22318.10.03 15.09.05
11
11. Technical Data.
•
Operating Range Fireray 50RU
15 to 160 Feet
•
Operating Range Fireray 100RU
160 to 330 Feet
•
Lateral
Coverage
30
Feet (either side of the beam)
•
Supply Voltage
10.2 to 30 Volts DC
•
Quiescent
Current
Less
than
4mA
•
Alarm/Trouble
Current
Less
than
20mA
•
Alarm
Contacts
Normally
Open
contacts rated 1 amps, 30 Volts DC, resistive
•
Trouble
Contacts
Normally
Closed
contacts rated 1 amps, 30 Volts DC, resistive
•
Relay
Contacts
(all)
Maximum
voltage 220 Volts DC, 30 watts, resistive
•
Alarm and Trouble Signal Delay
10 seconds
•
Power Down Reset Time
>5 seconds
•
Operating
Temperature 32
°
F to 100
°
F
•
Moisture RH (max)
93% (non condensing)
•
Fire
Alarm
Thresholds
2.50dB
(25%), 3.74dB (35%), 6.02dB (50%)
•
Optical
Wavelength
880nm
•
Head Maximum Size
Width 5.1 inches, Height 8.25 inches, Depth 4.7 inches
•
Weight
24
ounces
12. Service / Application Notes.
•
Red LED indicates FIRE.
•
Continuous Amber LED indicates TROUBLE.
•
Flashing Amber LED once every 2 seconds indicates that the contamination/compensation function has reached its limit.
•
Alarm condition indicated by fire relay closing (relay contact is normally open).
•
Trouble condition indicated by Trouble relay opening (relay contact is normally closed).
•
Alarm may be latching or non-latching (default).
•
Periodic cleaning with a lint free soft cloth is required.
13. Parts List.
•
1 off: Detector Head Assembly with cable interface
•
1 off: Prism for the 50RU or 4 off: Prisms for the 100RU
•
1 off: Test Filter
14. Optional Extra Parts List.
•
Low Level Controller (Optional Extra Part Number 0400-01-XX, where XX is the latest version)
15. Technical Support.
•
Toll free hotline within USA 1-866-FIRERAY (347-3729)
•
E-mail: [email protected]
•
Website: www.ffeuk.com