2.8.2.1 Diagnostics history (object 0x10F3)
The diagnostic messages of the lower-order EtherCAT device are stored in the diagnostics history by
the object 0x10F3.
Index
(hex)
Subindex Description
Data
type
Values
Access
1)
0
Diagnostics history
U8
RO
1
Maximum messages
U8
20
RO
2
Newest message
U8
RO
3
Newest acknowledged message
U8
RW
4
New message available
BOOL
RO P
5
Flags
U16
0x0000
RW
0x10F3
6
…
70
Subindex 006
…
070
BYTE [23]
RO
1) RO = read only; RW = read/write; RO P = read only (PDO mappable)
Tab. 13 Structure of diagnostics object 0x10F3
To simplify diagnostics evaluation, the controller offers the option of having the presence of a new dia-
gnostic message evaluated by the process data. To do this, the object “New message available” can
optionally be mapped to the process data. This is done via diagnostics object 0x10F3 (sub-index 4).
Function
13
Festo — CPX-E-CEC-... — 2018-09