Terminal strip
6.1 Specification of the cables
Specification of the cables
Conductor cross-section
0.08 … 0.5 mm
2
or AWG 28 … 20
Stripping
5 … 6 mm
Permitted copper
conductors
Single wire, multi-wire, fine wire, also with tin-plated single conductors
Fine wire, strands compressed
Fine wire with wire end sleeves (crimped on gas-tight)
Fine wire with pin terminal (crimped on gas-tight)
1)
If necessary, use the next smaller conductor cross section.
Fig. 3
6.2 Mounting/dismounting of the cables
Note
To ensure a reliable contact, only connect one conductor per terminal.
Only insert cables into the terminal opening.
Pushing a screwdriver into the opening may damage the terminal.
1
2
3
4
5
1
Screwdriver
2
Cable ends
3
Terminal strip
4
Terminal opening
5
Actuating lever
Fig. 4
1. Press the screwdriver
1
against the white actuating lever
5
.
è
The terminal of the terminal strip
3
opens.
2. Insert or pull out the ends of the cable
2
through the opening
4
.
3. Put down the screwdriver
1
.
è
Actuating lever
5
is slack.
è
The terminal of the terminal strip is closed and the cable clamped.
7
Earth valve terminal
Note
Observe the following points to avoid malfunctions from electromagnetic inter
ference:
Use a large-cross-section earth conductor that is as short as possible.
The earth conductor should ideally be a braided conductor, alternatively a
cable with a cross section of at least 2.5 mm², preferably 4 mm², and a maxim
um length of 20 cm. A different cable may be required depending on the
installation situation.
Connect the earth terminal with low resistance and low impedance to the
earth potential.
1
2
1
Earth terminal on the left end plate
2
Earth terminal on the right end plate
(grounding screw premounted)
Fig. 5
Connect one of the earth terminals (
è
Fig. 5) to the earth potential.
8
Address assignment of the valves
Addresses are allocated in ascending order without gaps, from left to right. Depen
ding on the integrated electrical interlinking module, a valve position occupies the
following number of addresses:
Electrical interlinking module
Number of
valve positions
Number of
occupied
addresses per
valve position
Type
Housing
colour
Individual electrical interlinking module
VMPAL-EVAP-…-1
Grey
1
1
VMPAL-EVAP-…-2
Black
1
2
4-fold electrical interlinking module
VMPAL-EVAP-…-1-4
Grey
4
1
VMPAL-EVAP-…-2-4
Black
4
2
Electrical interlinking module of the power supply module
VMPAL-EVAP-20-SP
Black
0
0 (signals are
passed through)
Fig. 6
If one valve occupies both addresses of a valve position:
– Solenoid coil 14 occupies the less significant address.
– Solenoid coil 12 occupies the higher-value address.
Address assignment does not depend on it is equipped with blanking
plates or valve plates.
Additional information
è
Description MPAL-VI
9
Technical data
General information
Dimensions
è
Description MPAL-VI
Ambient temperature (in operation)
–5 … +50
°
C
Storage temperature
–20 … +40
°
C
Degree of protection in accordance with
EN 60529 for completely mounted valve
terminal
– IP40 (open cover)
– IP67 (closed cover)
Protection against electric shock
(protection against direct and indirect con
tact in accordance with IEC/EN 60204-1)
Through the use of PELV circuits
(Protected Extra-Low Voltage)
CE marking (see declaration of conformity)
è
www.festo.com/sp
In accordance with EU EMC Directive
Materials
è
Description MPAL-VI
1)
The product is intended for use in industrial environments. If the product is used in a low-voltage net
work that also supplies residential areas, actions against interference may be required.
2)
The maximum permitted signal cable length for the valve terminal with multi-pin plug connection is 30 m.
Fig. 7
Pneumatics
Number of valve positions
Max. 32,
dependent on the variant of the multi-pin plug connection
è
Chap. 5
Medium
Compressed air in accordance with ISO 8573-1:2010 [7:4:4]
lubricated or unlubricated (oil: VG32)
Notes on the operating/
pilot medium
Lubricated operation possible (in which case lubricated operation
will always be required)
Operating pressure
With int. pilot air
3 … 8 bar
With ext. pilot air
Dependent on the valve sub-base types used
è
Description MPAL-VI
Fig. 8
Electrical data
Power supply
Nominal voltage
24 V DC (±25 %)
Current consumption
(per coil, with LED) at 24 V
MPA1
MPA14
MPA20
Nominal pick-up
current
50 mA
50 mA
110 mA
Pick-up duration
Approx. 20 ms
Nominal current with
current reduction
10 mA
10 mA
23 mA
Fig. 9