EtherCAT interface [LA EC]
LED
(green)
Meaning
Remedy
Off
No network connection
Check network connection.
Tab. 14 EtherCAT interface [LA EC]
Network-specific LED indicators
Connection status [XF1], [XF2]
LED
(green)
Meaning
Remedy
Lit
Network connection established
Status “Link”
–
Flashing
Network connection established
Status “Activity”
–
Off
No network connection
Check network connection.
Tab. 15 Connection status [XF1], [XF2]
Module status [MS]
LED
(green,
red,
orange)
Meaning
Remedy
Lit up
green
Normal operating status
–
Flashing
green
Configuration of automation system CPX-E
not complete or not correct
Complete or correct configuration of the
automation system CPX-E.
Lit up red
Error cannot be rectified
Contact Festo Service
è
Flashing
red
Error can be rectified
Check configuration of the automation
system CPX-E.
Flashing
altern-
ately
red/green
The automation system CPX-E is in self-
test mode.
–
Lit up
orange
Bootloader
–
Off
No logic power supply to the network
interface
Check logic supply.
Tab. 16 Module status [MS]
Network status [NS]
LED
(green,
red,
orange)
Meaning
Remedy
Lit up
green
The automation system CPX-E is online
and has a network connection (normal
operating status).
–
Network status [NS]
LED
(green,
red,
orange)
Meaning
Remedy
Flashing
green
The automation system CPX-E is online
and has received an IP address but does
not have a configured network connection.
Check configuration of the automation
system CPX-E; it is possible that the auto-
mation system CPX-E is not assigned to a
master/scanner.
Lit up red
Communication has failed.
Non-permitted IP address set that is
already used in the network.
Correct IP address.
Flashing
red
One or more “I/O connections” are in the
“time-out state”.
Check the physical connection to the
master/scanner.
Flashing
altern-
ately
red/green
The automation system CPX-E is in self-
test mode.
–
Lit up
orange
Bootloader, if the LED [MS] is also lit up
orange
è
Network-specific LED indicators
–
Off
The automation system CPX-E is offline.
No IP address assigned or no IP address
received from DHCP server.
Check network connection.
Check IP addressing settings.
Tab. 17 Network status [NS]
12
Disposal
ENVIRONMENT!
Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations
è
13
Technical Data
13.1
General Technical Data
General technical data
General technical data
Automation system CPX-E
Description of automation system CPX-E
è
1.1 Further applicable documents
Dimensions
(length × width × height)
1)
[mm]
124.3 × 75.9 × 82.5
Product weight
2)
[g]
288
Ambient temperature with
vertical mounting position
[°C]
–5 … +60
3)
Ambient temperature with
horizontal mounting position
[°C]
–5 … +50
3)
Storage temperature
[°C]
–20 … +70
Humidity
(non-condensing)
[%]
0 … 95
Degree of protection in accordance with
EN 60529
IP20
The degree of protection is not UL-tested.
Protection against electric shock
(Protection against direct and indirect
contact in accordance with IEC 60204-1)
through the use of PELV circuits
(protected extra-low voltage)
Electromagnetic compatibility
To EN 61000-6-2/-4 and NE 21
Module code/sub-module code
CPX-E-CEC-C1-EP
222/102
CPX-E-CEC-M1-EP
222/103
Module identification
CPX-E-CEC-C1-EP
E-CEC-C1-EP
CPX-E-CEC-M1-EP
E-CEC-M1-EP
1) including cover, not including linking element
2) Including linking element
3) for non-conforming technical data see UL operating conditions table
Tab. 18 General Technical Data