds (adjustable)
•
Built-in test: Automatic and Manual
6.2
Video functionality
•
HD Video allowing clear imaging of fire and people at 100ft. (30m) distance.
•
Video recording of alarm events 1 minute before and up to 3 minutes after the flame is
detected.
•
System integration protocol: ONVIF (Open Network Video Interface Forum) Profile S
6.3
Electrical Specifications
•
Operating Voltage: 24 VDC nominal (18-32 VDC)
•
Current Consumption:
o
Standby
180mA
o
Maximum
250mA all systems in operation (including window heater)
•
Cable Entries:
2x conduit entries 3/4” 14NPT or M25x1.5
•
Wiring: 12-20AWG (2.5-0.35mm
2
)
6.4
Outputs
•
Relays: Volt-free contacts rated 2A at 30 VDC
o
Alarm: Normally open and normally closed
o
Fault
2
: Normally open energized
2
The FAULT relay will normally be energized and the contact will be closed during normal operation of the
detector. The contact will be open at fault condition or low voltage.