6.6
Speed regulator
6.6.1
Overview
The parameter set of the motor controller must be adapted for the application. In
particular, the amplification is strongly dependent on masses that may be connected to
the motor. The data must be optimally determined during system start-up using the
parameterisation software.
Caution
Incorrect setting of the speed regulator parameters can result in
strong vibrations and possibly destroy parts of the system!
6.6.2
Description of the Objects
Index
Object
Name
Type
Attr.
60F9
h
RECORD
velocity_control_parameters
rw
2073
h
VAR
velocity_display_filter_time
UINT32
rw
Objekt 60F9
h
: velocity_control_parameters
The data of the velocity controller must be taken from the parameterisation software.
Attention must be paid to the following calculations:
The amplification of the velocity controller must be multiplied by 256.
With a gain of 1.5 in the "Velocity controller" menu of the parameterisation software, the
value 384 = 180
h
must be written in the object
velocity_control_gain
.
The velocity controller time constant is specified in the parameterisation software in
milliseconds. To transfer this time constant into the
velocity_control_time
object, it must
previously be converted into microseconds. With a specified time of 2.0 milliseconds, the
corresponding value 2000 is entered in the object
velocity_control_time
.