OVEM-…-LK
60
Festo – OVEM-…-LK – 1602NH English
Index
Sub-
index
Name
Value
Description
Length
(byte)
Inform
BDC3 - Out B
0x4000
0
Setpoint SP1
0…16383
(0…-1 bar)
Lower switchpoint
Standard values:
OVEM-...-L: 3227 (-0.2 bar)
OVEM-...-H: 11468 (-0.5 bar)
2
R/W
FR
DS
1
Setpoint SP2
0…16383
(0…-1 bar)
Upper switchpoint
Standard values:
OVEM-...-L: 6717 (-0.41 bar)
OVEM-...-H: 15892 (-0.71 bar)
2
0x4001
1
Switchpoint
logic
Switchpoint logic
1
0
NO (Standard)
1
NC
2
Switchpoint
mode
Switchpoint mode
1
1
Single point mode (Standard)
2
Window mode
3
Switchpoint
hysteresis
0…14745
(0…-0.9 bar)
Hysteresis value
Standard values:
OVEM-...-L: 1638 (-0.1 bar)
OVEM-...-H: 3227 (-0.2 bar)
2
BDC4 - Evacuation time t
E
and air supply time t
B
(Time monitoring evacuation/ventilation)
0x4002
0
Setpoint SP1
(evacuation
timeout)
0…4000
(0…10000 ms)
Evacuation time limit value t
E
Standard: 0
2
R/W
FR
DS
1
Setpoint SP2
(ventilation
timeout)
0…4000
(0…10000 ms)
Air supply time limit value t
B
Standard: 0
2
0x4003
1
Switchpoint
logic
Switchpoint logic of the
diagnostic output 1/2
1
0
NO (Standard)
1
NC
0x4003
2
Switchpoint
mode
128
Switchpoint mode BDC4
Standard value: 128
1
3
Switchpoint
hysteresis
0
Hysteresis value
2
1)
R/W = read and write, FR = restore factory settings (Factory Reset), DS = data storage (Data Storage) possible
2)
Time = 2.5 ms * Value
3)
Value = 128: vendor specific. Five measurements are recorded; if the limit is exceeded 3 times, an event is created as a warning
Tab. 9
Smart Sensor Profile Parameter - (Smart Sensor Profile Parameters)