6. Multi I/O modules
6−10
Festo P.BE−CPX−EA−EN en 0705f
6.4
Instructions on commissioning
The reaction of the I/O modules can be parametrized.
The table below gives an overview of the parameters.
Further information on parametrizing can be found in the
system manual or in the manual for the field bus node.
Parameters of the multi I/O modules
typeCPX−8DE−8DA
Module parameters: Monitoring the CPX module
Function no.
4828 + m * 64 + 0
m = module number (0...47)
Description
Monitoring of the possible faults can be activated or deactivated (suppressed)
for each module independently. Active monitoring causes the following:
The fault is:
sent to the CPX field bus node
displayed by the module common error LED
Bit
0
1
2
Monitoring
Description
Short circuit/overload in sensor supply (SCS)
Short circuit/overload at the outputs (SCO)
Undervoltage at outputs (V
OUT
)
[Monitor]
[Monitor SCS]
[Monitor SCO]
[Monitor Vout]
Values
1 = active (presetting)
0 = inactive
[Active]
[Inactive]
Remark
Monitoring can also be set for the complete CPX terminal
(see System parameter monitoring")
Tab.6/5:
Monitoring the CPX module
Содержание VMPA...-FB-EPL Series
Страница 2: ......
Страница 22: ...Contents and general instructions XX Festo P BE CPX EA EN en 0705f ...
Страница 46: ...1 Pneumatic interfaces 1 24 Festo P BE CPX EA EN en 0705f ...
Страница 100: ...3 Overview and connecting technology I O modules 3 30 Festo P BE CPX EA EN en 0705f ...
Страница 101: ...Input modules 4 1 Festo P BE CPX EA EN en 0705f Chapter 4 Type CPX 4DE CPX 8DE CPX 8DE D CPX 16DE CPX M 16DE D CPX 8NDE ...
Страница 141: ...Output modules 5 1 Festo P BE CPX EA EN en 0705f Chapter 5 Type CPX 4DA CPX 8DA CPX 8DA H ...
Страница 171: ...Multi I O modules 6 1 Festo P BE CPX EA EN en 0705f Chapter 6 Type CPX 8DE 8DA ...
Страница 191: ...Technical appendix A 1 Festo P BE CPX EA EN en 0705f Appendix A ...
Страница 223: ...Index B 1 Festo P BE CPX EA EN en 0705f Appendix B ...
Страница 224: ...B Index B 2 Festo P BE CPX EA EN en 0705f Contents B Index B 1 ...