background image

Fitting the modules

1.  Switch off the compressed air supply and the operating volt-

age.

2.  Unlock the safety lever (if fitted) and remove the blind plate.

3.  Grasp the module by the front plate and push it into the

guide rail. Be careful not to tilt the module when sliding it
into the slot and make sure that none of the components
on the printed circuit board are damaged.  

4.  Make sure that the pins on the connectors are correctly

aligned. Then with a light pressure of the fingers push the
module in as far as it will go. The safety catches will then
lock automatically (see diagram).

1

2

3

Direction of unlocking
Self-actuated locking
Safety catches

4

5

6

Front plate of module
Contact strip 
Guide rail

6

5

1

4

2

1

2

3

E

n

g

lis

h

SPC200-COM-PDP

9903NH

13

Содержание SPC200-COM-PDP

Страница 1: ...Kurzbeschreibung Feldbus Baugruppe PROFIBUS DP Typ SPC200 COM PDP Brief description Field bus module PROFIBUS DP type SPC200 COM PDP 9903NH 388 645...

Страница 2: ...Deutsch 3 English 11 Festo AG Co D 73726 Esslingen 1999 SPC200 COM_PDP 9903NH 2...

Страница 3: ...RSICHT Beachten Sie unbedingt die dort aufgef hrten Sicherheitstechnischen Hinweise den bestimmungsgem en Gebrauch der jeweiligen Baugruppen und Module WARNUNG Aktoren k nnen ungewollt aktiviert und d...

Страница 4: ...installieren Wird die Feldbusbaugruppe neben die Diagnose Baugruppe installiert kann kein Bedienfeld aufge steck werden solange das Feldbuskabel aufgesteckt ist Es darf nur 1 Feldbus Baugruppe install...

Страница 5: ...chieben nicht verkanten und keine Bautei le auf der Leiterplatte besch digt werden 4 Achten Sie darauf da die Stecker der Messerleisten richtig aufeinander liegen Schieben Sie die Baugruppe dann mit l...

Страница 6: ...DGND VP n c RxD TxD N n c Schirm direkte Verbindung zum Geh use nicht angeschlossen Empfang Sende Daten P Repeater Steuersignal Datenbezugspotential M5V Versorgungsspannung Plus P5V nicht angeschlosse...

Страница 7: ...n Stecker der Siemens AG Bestellnummer Beschreibung 6ES7 972 0BA10 0XA0 Abschlu widerstand zuschaltbar senkrechter Kabelabgang bertragungsrate 9 6 kBit s 12 MBit s 6ES7 972 0BB10 0XA0 wie oben jedoch...

Страница 8: ...nge ist von der genutzten Be triebsart des SPC200 abh ngig Die folgende Tabelle gibt einen berblick Betriebsart des SPC200 max Adre bereich Funktion der Ein Ausg nge Start Stop I10 0 I13 15 I10 0 I10...

Страница 9: ...inkt schnell Parametrierfehler Profibusadresse oder Betriebsart unzul ssig leuchtet blinkt langsam Betriebszustand normal Verbindung zum Feldbusmaster nicht vorhanden leuchtet blinkt kurz Hardwarefehl...

Страница 10: ...ron halb duplex PROFIBUS DP Norm Slave zertifiziert nach DIN 19245 Teil 1 bis 4 EN 50170 Vol 2 9 6 12000 kBit s automatische Baudratenerkennung bis zu 23 8 km max 100 mA Elektromagnetische Vertr glich...

Страница 11: ...strict attention to the following instructions shown therein safety guidelines specifications for the use of the individual modules and components WARNING Actuators may be activated unintentionally a...

Страница 12: ...f the field bus module is fitted next to the diagnostic module it is not possible to connect an operating panel whilst the field bus cable is still connected Only 1 field bus module may be fitted All...

Страница 13: ...to the slot and make sure that none of the components on the printed circuit board are damaged 4 Make sure that the pins on the connectors are correctly aligned Then with a light pressure of the finge...

Страница 14: ...GND VP n c RxD TxD N n c Screening shield Direct connection to housing Not connected Receive send data positive Repeater control signal Data reference potential M5V Supply voltage positive P5V Not con...

Страница 15: ...in plugs from Siemens AG Part number Description 6ES7 972 0BA10 0XA0 Terminating resistor can be switched in vertical cable exit baud rate 9 6 kbit s 12 Mbit s 6ES7 972 0BB10 0XA0 as above but with co...

Страница 16: ...the operating mode of the SPC200 This is summarized in the following table Operating mode of the SPC200 Max address range Function of the inputs outputs Start Stop I10 0 I13 15 I10 0 I10 15 for contr...

Страница 17: ...hes fast parametrizing errror PROFIBUS address or operating mode not valid lights up flashes slowly operating status normal no connection to field bus master lights up flashes briefly hardware error s...

Страница 18: ...x PROFIBUS DP standard slave certified as per DIN 19245 parts 1 to 4 EN 50170 vol 2 9 6 12000 kbit s automatic baud rate recognition up to 23 8 km max 100 mA Electromagnetic compatibility interference...

Отзывы: