5. Commissioning with the control panel
5−39
Festo P.BE−HSP−AE−IO−EN en 0510NH
Start positioning
procedure
If there are no faults and enable is active (ENABLE = 1),
reference travel (input word I1 ... I4, positive edge at START
input) can be started. When the START signal is set (
>
1),
the MC signal (Motion Complete) is reset (
>
0), the drive
moves to the specified target position. As long as the drive
is in motion, the MC signal remains reset, and no other
positioning set can be started with the START signal.
Disable
With a falling edge at the ENABLE input (
>
0), the outputs
READY and the MC are reset. (
>
0). A current positioning
procedure is interrupted. The starting signal will then be
ignored.
When the ENABLE signal
>
1 is enabled again, READY and
MC will still not be set until the START signal is reset (
>
0).
The next positioning set can then be started with a rising
edge at the START input (
>
1).
Position reached
The TR signal will be set with positioning sets without torque
switching when the nominal position is reached (after approx.
20 ms). In the case of positioning sets with torque switching,
the TR signal will not be set until the nominal torque and posi
tioning at the stop (blocking) are reached.
If the TR signal is set when the START signal is still at 1, the
MC signal will remain at 0 until the START signal is reset. This
coupling of START / MC signal enables signal confirmation for
the PLC (handshake function).
If the START signal is reset after the MC signal has confirmed
the start (MC
>
0) and before the TR signal is set, the MC
signal will be set at the same time as the TR signal (MC,
TR
>
1) when the nominal position is reached.
Fault
During operation the outputs READY and MC will be reset if
there is a fault. A fault in operation is clearly indicated by the
following I/O status:
Inputs:
ENABLE = 1 and START = 0
Outputs:
MC = 0 and READY = 0.
Содержание HSP AE Series
Страница 1: ...Manual Type HSP Ū AE IO Ū Manual 541 946 en 0510NH 691 172 Handling module HSP AE ...
Страница 4: ...Contents and general instructions II Festo P BE HSP AE IO EN en 0510NH ...
Страница 19: ...System summary 1 1 Festo P BE HSP AE IO EN en 0510NH Chapter 1 ...
Страница 37: ...Fitting 2 1 Festo P BE HSP AE IO EN en 0510NH Chapter 2 ...
Страница 54: ...2 Fitting 2 18 Festo P BE HSP AE IO EN en 0510NH ...
Страница 55: ...Installation 3 1 Festo P BE HSP AE IO EN en 0510NH Chapter 3 ...
Страница 69: ...The control panel 4 1 Festo P BE HSP AE IO EN en 0510NH Chapter 4 ...
Страница 92: ...4 The control panel 4 24 Festo P BE HSP AE IO EN en 0510NH ...
Страница 93: ...Commissioning with the control panel 5 1 Festo P BE HSP AE IO EN en 0510NH Chapter 5 ...
Страница 133: ...Operation and maintenance 6 1 Festo P BE HSP AE IO EN en 0510NH Chapter 6 ...
Страница 142: ...6 Operation and maintenance 6 10 Festo P BE HSP AE IO EN en 0510NH ...
Страница 143: ...Diagnosis 7 1 Festo P BE HSP AE IO EN en 0510NH Chapter 7 ...
Страница 152: ...7 Diagnosis 7 10 Festo P BE HSP AE IO EN en 0510NH ...
Страница 153: ...Technical appendix A 1 Festo P BE HSP AE IO EN en 0510NH Appendix A ...
Страница 159: ...A Technical appendix A 7 Festo P BE HSP AE IO EN en 0510NH HSP AE HSP AE GE Fig A 1 Dimensions of the handling module ...
Страница 166: ...A Technical appendix A 14 Festo P BE HSP AE IO EN en 0510NH ...
Страница 167: ...Index B 1 Festo P BE HSP AE IO EN en 0510NH Appendix B ...
Страница 168: ...B Index B 2 Festo P BE HSP AE IO EN en 0510NH Contents B Index B 1 ...