background image

1.      Installation

1−19

Festo  P.BE−CPX−FB23−EN    en  0308NH

1.3

Connecting  the  field  bus

1.3.1

Field  bus  cable

Please  note

With  incorrect  installation  and  high  transmission  rates,
faults  in  data  transmission  my  occur  due  to  signal  reflec
tions  and  attenuations.

The  causes  of  transmission  faults  can  be:

 missing  or  incorrect  terminating  resistor

 incorrect  screening/shield  connection

 branches

 transmission  over  long  distances

 unsuitable  cables.

Observe  the  cable  specifications.  Refer  to  your  controller
manual  for  information  on  the  type  of  cable  to  be  used.

Please  note

If  the  valve  terminal  is  fitted  into  a  moving  part  of  a  ma
chine,  the  field  bus  cable  on  the  moving  part  must  be  pro
vided  with  strain  relief.  Note  also  the  relevant  specifica
tions  in  EN60204  part  1.

Bus  length

Exact  details  on  the  bus  length  can  be  found  in  section  1.3.2
and  in  the  manuals  for  your  control  system.

Содержание CPX-FB23

Страница 1: ...Electronics manual CPX field bus node Type CPX FB23 Field bus protocol CC Link CPX terminal Manual 526 404 en 0308NH 653 638...

Страница 2: ......

Страница 3: ...Festo AG Co KG D 73726 Esslingen Federal Republic of Germany 2003 Internet http www festo com E Mail service_international festo com The copying distribution and utilization of this document as well...

Страница 4: ...Contents and general instructions II Festo P BE CPX FB23 EN en 0308NH...

Страница 5: ...1 19 1 3 1 Field bus cable 1 19 1 3 2 Field bus baud rate and field bus length 1 21 1 3 3 Pin assignment of field bus interface 1 23 1 3 4 Connecting the field bus 1 24 1 3 5 Bus termination with ter...

Страница 6: ...messages of the field bus node CPX FB23 3 5 3 3 Diagnosis via LEDs 3 6 3 3 1 Normal operating status 3 7 3 3 2 CPX specific LEDs 3 8 3 3 3 CC Link specific LEDs 3 11 3 3 4 Possible operating states o...

Страница 7: ...the documentation supplied with the product are permitted in faultless technical condition The maximum values specified for pressures temperatures electrical data torques etc must not be exceeded Obs...

Страница 8: ...rogramming and diagnosing with the CPX field bus node for CC Link General information on the field bus CC Link can be found in the documentation for your CC Link master and the relevant control system...

Страница 9: ...tween the following danger warnings Warning This means that failure to observe this instruction may result in serious personal injury or damage to property Caution This means that failure to observe t...

Страница 10: ...ions tips and references to other sources of information Accessories Information on necessary or sensible accessories for the Festo product Environment Information on environment friendly use of Festo...

Страница 11: ...R14 see type plate This manual contains specific information on installing com missioning programming and diagnosing with the CPX field bus node for CC Link General basic information on the functioni...

Страница 12: ...e CPX as well as type CPA and midi maxi pneumatic interfaces CPX analogue I O modules type P BE CPX AX Connection types and instructions on fitting installing and commissioning CPX analogue I O module...

Страница 13: ...porated in a CPX terminal CPX terminal Modular electric terminal type 50 Data The CPX terminal provides settings and diagnostic information in the form of data Data can be read but not modified DIL sw...

Страница 14: ...rface The pneumatic interface is the interface between the modular electrical peripherals and the pneumatics PLC IPC Programmable logic controller industrial PC Status bits Internal inputs which suppl...

Страница 15: ...Installation 1 1 Festo P BE CPX FB23 EN en 0308NH Chapter 1...

Страница 16: ...1 Removing fitting the DIL switch cover 1 7 1 2 2 Setting the DIL switches 1 8 1 3 Connecting the field bus 1 19 1 3 1 Field bus cable 1 19 1 3 2 Field bus baud rate and field bus length 1 21 1 3 3 Pi...

Страница 17: ...s the pin assignment of the power supply Further information Information on fitting and installing the complete CPX terminal can be found in the CPX system manual P BE CPX SYS Information on installin...

Страница 18: ...roperty Before carrying out installation and or maintenance work switch off the following the compressed air supply the operating and load voltage supplies Caution The CPX field bus node may be damage...

Страница 19: ...tch cover 4 Service interface for handheld etc 3 4 1 2 RUN PS PL SF M SD RD Fig 1 1 Connecting and display elements on the CPX field bus node Dismantling and fitting The field bus node is fitted in a...

Страница 20: ...s node in the manifold sub base Make sure that the grooves with the terminals for electrical con tact on the bottom of the field bus node lie directly above the contact rails Press the field bus node...

Страница 21: ...ons for handling electrostatically sensitive components In this way you will avoid damage to the electronics 1 2 1 Removing fitting the DIL switch cover In order to set the CPX field bus node you must...

Страница 22: ...CC link slave address 4 DIL switch 4 Number of stations per slave 5 DIL switch 5 HOLD CLEAR System diagnosis 1 2 1 2 ON ON 1 2 3 1 2 3 4 5 6 7 8 ON 1 2 1 2 ON ON 4 5 Fig 1 3 DIL switches in the field...

Страница 23: ...directly by the higher order PLC IPC An FEC integrated in the CPX terminal functions as a passive function module without controller 1 1 OFF factory setting Reserved for future extensions Operating mo...

Страница 24: ...itch 2 Baud rate Setting of DIL switches 1 2 and 2 156 kBd 1 2 OFF 2 1 OFF 2 2 OFF 625 kBd 1 2 ON 2 1 OFF 2 2 OFF 2 5 MBd 1 2 OFF 2 1 ON 2 2 OFF 5 MBd 1 2 ON 2 1 ON 2 2 OFF 10 MBd 1 2 OFF 2 1 OFF 2 2...

Страница 25: ...3 4 5 6 7 8 3 8 reserved 3 7 22 x 10 3 6 21 x 10 3 5 20 x 10 3 4 23 3 3 22 3 2 21 3 1 20 40 20 10 8 4 2 1 Tab 1 3 CC Link slave address Please note CC Link slave addresses may only be assigned once pe...

Страница 26: ...th a Number of slaves with 1 station b Number of slaves with 2 stations c Number of slaves with 3 stations d Number of slaves with 4 stations The following condition must be fulfilled 16 x A 54 x B 88...

Страница 27: ...ON OFF OFF OFF OFF 22 OFF ON OFF OFF OFF ON OFF 7 ON ON ON OFF OFF OFF OFF 23 ON ON OFF OFF OFF ON OFF 8 OFF OFF OFF ON OFF OFF OFF 24 OFF OFF ON OFF OFF ON OFF 9 ON OFF OFF ON OFF OFF OFF 25 ON OFF...

Страница 28: ...ON 39 ON OFF OFF ON ON ON OFF 55 ON OFF ON OFF ON OFF ON 40 OFF OFF OFF OFF OFF OFF ON 56 OFF ON ON OFF ON OFF ON 41 ON OFF OFF OFF OFF OFF ON 57 ON ON ON OFF ON OFF ON 42 OFF ON OFF OFF OFF OFF ON 58...

Страница 29: ...mmunication between the field bus node and the FEC 4 1 OFF 4 2 OFF 2 stations per slave Not permitted 4 1 ON 4 2 OFF 3 stations per slave 4 1 OFF 4 2 ON 4 stations per slave 4 1 ON 4 2 ON factory sett...

Страница 30: ...d in section 2 1 Please note Depending on the number of stations set per slave subse quent slave addresses are also assigned CC Link slave addresses may only be assigned once per field bus line Exampl...

Страница 31: ...ou can set the HOLD CLEAR function of the CPX terminal Operating mode Setting DIL switch 5 1 CLEAR Logical communication outputs are reset in the event of field bus communication faults 5 1 OFF factor...

Страница 32: ...5 2 OFF factory setting Systemdiagnosis see sections 2 1 6 Tab 2 9 and 3 4 5 2 ON Tab 1 10 System diagnosis Please note If the system diagnosis with the status bits or the I O diag nostic interface i...

Страница 33: ...ncorrect screening shield connection branches transmission over long distances unsuitable cables Observe the cable specifications Refer to your controller manual for information on the type of cable t...

Страница 34: ...nce 110 15 Isolationresistor 10 000 M km Electric strength 500 V DC for 1 minute Reference cable FANC 110SBH 0 5 mm2 x 3 Kurashige Electronics Inc terminating resistor 110 0 5 W Otherpossibilities CSF...

Страница 35: ...110 Baud rate Cable length between stations Max total cable length 156 kBd 1200 m 625 kBd 600 m 2 5 MBd 0 2 m for all baud rates 200 m 5 MBd 150 m 10 MBd 100 m Master station Remote I O station Remot...

Страница 36: ...e CC Linkreference cable CC Link high perfomance cable cannot be used e g FANC SBH The use of different cables is not possible Branch line sub bases Commercially avail able branch line sub bases Remov...

Страница 37: ...n c DA DG n c n c 1 n c DB n c n c SLD FG Not connected Data A Data reference potential data ground Not connected FE via R C combination 1 Not connected Data B Not connected Not connected Cable scree...

Страница 38: ...k You can connect the CPX terminal to the field bus CC Link in one of the following ways Sub base plug Remarks Festo sub base type FBA 1 KL 5POL Protection class IP20 connection with cable shoes Festo...

Страница 39: ...he sub bases use claw cable shoes similar to DIN 46225 form B size B4 1 1 Terminal block FG ground SLD cable screen ing shield DG Data Ground DB Data B DA Data A 2 Connect FG with low impedance to FE...

Страница 40: ...ase note The clamp strap in the field bus plug is connected capaci tively internally with the metal housing of the sub D plug Connection NC must not be connected 1 Hinged cover with viewing window 2 F...

Страница 41: ...ce with the protective cap supplied Use the Festo sub D plug Note that only the Festo sub D plug guarantees compliance with protection class IP65 IP67 Connecting with sub D plugs of other manufacturer...

Страница 42: ...between Data A and Data B is used as a bus termination depending on cable type see table 1 Festo field bus plug 2 Connection for continuing field bus sealed with a blanking plug 3 Terminating resisto...

Страница 43: ...e with EN 60950 VDE 0805 By the use of PELV power units protection against electric shock protection against direct and indirect contact is guar anteed in accordance with EN 60204 1 IEC 204 Safety tra...

Страница 44: ...ld base with Systemfeed type CPX GE EV S Additionalfeed type CPX GE EV Z Valve supply type CPX GE EV V 2 3 4 1 1 24 VEL SEN 2 24 VVAL 24 VOUT 3 0 VEL SEN 0 VVAL 0 VOUT 4 Earth ground connection 1 Not...

Страница 45: ...Commissioning 2 1 Festo P BE CPX FB23 EN en 0308NH Chapter 2...

Страница 46: ...igned stations 2 10 2 1 4 Addressing examples examples of address assignment 2 11 2 1 5 Address assignment after extension conversion 2 21 2 1 6 CC Link memory mapping 2 23 2 1 7 Bus configuration and...

Страница 47: ...ld This enables e g the setting of debounce times or signal lengthening Further information Before commissioning you must install the CPX terminal correctly Information on this can be found in chapter...

Страница 48: ...itches The 16 bits of the system diagnosis must be treated like inputs and outputs They occupy the word range of sta tion 1 16 input and 16 output addresses Providing no detailed diagnostic informatio...

Страница 49: ...DA 4DO 4 bits Digital 8 input module CPX 8DE 8DI 1 byte Digital multi I O module CPX 8DE 8DA 8DI 8DO 1 byte 1 byte Analogue 2 input module CPX 2AE U I 2AI 2 words Analogue 2 output module CPX 2AA U I...

Страница 50: ...alve coils 1 24 valve coils 22 usable CPX GP CPA 10 CPX GP CPA 14 CPA10 14 1 byte 2 bytes 3 bytes Pneumatic interface for Midi Maxi valves type 03 with DIL switch setting 4 1 8 valve coils 1 16 valve...

Страница 51: ...of type 32 MPA pneumatic modules From a technical point of view the individual MPA pneu matic modules each provide an electric module with digi tal outputs for controlling the fitted valves Please no...

Страница 52: ...les of the same type are arranged linearly in the address range providing they are arranged one behind the other I Os of the same type each occupy their own station in ascending order without gaps dig...

Страница 53: ...assigned in the free bit range RX RY of stations 1 to 4 Arrangement from left to right corre sponding to the address range one next to the other beyond the station limits ascending without gaps 4 Anal...

Страница 54: ...r slave a nominal actual comparison is made of the assigned address range in the starting phase of the field bus node If the number of stations selected by means of DIL switches is less than the recog...

Страница 55: ...1 O15 O0 0 1 2 3 System diagnosis 16 I O reserved reserved reserved reserved reserved reserved Fig 2 1 CC Link memory mapping 16 digital inputs and outputs Digital I O modules 48 I O 2 stations I O d...

Страница 56: ...16 Fig 2 3 CC Link memory mapping 80 digital inputs and outputs Digital I O modules 112 I O 4 stations I O data in the bit range System diagnosis optional I digital input O digital output Bit range RX...

Страница 57: ...l reserved reserved reserved Control reserved AI0 AO0 Fig 2 5 CC Link memory mapping 16 analogue inputs and outputs Analogue I O modules 12 AI AO with system diagnosis 2 to 4 stations 2 4 AI AO 3 8 AI...

Страница 58: ...ange RWr RWw Inputs Outputs Station 1 Station 3 Station 2 0 1 2 3 AI1 AI2 AO1 AO2 AI3 AO3 Station 4 RR Remote Ready Control reserved AI0 AO0 0 1 2 3 System diagnosis 16 I O reserved reserved reserved...

Страница 59: ...put module 8DI 1 byte 2 Digital 8 input module 8DI 1 byte 3 Digital 4 output module 4DO 4 bits 4 Digital multi I O module 8DI 8DO 1 byte 1 byte 5 Digital 4 output module 4DO 4 bits 6 Pneumatic interfa...

Страница 60: ...DO 8DO 16 O 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1...

Страница 61: ...8DI 1 byte 2 Digital 8 input module 8DI 1 byte 3 Digital 4 output module 4DO 4 bits 4 Digital multi I O module 8DI 8DO 1 byte 1 byte 5 MPA pneumatic module type 32 with electrical isolation MPA1G 1 by...

Страница 62: ...Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready...

Страница 63: ...al 8 input module 8DI 1 byte 4 Analogue 2 output module 2AO 2 bytes 3 2 words 5 MPA pneumatic module type 32 with electrical isolation MPA1G 1 byte 6 MPA pneumatic module type 32 with electrical isola...

Страница 64: ...1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr...

Страница 65: ...be shifted This applies in the following cases Additional modules are inserted between existing modules Existing modules are removed or replaced by other mod ules which have more or fewer input outpu...

Страница 66: ...valve side the pneumatic interface has been set to 8 O As a result of these changes only one station is now necessary System diagnosis Inputs RX RWr Assigned addresses Outputs RY RWw Assigned addresse...

Страница 67: ...F reserved reserved reserved reserved reserved reserved reserved reserved reserved reserved reserved Remote ready 1 reserved reserved reserved reserved RY n m 0 RY n m 1 RY n m 2 RY n m 3 RY n m 4 RY...

Страница 68: ...d address in memory mapping master depends on station address set Tab 2 8 System diagnosis I O diagnostic interface and status bits System diagnosis see CPX system manual Slave Master RWr n 0 Bit 15 1...

Страница 69: ...gital outputs 32 39 Digital outputs 40 47 RX n 3 0 7 RX n 3 8 F Digitale Eing nge 48 55 1 Digital inputs 56 63 1 RY n 3 0 7 RY n 3 8 F Digital outputs 48 55 1 Digital outputs 56 63 1 Station 3 RX n 4...

Страница 70: ...t 1 m 1 5 9 13 RWr n m 2 Analogue input 2 m 2 6 10 14 RWw n m 2 Analogue output 2 m 2 6 10 14 RWr n m 3 Analogue input 3 m 3 7 11 15 RWw n m 3 Analogue output 3 m 3 7 11 15 n Assigned address in memor...

Страница 71: ...ve RY n m Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Signal Reserved S3 S2 S1 S0 S Enable Disable channel 0 1 2 3 or 4 5 6 7 or 8 9 10 11 or 12 13 14 15 Control bit for the relevant analogue output The...

Страница 72: ...nning cycle the status if there is a CPU fault in the main computer station data settings of the slave the station type CPX FB23 remote device station the number of stations occupied by the slave 1 4...

Страница 73: ...Network parameters 2 CC Link parameters 3 Set station data see Fig 2 16 4 Status if there is a CPU fault in the main computer 5 Number of slaves to be connected again during a scanning cycle 6 Configu...

Страница 74: ...umber of the slave CC Link slave address station number station address 2 Station type for CPX FB23 remote device station 3 Set the module as reserved or invalid 4 Number of stations per module Fig 2...

Страница 75: ...ion Saves the input data of the master station Writeonly 1E0H 2DFH Decentral register RWw output data Master station Transmitted data are saved in the decentral local stations Read write Local station...

Страница 76: ...tions which can be connected to the system again during a scanning cycle Setting range 1 10 6H Status if there is a CPU fault in the main computer The status if there is a CPU fault in the main comput...

Страница 77: ...ce station Stations 1 Slave occupies 1station 2 Slave occupies 2 stations 3 3 stations 4 4 stations CC Link slave address 1 64 01H 40H x CC Link slave address Tab 2 15 Station data Examples Memory add...

Страница 78: ...ned addresses Outputs RY RWw Assigned addresses 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Ready 1 2 RX RY RWr RWw Remote Rea...

Страница 79: ...ollowing parametriz ings system parametrizing e g switching off fault messages etc module parametrizing module and canal specific e g Monitoring settings in the event of faults setttings for Forcing A...

Страница 80: ...the M LED lights up permanently after the system start then System start with saved parametrizing and saved CPX system equipment is set Caution With CPX terminals on which the M LED lights up perma ne...

Страница 81: ...rs and data see CPX system manual It is possible to check the current parameter setting by means of the master The parameters cannot be modified Expensiveprogram ming Tab 2 17 Parametrizing Please not...

Страница 82: ...onfiguration and parametrizing faults during commissioning Observe the general commissioning instructions in the CPX system Check the DIL switch settings before using and replacing CPX terminals Check...

Страница 83: ...setting see section 1 2 2 The following field bus communication faults count as fault cases communication interruption communication time out Depending on the DIL switch setting the CPX terminal react...

Страница 84: ...ord range RWw The following table shows the reaction according to CC Link specifications Outputs CPU status RUN PAUSE STOP RY output Refresh Clear In the STOP status the outputs are reset RWw output R...

Страница 85: ...oltage drop network operation will not be impaired A defective slave station can be replaced whilst the net work is in operation the voltage of the station to be re placed must be switched off When a...

Страница 86: ...2 Commissioning 2 42 Festo P BE CPX FB23 EN en 0308NH...

Страница 87: ...Diagnosis and error treatment 3 1 Festo P BE CPX FB23 EN en 0308NH Chapter 3...

Страница 88: ...ies 3 4 3 2 Fault messages of the field bus node CPX FB23 3 5 3 3 Diagnosis via LEDs 3 6 3 3 1 Normal operating status 3 7 3 3 2 CPX specific LEDs 3 8 3 3 3 CC Link specific LEDs 3 11 3 3 4 Possible o...

Страница 89: ...ticpossibilities LEDs status bits I O diagnostic interface handheld Further information Information on the general diagnosis of the CPX terminal can be found in the CPX system manual P BE CPX SYS Inf...

Страница 90: ...h the normal inputs Fast access to fault messages irrespective of the module and master Section 3 4 1 and CPX system manual I O diagnostic interface The I O diagnostic interface is a bus independentdi...

Страница 91: ...special faults Fault number Fault class Operating status Fault elimination 70 2 Set number of stations too small Check the equipment fitted on the CPX terminal and the number of stations required and...

Страница 92: ...ules can be found in the manual for the relevant module LEDs on field bus node CPX FB23 The LEDs on the cover indicate the operating status of the CPX field bus node 1 CPX specific LEDs PS green PL gr...

Страница 93: ...Normal operating status In the normal operating status all green LEDs light up The yel low LEDs light up or flash The red LEDs do not light up LED display Operating status PS PL SF RUN SD RD M All gre...

Страница 94: ...te short circuit overload on module side 2 Depending on the parametrizing of the module module parameter The sensor supply voltage is automaticallyswitched on again when the short circuit has been eli...

Страница 95: ...ystem manual LED flashes ON OFF Fault fault class 2 See description of fault numbers in the CPX system manual See specific faults of the CPX FB23 section 3 2 LED flashes ON OFF Serious fault fault cla...

Страница 96: ...t Parameters and CPX equip ment status are saved remanently external parametrizing is blocked 1 Caution when replacing CPX terminals with saved parametrizing With these CPX terminals the parame trizin...

Страница 97: ...lt Data communication OK See section 3 3 4 LED is out ON OFF Data communication is not yet started Data communication faulty Timeout Hardware reset FAULT data communication faulty LED green Sequence S...

Страница 98: ...g faulttreatment LED flashes ON OFF CPX terminal sends data See section 3 3 4 LED is out ON OFF CPX terminal does not send data RD Receive Data LED yellow Sequence Status Meaning faulttreatment LED li...

Страница 99: ...nnot replay the data received cause a CRC fault Normalcommunication No data for the master Field bus node replies to a request for data but the Refresh Reception has caused a CRC fault Data for the ma...

Страница 100: ...hese status bits are treated like inputs and are transmitted to the master with the other inputs There they can be interro gated linked and processed as normal inputs The status bits always occupy the...

Страница 101: ...4 Undervoltage Type of fault 5 Short circuit overload 6 Wire fracture 7 Other faults Tab 3 4 Overview of status bits If all status bits supply a 0 signal no fault will be registered If various faults...

Страница 102: ...g Trace 16 input bits and 16 output bits via which all diagnostic data can be read are available for accessing the system diagnosis Please note In order to use the I O diagnostic interface the system...

Страница 103: ...factory setting or retain their status see section 2 3 1 Warning Make sure that valves and outputs are put into a safe state if the faults named occur An incorrect status of the valves and outputs ca...

Страница 104: ...3 Diagnosis and error treatment 3 18 Festo P BE CPX FB23 EN en 0308NH...

Страница 105: ...Technical appendix A 1 Festo P BE CPX FB23 EN en 0308NH Appendix A...

Страница 106: ...ppendix A 2 Festo P BE CPX FB23 EN en 0308NH Contents A Technical appendix A 1 A 1 Technical specifications of field bus node type CPX FB23 A 3 A 2 Accessories A 5 A 3 Default parametrizing of the CPX...

Страница 107: ...letely plug connector as per Accessories plugged in or fitted with protective cap IP65 IP67 IP20 Module code CPX specific Moduleidentifier handheld Remote I O 206 Remote controller 157 Remote I O FB23...

Страница 108: ...ansmission speeds 156 kBd 625 kBd 2 5 MBd 5 MBd 10 MBd Coupling and uncoupling during operation Yes online return function slave station cut off function Cable type Reference cable Kurashige Electroni...

Страница 109: ...rs are used for the field bus connection the flat screws on the field bus node must be re placed by threaded sockets FBA 1 KL 5POL Sub base Sub base for field bus connec tion 9 pin sub D IP20 ISK M12...

Страница 110: ...o Default setting Monitoring Short circuit overload in sensor supply SCS Short circuit overload at outputs SCO Undervoltage at outputs Vout Undervoltage at valves Vval Short circuit at valves SCV 4401...

Страница 111: ...end filter Defines whether current faults are to be recorded or not 3484 Record current faults fault end filter inactive Fault number filter Suppresses or records exclusively certain faults 3484 Faul...

Страница 112: ...number 1 10 counting of the modules from left to right beginning with 0 x channel number valve number 0 25 Midi maxi 0 21 CPA 2 Access is made protocol specific see manual for handheld Tab A 7 Parame...

Страница 113: ...0 10 counting of the modules from left to right beginning with 0 x channel number 0 7 for CPX 8DE 0 3 for CPX 4DE 2 Access is made protocol specific see manual for handheld Tab A 9 Parameters of the i...

Страница 114: ...1 Switch Vsen on again Vout remains switched off Input debounce time 4828 m 64 1 1 3 ms Signal lengthening time 4828 m 64 1 1 15 ms Signal lengthening channel x 1 Channel by channel enable channel 0 7...

Страница 115: ...ing wire fracture Monitoringparametrizingfaults 4828 m 64 6 1 4828 m 64 7 1 Inactive Inactive Inactive Active Signal range channel x 1 Channel by channel setting of the signal range 4828 m 64 8 1 Use...

Страница 116: ...ingvalue above rated range upper limit value Short circuit overload at output Monitoringwirefracture idling Monitoringparametrizingfaults 4828 m 64 6 1 4828 m 64 7 1 Active Active Active Inactive Acti...

Страница 117: ...Index B 1 Festo P BE CPX FB23 EN en 0308NH Appendix B...

Страница 118: ...B Index B 2 Festo P BE CPX FB23 EN en 0308NH Contents B Index B 1 B 1 Index B 3...

Страница 119: ...A 5 Additional supply 1 30 Addressing 2 28 Addressing examples 2 11 Addressing rules 2 8 B Baud rate 1 10 1 21 Bus configuration 2 28 Bus termination 1 28 C Cable Field bus 1 19 CC Link slave address...

Страница 120: ...es Setting 1 8 Dismantling 1 5 E Electrical connecting and display elements 1 5 F Field bus baud rate 1 21 Field bus cable 1 19 Field bus length 1 21 Fitting 1 5 H HOLD 2 39 HOLD CLEAR 1 17 2 39 I I O...

Страница 121: ...1 9 P PELV 1 29 Pictograms VIII Pin assignment Field bus interface 1 23 Power supply 1 29 R RAS 2 41 RUN PAUSE 2 40 S Screening shield connection 1 25 1 26 Service V Setting Baud rate 1 10 CC Link sla...

Страница 122: ...Festo P BE CPX FB23 EN en 0308NH Stations Number 2 10 Status bits 3 14 STOP 2 40 Strain relief 1 19 Switch cover Removing and fitting 1 7 System supply 1 30 T Target group V Text markings VIII V Valve...

Отзывы: