Steps for updating the parameter set

4. Open the parameter set file (e.g. Festo-EGSS_...-20210209-IOLFW1.0.iolfw)

Open the "Firmware Update (Profile) 

1

" tab

Variants for opening the file:

Open the "File" tab and execute the "Open IODDs" submenu 

2

Via the key combination "Ctrl + u 

3

"

By drag-&-drop 

4

5. Load the parameter set file into the integrated drive

Press the "Update 

1

 button

The parameter set is transmitted 

2

The transfer is successfully completed 

3

6. Update the parameter set file in the integrated drive

An automatic restart is executed

The connection to the IO-Link master is interrupted 

1

After successful loading of the parameter file, the connection to the IO-Link master is automati-

cally established 

2

 or it must be established manually 

è

 step "3. Establish a connection to the

IO-Link master"

Steps for updating the parameter set

7. Open the IODD file of the drive unit (device description file)

Variants for opening the file:

Open the "File" tab and execute the "Open IODDs" submenu 

1

Via the automatic search 

2

1)

Via the key combination "Ctrl + o 

3

"

By drag-&-drop 

4

8. Acknowledge error (only if an error is pending)

Open the "Specialist (user role) 

1

" tab

Open submenus "Parameter 

2

" and "Control parameter 

3

Press the "Acknowledge error 

4

" button

9. Check the current status of the parameter set
When commissioning a new integrated drive (spare part)

Open the "Identity 

1

" tab

Check the current device ID in the "Device 

2

" parameter. The device ID must correspond to the

drive system in use

0x000259 (601): ELGS-TB

0x00025A (602): ELGS-BS

0x00025B (603): EGSS-BS

0x00025C (604): ELGE-TB

0x00025E (606): EPCS-BS

With 0x000258 (600), EMCS-YY-ST spare part, the parameter set file was not updated successfully.
Follow the sequence from step "4. Repeat the "Open parameter set file".