Steps for updating the parameter set
4. Open the parameter set file (e.g. Festo-EGSS_...-20210209-IOLFW1.0.iolfw)
–
Open the "Firmware Update (Profile)
1
" tab
Variants for opening the file:
–
Open the "File" tab and execute the "Open IODDs" submenu
2
–
Via the key combination "Ctrl + u
3
"
–
By drag-&-drop
4
5. Load the parameter set file into the integrated drive
–
Press the "Update
1
button
–
The parameter set is transmitted
2
–
The transfer is successfully completed
3
6. Update the parameter set file in the integrated drive
–
An automatic restart is executed
–
The connection to the IO-Link master is interrupted
1
–
After successful loading of the parameter file, the connection to the IO-Link master is automati-
cally established
2
or it must be established manually
è
step "3. Establish a connection to the
IO-Link master"
Steps for updating the parameter set
7. Open the IODD file of the drive unit (device description file)
Variants for opening the file:
–
Open the "File" tab and execute the "Open IODDs" submenu
1
–
Via the automatic search
2
1)
–
Via the key combination "Ctrl + o
3
"
–
By drag-&-drop
4
8. Acknowledge error (only if an error is pending)
–
Open the "Specialist (user role)
1
" tab
–
Open submenus "Parameter
2
" and "Control parameter
3
–
Press the "Acknowledge error
4
" button
9. Check the current status of the parameter set
When commissioning a new integrated drive (spare part)
–
Open the "Identity
1
" tab
–
Check the current device ID in the "Device
2
" parameter. The device ID must correspond to the
drive system in use
–
0x000259 (601): ELGS-TB
–
0x00025A (602): ELGS-BS
–
0x00025B (603): EGSS-BS
–
0x00025C (604): ELGE-TB
–
0x00025E (606): EPCS-BS
With 0x000258 (600), EMCS-YY-ST spare part, the parameter set file was not updated successfully.
Follow the sequence from step "4. Repeat the "Open parameter set file".