Steps for updating the parameter set
8. Eliminate incompatibility errors. Only if the error in question is displayed.
With error message "Parameter package download error - parameter set incompatible".
–
Restart the drive with power OFF/ON at the logic power supply 24 V DC [Pin 1].
Upload the parameter set to the integrated drive again and update it in the drive.
è
5. Upload the parameter set file to the integrated drive.
è
6. Update the parameter set file in the integrated drive.
–
Open the ‘Specialist (user role)’
1
tab.
–
Open the ‘Parameters’
2
and ‘Save parameters’
3
submenus.
–
In the ‘Save parameters’ parameter press the ‘Save parameter’
4
button.
9. Acknowledge error (only if an error is pending)
–
Open the "Specialist (user role)
1
" tab
–
Open submenus "Parameter
2
" and "Control parameter
3
–
Press the "Acknowledge error
4
" button
10. Check current status of the parameter set
–
Open the "Identity
1
" tab
–
Check the current device ID in the "Device
2
" parameter. The device ID must correspond to the
drive system in use
–
0x000259 (601): ELGS-TB
–
0x00025A (602): ELGS-BS
–
0x00025B (603): EGSS-BS
–
0x00025C (604): ELGE-TB
–
0x00025E (606): EPCS-BS
With 0x000258 (600), EMCS-YY-ST spare part, the parameter set file was not updated successfully.
Repeat the sequence from step "4. Open parameter set file".
Steps for updating the parameter set
11. Initialise end positions "Lim
In
/ Lim
Out
" and reference end position "Ref"
–
Open the "Specialist (user role)
1
" tab
–
Open the "Parameter
2
" and "System commands
3
" submenus
–
Execute the default command ""Reference" movement"
4
Press one of the two following buttons for the default commands:
–
Execute "Reference" movement (False)
4
(factory setting, motor-facing reference end position
"Ref")
–
Execute "Reference" movement (True)
5
(reference end position "Ref" motor facing away)
12. Save parameter set as factory setting
–
Open the "Specialist (user role)
1
tab
–
Open the "Parameter
2
" and "File handling commands
3
" submenus
–
In the "Activate file handling" parameter activate the "Activate file handing
4
" value and press
the "Write
5
" button
–
In the "Execute file handling" parameter select the "Overwrite factory settings
6
" value and
press the "Write
7
" button
1) The use of the function depends on the application software.
Tab. 8: Steps for updating the parameter set
Diagnostic messages when updating the parameter set
The table shows all diagnostic messages that may be shown when updating the
parameter set.
Event code Description
LED
Error code
(IO-Link)
C/Q
hex (dec)
0x1820
Parameter set not found
red light
0x0061
(97)
Remedy
–
Check parameter set selection
0x1821
Parameter set invalid
0x0062
(98)
Remedy
–
Overwrite parameter set (save)
Steps for updating the parameter set, 8. Elim-
inate incompatibility error.
0x1822
Parameter set incompatible
0x0063
(99)
Remedy
–
Overwrite parameter set (save)
Steps for updating the parameter set, 8. Elim-
inate incompatibility error.
0x1823
Parameter not found
0x0064
(100)
Remedy
–
Overwrite parameter set (save)
Steps for updating the parameter set, 8. Elim-
inate incompatibility error.
Tab. 9: "Parameter set error" diagnostic messages