Module error [

P

]

1)

LED
(red)

Significance

Remedy

Parameterisation error (error number 29)

Check parameterisation and adjust.

Lit

Encoder error

2)

 (error number 108)

è

 Tab. 11 Encoder error [X2]

Off

Normal operating status

1) Lights up until the module initialisation is completed.

2) If monitoring via parameters is activated.

Tab. 8 Module error

Status of input I0 

 I3 [X0], [X1]

LED
(green)

Significance

Remedy

Lit

Input active (logic 1)
1 signal at input

Off

Input inactive (logic 0)
0 signal at input

Tab. 9 Status of input I0 ... I3 [X0], [X1]

Normal operation of encoder [X2]

LED
(green)

Significance

Remedy

Lit

Encoder in normal operation

Off

Encoder error
(

è

 Tab. 11 Encoder error [X2]) or module

not initialised

Tab. 10 Normal operation of encoder [X2]

Encoder error [X2]

LED
(red)

Significance

Remedy

Encoder error (error number 108)

Cable break

Check cables and connections.

Tracking error

Reduce frequency of input pulses.

Lit

Zero pulse error

Check “pulse/zero pulse” parameter and
adjust 

è

 Description of module.

Off

Encoder in normal operation
(

è

 Tab. 10 Normal operation of encoder

[X2]) or module not initialised

Tab. 11 Encoder error [X2]

Normal operation of encoder supply [X3]

LED
(green)

Significance

Remedy

Lit

Encoder supply in normal operation

Off

Error in encoder supply
(

è

 Tab. 13 Error in encoder supply [X3]) or

module not initialised

Tab. 12 Normal operation of encoder supply [X3]

Error in encoder supply [X3]

LED
(red)

Significance

Remedy

Lit

Short circuit/overload of encoder supply
(error number 2)

Check cables and connections.

Off

Encoder supply in normal operation
(

è

 Tab. 12 Normal operation of encoder

supply [X3]) or module not initialised

Tab. 13 Error in encoder supply [X3]

12

Disposal

ENVIRONMENT!

Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations 

è

 www.festo.com/sp.

13

Technical data

General technical data

General technical data for
automation system CPX-E

Description of automation system CPX-E

è

 1.1 Further applicable documents

Dimensions (length x width x
height)

[mm]

124.3 x 18.9 x 76.6

Product weight

1)

[g]

88

Mounting position

Vertical/horizontal

Ambient temperature

[°C]

–5 … +60 (–5 … +50)

2)

Storage temperature

[°C]

–20 … +70

Air humidity
(non-condensing)

[%]

0 … 95

Assigned address space
(inputs/outputs)

[bytes]

12/2

Degree of protection in
accordance with EN 60529

IP20

Protection against electric
shock (protection against dir-
ect and indirect contact in
accordance with
IEC 60204-1)

Through the use of PELV circuits
(protected extra-low voltage)

Electromagnetic compatibil-
ity

To EN 61000-6-2/-4

Module code/submodule
code (CPX-E-specific)

174/10

Module identification

E-1CI

1) Including linkage

2) for horizontal mounting position

Tab. 14 General technical data

Power supply

Operating voltage supply
U

EL/SEN

[V DC]

24 ± 25 %

Intrinsic current consumption
at nominal operating voltage
24 V from U

EL/SEN

[mA]

15

Reverse polarity protection

Yes

Encoder supply 5 V DC /
24 V DC

[V DC]

5 ± 5 % / 24 ± 25

%

Continuous nominal current
of encoder supply

[mA]

500

Short circuit protection of
encoder supply

Yes

Undervoltage identification

Response threshold U

EL/SEN

[V DC]

<

 16

Hysteresis U

EL/SEN

[V DC]

0.3 … 0.5

Response threshold, encoder
supply 5 V DC

[V DC]

4.5

Tab. 15 Power supply

Encoder inputs

Max. input frequency of encoder signals

1)

Differential

[MHz]

2

Single ended

[kHz]

250

Max. debounce time of encoder inputs

1)

Differential

[ns]

125

Single ended

[µs]

1

1) Dependent on the connection type of the encoder, "differential" or "single ended"

Tab. 16 Encoder inputs