1. Installation
1−15
Festo P.BE−CPX−FB23−EN en 0308NH
Setting the number of stations per slave or the number of
I/O bytes
4
The function of this DIL switch depends on the set operating
mode of the CPX terminal (see also Tab.1/1).
Operating mode
Remote I/O
Operating mode Remote
Controller
Setting DIL switch 4
Number of stations per
slave
Number of I/O bytes
1 station per slave
Reserved for future extensions:
1 station per slave
Provision is made for
8 I/O bytes
for
communication between the
field bus node and the FEC
4.1: OFF
4.2: OFF
2 stations per slave
Not permitted
4.1: ON
4.2: OFF
3 stations per slave
4.1: OFF
4.2: ON
4 stations per slave
4.1: ON
4.2: ON
(factory setting)
Tab.1/7:
Number of stations per slave
With operating mode Remote I/O" you can set the number
of stations per slave with the 2−element DIL switch 4.
The required setting of the number of stations depends on
the equipment fitted on the CPX terminal (modules used) as
well as whether or not the I/O diagnostic interface is used.
The assigned I/O bits are in some cases reserved for system
functions and are therefore not available for the address
range of the CPX modules.
Содержание CPX-FB23
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE CPX FB23 EN en 0308NH...
Страница 15: ...Installation 1 1 Festo P BE CPX FB23 EN en 0308NH Chapter 1...
Страница 45: ...Commissioning 2 1 Festo P BE CPX FB23 EN en 0308NH Chapter 2...
Страница 86: ...2 Commissioning 2 42 Festo P BE CPX FB23 EN en 0308NH...
Страница 87: ...Diagnosis and error treatment 3 1 Festo P BE CPX FB23 EN en 0308NH Chapter 3...
Страница 104: ...3 Diagnosis and error treatment 3 18 Festo P BE CPX FB23 EN en 0308NH...
Страница 105: ...Technical appendix A 1 Festo P BE CPX FB23 EN en 0308NH Appendix A...
Страница 117: ...Index B 1 Festo P BE CPX FB23 EN en 0308NH Appendix B...
Страница 118: ...B Index B 2 Festo P BE CPX FB23 EN en 0308NH Contents B Index B 1 B 1 Index B 3...