1 Intended use

The bus node CTEU-PN is intended exclusively for use as a
participant (“I/O device”) in a PROFINET network.
The bus node may only be used in its original status
without unauthorised modifications and only in perfect
technical condition.
The specified limit values must be observed here.
The product is intended for use in industrial environ­
ments. Outside of industrial environments, e.g. in com­
mercial and mixed-residential areas, actions to suppress
interference may have to be taken.

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Comply with the legal rules and regulations and
standards, rules of the testing organisations and
insurance companies and national specifications
applicable for the location.

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Detailed information on commissioning is provided in
the documentation provided for the primary control
system.
Information about PROFINET:

è

 www.profinet.com

Information about products from Festo:

è

 www.festo.com/sp

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PI PROFIBUS PROFINET

®

, SIEMENS

®

, SIMATIC

®

,

TIA Portal

®

 are registered trademarks of the respective

trademark owners in certain countries.

For all available product documentation

è

 www.festo.com/pk

Qualified personnel

The product may only be commissioned by trained control
and automation technology professionals, who are famili­
ar with:
– the assembly, installation, operation and diagnosis of

control systems, networks and field bus systems

– the applicable regulations for accident prevention and

industrial safety

– the documentation for the product.

Service

Consult your local Festo repair service if you have any
technical problems.

2 Safety instructions

 Prior to any assembly or installation work, switch off

power supplies, disconnect the compressed air supply
and vent the pneumatics.

 For the electrical power supply, only use PELV circuits in

accordance with IEC 60204-1.

 Observe the handling specifications for electrostatically

sensitive devices.

 Use cover caps to seal unused connections to achieve

the required degree of protection.

 Use connection technology with the required degree of

protection.

3 Connections and displays

2

3

1

1

Netzwork connections (network ports TP1/TP2, field
bus interface)

è

 Section 3.1

2

Status LEDs

è

 Section 3.2, Section 7

3

Power supply connection (X0)

è

 Section 3.1.

I-port interface

The I-port interface is located on the underside of the bus
node.

3.1

Ports

Network connections

1)

Pin allocation

1

TD+

Transmitted data
(Transmit Data) +

2

RD+

Received data
(Receive Data) +

3

TD–

Transmitted data –

4

RD–

Received data –

housing

Shield/
FE

Shield/functional earth

2)

1) 2 x socket, M12, 4-pin, D-coded, according to IEC 61076-2; in­

stallation guidelines, line specification 

è

 Section 4.4

2) Connection to functional earth must be secured over the connec­

ted product 

è

 Section 4.3, “Equipotential bonding”

Power supply connection

1)

Pin allocation

1

24V

Operating voltage
Electronics/sensors
(power system)

PS

U

EL/SEN

2

24V

Load voltage
Valves/outputs
(Power Load)

PL

U

VAL/OUT

3

0V

Operating voltage

PS

U

EL/SEN

4

0V

Load voltage

PL

U

VAL/OUT

5

FE

Functional earth

2)

FE

1) Plug, M12, 5-pin, A-coded, according to IEC 61076-2
2) Connection to functional earth must be secured over the connec­

ted product 

è

 Section 4.3, “Equipotential bonding”

3.2

Indicators

Status LEDs

1)

Function

PS

Status of the operating voltage supply
(power system)

X1

Status of the internal communication between
the bus node and the connected product
(“I-Por t Device” 1 and/or “I-Port Device” 2)

2)

X2

NF

Network status/network failure
(Network Failure)

TP1

Connection status
(“Link” 1 and/or “Link” 2)

TP2

1) Other information

è

 Section 7

2) Accessories with two I-port interfaces required to connect up

two products, e.g. the decentralised electric sub-base CAPC

è

www.festo.com/catalogue

4 Assembly, disassembly, installation

 Warning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Uncontrolled movement of the actuators, loose tubing,
undefined switching states of the electronics.

Injury caused by moving parts, damage to machine and to system.
Before mounting and installation work:
 Switch off the power supply
 Switch off the compressed air supply.
 Vent the pneumatics.

4.1

Mounting the bus node

For mounting the bus node, a product with I-port interface
is required (“I-port device”), e.g. valve terminal with I-port
interface or the decentralised electrical connection box,
type CAPC-... .

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Assembly of the bus node on the decentralised electric
sub-base 

CAPC 

è

 Assembly instructions CAPC-...

1. Check seal and sealing surfaces of the bus node and the

product with the I-port interface. Replace damaged
parts.

2. Push the bus node onto the product carefully and

without tilting and press up to the stop.

3. Gently tighten down the self-tapping screws, using ex­

isting threads.

4.Tighten the screws with tightening torque:

0.7 Nm ± 0.1 Nm.

4.2

Dismantling the bus node

1. Unscrew the screws.
2. Pull the bus node off without tilting it.

4.3

Connecting the power supply

 Warning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical voltage

Injury caused by electric shock, damage to machine
and to system.
 For the electrical power supply, use only PELV circuits

in accordance with IEC60204-1 (Protective Extra-
Low Voltage, PELV).

 Observe the general requirements IEC60204-1 of

the PELV power circuits.

 Only use power sources that guarantee reliable elec­

trical isolation of the operating and load voltage in
accordance with IEC60204-1.

 Always connect all circuits for operating and load

voltage supplies U

EL/SEN

 and U

VAL/OUT

.

Fuse protection

The bus node also supplies operating and load voltage to
products connected via the I-port interface.
 Secure operating voltage U

EL/SEN

 and load voltage

U

VAL/OUT

 separately.

 Take due account of the current consumption of con­

nected products during design and protection of the
power supply.

 Observe power rating of power supply (no bus node-in­

ternal overload protection for the connected products)

è

 Section 10.

 Ensure correct polarity (no bus node-internal reverse

polarity protection for the connected products).

Potential equalisation (earthing measures)

 Connect the functional earth (FE) connections of the

connected products to the earth potential with a short
conductor with the greatest possible cross section
(

 4 mm

Cu).

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Functional test

– The 

PS

 LED lights up when operating voltage is ap­

plied (within permitted range).

– LED 

X1

 or 

X2 

lights up green if a product with an I-port

interface is connected up correctly (

è

 Section 7).

4.4

Connecting to the network

Installation guidelines

 Warning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical voltage

Injury caused by electric shock, damage to machine
and to system.
 For the electrical power supply to 

all PROFINET net­

work participants

 (“IO Devices”) and other network

components (e.g. on switches and routers) only use
PELV circuits in accordance with IEC60204-1.

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Data transmission errors

Malfunction:
If installation has not been carried out correctly and if
high baud rates are used, data transmission errors may
occur, e.g. as a result of signal reflections and attenu­
ations.
 Connect screening to all network cables
 Wherever possible, only ground screening once (“star

topology”) to prevent ground loops

 Observe installation guidelines for the PROFINET

user organisation (PNO):

è

 www.profinet.com

è

 www.profibus.com/download/

è

 PROFINET installation guidelines

(“PROFINET Installation Guide”,
“Installation Guideline PROFINET Part 2…”)

 Observe port and cable specifications:

è

 PROFINET installation guidelines

è

 Documentation relating to the control system

è

 Section 3.1, table “network connections”

è

 Table “Line specification”.

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unauthorised access

 to the product can cause damage

or malfunctions.
When connecting the product to a network:
 Protect the network from unauthorised access.
Measures for protecting the network include:
– Firewall
– Intrusion Prevention System (IPS)
– Network segmentation
– Virtual LAN (VLAN)
– Virtual private network (VPN)
– Security at physical access level (Port Security).
Further information:

è

 Guidelines and standards for security in informa­

tion technology, e.g. IEC 62443, ISO/IEC 27001.

An access password protects only against accidental
changes.

Use of switches and routers

When using the PROFINET function “Fast Start-up” (FSU):
 Only use switches and routers that support the “Fast

Start-up” function.

 Connect up network participants (“IO devices”) and

network components via LAN (“wire-bound”)
(no support of “Fast Start-up” by Industrial Wireless
LAN Access Points, IWLAN).

Use of crossover cables

When using patch cables and crossover cables in the
same network:
 Ensure that the crossover detection (“Crossover Detec­

tion”, “Auto-MDI” or “Autocrossover/Autonegotiation”)
is enabled in the control system.

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

When using the PROFINET function “Fast Start-up”
(FSU), crossover detection is not available.
 Observe notice relating to “Fast Start-up”

è

 Section 5.10.

Cable specification

Cable

Ethernet twisted pair cable, shielded
(Shielded Twisted Pair, STP)

Transmission class
(Link Class)

Category Cat 5

Cable diameter

1)

6 ... 8 mm

Core cross section

0.14 ... 0.75 mm

2

;

22 AWG required for max. connection
length between network participants
(End-to-end-Link)

Connection length

2)

max. 100 m PROFINET-End-to-end-Link

1) When using plug NECU­M­S­D12G4­C2­ET
2) In accordance with specification for PROFINET networks

(PROFINET installation guideline), based on ISO/IEC 11801,
ANSI/TIA/EIA-568:

è

 www.profinet.com

è

 www.profibus.com/download/

Strain relief

When mounting on a moving part of a machine:
 Provide the network cable with strain relief.

4.5

Ensuring the protection class

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Short circuit

Malfunction or damage to the electronics
 Use connection technology (interconnecting cables,

push-in connectors, adapters) with the required de­
gree of protection, e.g. plug NECU-M-S-D12G4-C2-ET.

 Use cover caps to seal unused connections, e.g.

cover cap ISK-M12:

è

 Accessories

è

 www.festo.com/catalogue

 Do 

not

 remove sealing plug from underside of bus

node.

 Only when mounting bus node on the decentralised

electric sub-base 

CAPC

: Replace sealing plug on

underside fo bus node 

è

 Assembly

instructions CAPC-...

5 Commissioning, configuration and parameterisation

Commissioning, configuration and parametrisation of the
bus node is dependent on the primary control system
used. The basic approach and required configuration data
are explained in the following sections.

 Warning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Uncontrolled movement of the actuators, loose tubing,
undefined switching states of the electronics.

Injury caused by moving parts, damage to machine and to system.

 Before commissioning, ensure that the connected

products do not perform any uncontrolled
movements.

 Observe commissioning notices in the control system

documentation.

No automatic checking of configuration and
parameterisation: The bus node and the connected
products also go into operation if configuration is
incorrect.

5.1

Switching on the power supply

If the control system and network participants have sep­
arate voltage supplies, the devices must be switched on
in the following sequence:
1. Switch on power supply to all network participants

(“IO Devices”).

2. Switch on power supply to control system.

5.2

Addressing

PROFINET uses module-oriented addressing, i.e. each
network participant is addressed separately (in contrast
to block-oriented addressing of other fieldbus systems).
The controller uses the following for addressing:
– Fieldbus device names, short form “Device Names”

è

 Section 5.6

– IP addresses 

è

 Section 5.7

– Input/output addresses (I/O addresses) 

è

 Section 5.9.

 Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Addressing errors

Incomplete faulty configuration, malfunction, fault in­
dication
The address space of the bus node is limited
(

è

 Section 10, Technical data).

 Determine the number of assigned inputs and out­

puts prior to commissioning.

Basic rules for addressing

– Addressing: 

Module-oriented, byte-by-byte

. Modules

with less than 8 bits occupy 8 bits of address space
and/or 1 byte of address space, but which do not use
all this space.

– The address assignment of the inputs does 

not depend

on the address assignment of the outputs.

5.3

Import device master file (GSDML file)

A device master file (GSD) in XML format (GSDML) is
needed for configuration, parameterisation and program­
ming of the bus node. The GSDML contains all information
required to connect into the hardware configuration of
the control system, e.g. Siemens SIMATIC STEP 7.

Download of the GSDML file

è

 www.festo.com/sp

1. Enter search term: “GSDML”.
2. Click “Firmware and drivers” tab.
3. Click “File and language versions” link.
4.Transmit file “GSDML-V...-Festo-CTEU-...zip” to the con­

trol system and unpack it.
The file contains:
– one or more GSDML files

(GSDML-V...-Festo-CTEU-...xml)

– a symbol file (GSDML-...-...-CTEU.bmp)
– optionally a “Read Me” file with notes on the current

GSDML versions.

 Observe comments in the “Readme” file.

Installation of the GSDML file

è

 Documentation of the control system

After installation of the GSDML file, all available network
participants (“IO devices”, bus nodes) and field devices
(“Field devices”), e.g. products with an I-port interface
appear in the hardware directory of the control system
(“Catalog”).
Example of Siemens SIMATIC S7-1200, TIA portal:
 Install GSDML file (“Install general station description

file (GSD)”).

Operating instructions