EN
Document No: 0044-117-01
www.ffeuk.com
Страница 1: ...Page 1 User Guide EN Document No 0044 117 01 www ffeuk com...
Страница 2: ...6 Maintaining the TalentumTT2 7 Introducing the TalentumTT2 8 Testing a Talentum Flame Detector Setting up a Talentum Flame Detector Test Testing an IR2 or IR3 Talentum Testing a UV IR Talentum 9 Reca...
Страница 3: ...real fire not the sun or artificial light Broad spectrum test UV visible near IR Mid IR frequencies Flickering multi spectral output Solar spectrum profile not present in the output Flame Detector Re...
Страница 4: ...tery Performance Operational Environment Operating Temperature 10 C to 55 C Hazardous Ex Areas Not suitable for use in hazardous areas IP Rating IP54 Recycle raw materials instead of disposing of them...
Страница 5: ...within a safe location to perform the test Testing of a Flame Detector should only be conducted where it is safe to do so and by personnel with appropriate training and equipment Ultraviolet radiatio...
Страница 6: ...6579 IR3 Flame Detector Intrinsically safe IS 16519 IR3 Flame Detector Flameproof Exd 16509 IR3 Flame Detector Stainless Steel 16549 IR3 Flame Detector Stainless steel flameproof Exd 16591 UV IR2 Flam...
Страница 7: ...ied Any USB A standard charging port such as a USB mains charger Not Supplied USB data and charging cable Supplied A Fast Charge capable USB A standard charging port such as a Fast Charge USB mains ch...
Страница 8: ...ting the other end to a Fast Charge capable USB socket The LED next to the USB C connector will be solid green while the TalentumTT2 is charging turns off when charging is complete and will flash if t...
Страница 9: ...soiling before use discontinue use if the item is more than cosmetically damaged or soiled Check the USB cable for damage before use replace with Fast Charge and data transfer compatible USB A male t...
Страница 10: ...CD screen and seven control buttons as illustrated below 7 Introducing the TalentumTT2 Power Button OK Button Direction Buttons Up Down Left Right Getting to know your TalentumTT2 Back Button Trigger...
Страница 11: ...ery will be checked before taking you to the main screen The main screen will allow you to select either a IR test a UV IR test or to recalibrate your Talentum Flame Detector Pressing the Up or Down A...
Страница 12: ...th bring up the main menu Menu Select Torch Info Main Menu Power on count Test count Recal count SBR cal 2134499004 v 0 7 6 2022 04 07 12 30 47 2 1 0 50 1 Selecting Torch Info will bring up a screen s...
Страница 13: ...Power button It will turn itself off when it has finished a test or recalibration if the user is inactive in a menu for 30 seconds or if the TalentumTT2 has encountered an error condition Switching of...
Страница 14: ...etector s line of sight taking care to point the unit emitter towards the Detector s sensors Some adjustments may be required to find the ideal position and distance for a specific Detector Note Ultra...
Страница 15: ...m Aim torch at Talentum within 2 8m Do not aim at eyes Press the Trigger button to start the test or Back to cancel When the test starts the screen will change to show The number on the bottom row wil...
Страница 16: ...r that there is a range of distances between the TalentumTT2 and Flame Detector where it should trigger for example try reducing the distance between the TalentumTT2 and the Flame Detector If you are...
Страница 17: ...hat the TalentumTT2 is pointed away from people during this procedure The first two screens are modified to warn about the presence of UV C light Testing a UV IR Talentum Warming up WARNING UV light C...
Страница 18: ...a Flame Detector Remove the front cover of the Talentum Flame Detector by loosening the four bolts with a 5mm Allen key Carefully peel back the sticker surrounding the DIL switches by using a small f...
Страница 19: ...procedure to prevent ambient light from influencing the test Place the Shroud provided over the front of the TalentumTT2 The large end fits over the front of the TalentumTT2 and the small end fits ov...
Страница 20: ...le to test Torch and Talenum Confirm The following confirmation screen will be shown Press the Trigger button to start calibration or the Back button to cancel The Talentum TT2 should connect to the F...
Страница 21: ...edure and the TalentumTT2 display indicates what it is doing throughout This process takes approximately one minute to complete The following sequence of screens should be displayed Calibrating Readin...
Страница 22: ...s a list of the possible error messages along with more detail on their meaning Shroud not fitted Check the shroud Check that the Shroud is fitted to the TalentumTT2 and the Flame Detector correctly U...
Страница 23: ...te Talentum The Flame Detector is of a type that has only a single IR sensor calibration requires at least two IR sensors or does not have a recognised part number Unknown unit type The TalentumTT2 do...
Страница 24: ...ly high The Flame Detector should be returned for servicing Unit overheating The temperature in the TalentumTT2 is too high Recalibration will be abandoned for safety Allow the TalentumTT2 to cool dow...
Страница 25: ...ion operations which have been carried out To retrieve the data logs first before powering the TalentumTT2 attach a USB cable to connect the USB C port of the TalentumTT2 to the USB port of a computer...
Страница 26: ...n supporting documentation and that the name of the author not be used in advertising or publicity pertaining to distribution of the software without specific written prior permission The author discl...