6
Commissioning
Information on commissioning
è
Description CECC.
7
Accessories
è
www.festo.com/catalogue
8
Technical data
CECC-...
D
LK
S
Operating voltage X1
19.2 VDC
…
30.0 VDC
20.4 VDC
…
30.0 VDV
Nominal current consumption at
24 V DC
100 mA
Ambient temperature
0 °C
…
55 °C
Storage temperature
–25°C
…
+70°C
Relative humidity
95 %, non-condensing
Degree of protection
IP20 (use in inside spaces)
Protection class
III
Dimensions
Length x width x height
130 mm x106 mm x48.15 mm
Product weight
200 g
Resistance test
Against vibration
In accordance with EN 61131-2
Against shock
In accordance with EN 61131-2
Electrical connection technology I/O
Socket strip, grid 3.5 mm
Status displays
LED
High-speed digital counter inputs X2.0 and X2.1
Number
2
Switching frequency
180 kHz
Signal delay (debounce time)
1 μs, factory setting, configurable with CODESYS
Digital inputs X2.2 …
X2.7 and X3.0 …
X3.5
Number
12
Switching frequency
1 kHz
Signal delay (debounce time)
3 ms, factory setting, configurable with CODESYS
All digital inputs X2 and X3
Switching logic
Positive logic (PNP)
Input voltage
24 VDC
Nominal value for TRUE
15 VDC
Nominal value for FALSE
5 VDC
Disconnection
Digital inputs from the internal
switching logic of the CECC
Galvanically separated
External power supply of
the interface from the operating
voltage supply of the CECC
Galvanically separated
Status indication
LED
Permissible connecting cable length
30 m
Digital outputs X4
Number
8
Switching logic
Positive logic (PNP)
Contact
Transistor
Output voltage
24VDC
Output current
500 mA
Disconnection
Digital outputs from the internal
switching logic of the CECC
Galvanically separated
External power supply of
the interface from the operating
voltage supply of the CECC
Galvanically separated
Switching frequency
1 kHz
Short-circuit proof
Yes
Fieldbus interface X6
Type
CAN bus
Connection technology
Plug, Sub-D, 9-pin
Transmission rate
10, 20, 50, 100, 125, 250, 500, 800, 1000 kBit/s
configurable with CODESYS
Disconnection
Signal lines of the interface from
the internal switching logic of the
CECC
Galvanically separated
Internal power supply of the
interface from the operating
voltage supply of the CECC
Galvanically separated
CECC-...
D
LK
S
USB interface X7
USB1.1
Ethernet interface X8
Connector plug
RJ45
Quantity
1
Transmission speed
10/100 Mbit/s
Suppor ted protocols
TCP/IP, EasyIP, ModbusTCP
IO-Link-interfaces
–
X12…X16
X15…X16
Protocol
–
IO-Link Device Port: V 1.0
IO-Link Master Port: V 1.1
Connection technology, plug
–
IO-Link Device Port: 3-pin
IO-Link Master Port: 5-pin
Communication mode
–
Can be configured via software
IO-Link Device Port: COM1, COM2, COM3
IO-Link Master Port: SIO, COM1, COM2, COM3
Permitted cable length
–
20 m
Port type
–
IO-Link Device Port: A
IO-Link Master Port: B
Number of ports
–
1 IO-Link Device Port
4 IO-Link Master
Ports
1 IO-Link Master Port
Output current operating voltage
(L+, L-)
–
≤ 200 mA/IO-Link Port
Output current load voltage (24, 0)
–
≤ 3.5 A/IO-Link Master Port
Communication
–
C/Q LED green
C/Q LED red
Ready status display
–
L+ LED green on
L+ LED green off
Process data width OUT
–
IO-Link Master: 2
…
32 byte, can be
parameterised
Process data width IN
–
IO-Link Master: 2
…
32 byte, can be
parameterised
Storage
–
2 kByte/IO-Link Master Port
Minimum cycle time
–
IO-Link Device Port: 3.2 ms
IO-Link Master Port: 5 ms
Device ID
–
0x550000, 0x550001, 0x550002, 0x550003,
0x550004
Serial interface modules
–
–
X12…X14
Type
–
–
2xRS232
1xRS485-A/422-A
Connection technology
–
–
Plug connector
Transmission rate
–
–
300…
375000 bit/s
Encoder interface
–
–
X14
Resolution
–
–
32 bit
Signal range
–
–
5 V, differential (RS422)
Maximum input frequency
–
–
1000 kHz
Operating voltage supply
for encoders
–
–
5 VDC
Programming languages
In accordance with IEC61131-3 AS, AWL, FUP, KOP, ST
Programming software
CODESYS V3pbF
Approvals
RCM mark
cULus - Listed (OL)
UL certification
Contamination level
2
Setup altitude
2000 m
Total power rating of the operating
and load voltage power supplies at
X1, X5 and X11
4.3 A
6 A
Load rating of the operating voltage
supply X1
125 mA
Load rating of the operating voltage
supply of the I/O interfaces X5
4.1 A
Load rating of the load voltage
supply X11
–
5.875 A
3.5 A
CE marking
è
www.festo.com/sp
è
Declaration of conformity
In accordance with EU EMC Directive
1)
The outputs of the CECC may be loaded only to the extent that the maximum total of input currents at
X1 (V-El.), X5 and X11 (CECC-LK: V-IOL, CECC-S: 24 V DC) is limited to 6 A.
2)
The controller is intended for use in an industrial environment: Outside of industrial environments, e.g.
in commercial and mixed-residential areas, actions to suppress interference may have to be taken.
3)
The controller is classified in zone A in accordance with EN 61131-2:2007.
Fig. 18 Technical data