1. Installation
1−21
Festo P.BE−CPX−FB23−EN en 0308NH
1.3.2
Field bus baud rate and field bus length
The maximum permitted field bus length depends on the
baud rate used. The following table shows the baud rates
which can be used (CC−Link version 1.10 compatible refer
ence cable, terminating resistor 110 ).
Baud rate
Cable length between stations
Max. total cable length
156 kBd
1200 m
625 kBd
600 m
2.5 MBd
> 0.2 m (for all baud rates)
200 m
5 MBd
150 m
10 MBd
100 m
Master
station
Remote I/O station/
Remote device
station
1)
Local station/
intelligent device
station
Local station/
intelligent device
station
Cable length
between stations
Total cable length
Remote I/O station/
Remote device
station
1)
1)
CPX terminal with field bus node CPX−FB23 = remote device station
Tab.1/11:
Baud rate and field bus length
Содержание CPX-FB23
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE CPX FB23 EN en 0308NH...
Страница 15: ...Installation 1 1 Festo P BE CPX FB23 EN en 0308NH Chapter 1...
Страница 45: ...Commissioning 2 1 Festo P BE CPX FB23 EN en 0308NH Chapter 2...
Страница 86: ...2 Commissioning 2 42 Festo P BE CPX FB23 EN en 0308NH...
Страница 87: ...Diagnosis and error treatment 3 1 Festo P BE CPX FB23 EN en 0308NH Chapter 3...
Страница 104: ...3 Diagnosis and error treatment 3 18 Festo P BE CPX FB23 EN en 0308NH...
Страница 105: ...Technical appendix A 1 Festo P BE CPX FB23 EN en 0308NH Appendix A...
Страница 117: ...Index B 1 Festo P BE CPX FB23 EN en 0308NH Appendix B...
Страница 118: ...B Index B 2 Festo P BE CPX FB23 EN en 0308NH Contents B Index B 1 B 1 Index B 3...