Festo CPV..-GE-ASI-4E4A-... 0112c English
26
Type CPV...-GE-ASI-4E4A... M8
Load voltage connection
(only type ...-4E4A-Z)
– rated value
(protected against incorrect polarity)
– residual ripple
– Current consumption for 4 valves
(at 24 V)
– when switching on
– after current drop (stationary)
DC 21.6 ... 26.4 V
4 Vss
CPV10-... CPV14-...
108 mA
176 mA
42 mA
72 mA
Valves (see pneumatics manual)
Watchdog function active
after 50 ms (see 3.4)
Digital inputs
– design
– logic level
– reference potential
– response delay
4 inputs based on IEC
1131-2 type 2
DC 24 V, PNP, Status dis-
play (LED)
ON: 11 ... 30 V
OFF: -30 ...-5 V
0V
typ. 3 ms (at 24V)
Protection against explosion (as per EU
guideline 94/9/EG, EN 50021 and EN
50281-1-1).
Do not disconnect electrical connections
which are under tension. Plugs or adapters
of the electric connections must comply at
least with protection class IP64!
II 3 G/D EEx nA II T5 X
-5 °C
≤
Ta
≤
+50 °C
T 80 °C IP65 (year of
manufacture see Ex-
identification on the
product)
AS-Interface data
– Profile
ID-Code=F
H
;IO-Code=7
H
S-7.F