background image

CMGA-E1-CO

6

Festo – GDCP-CMGA-E1-CO-EN – 1201NH

The value of the rotary switches can be calculated as follows:

RDS value = 16 x (value of the “HIGH” rotary switch) + (value of the “LOW” rotary switch)

Please note that if you are using more than one CMGA-E1-CO in the same CANopen net-

work, the addresses of these must differ by at least 2.

Since a CANopen subscriber can have only one address in the range 1 to 127, the most significant bit is

used for the selection of the baud rate.

The CMGA-E1-CO supports 500 kBaud and 1 MBaud. If the most significant bit is a RDS value 0, the

device uses 500 kBaud, if it is 1, the device uses 1 MBaud.

Due to the number of TPDOs generated, there is a further restriction for the highest configurable ad-

dress. Therefore for the address range 1 to 126 (if you configure the address as 127, the device sees

this as 126).

If you want to generate heartbeat messages with the CMGA-E1-CO, you can configure the “Producer

Heartbeat Time” as described below under “Heartbeat Producer”.

Example: the “HIGH” rotary switch has the value 10, the “LOW” rotary switch the value 3:

RDS value = 10 * 16 + 3 = 163 = 0xA3

The most significant bit is set, and the CMGA-E1-CO CANopen interface is thereby configured with

1 MBaud.

The node ID is constituted from the 7 lower significant bits, and it can therefore be calculated as

follows: (0xA3 & 0x7F) = 0x23 = 35.

As described below under “TPDOs”, the COB-IDs can be calculated on the basis of the node ID.

TDPO

COB-ID

TPDO1

0x180 + 0x23 = 0x1A3

TPDO2

0x280 + 0x23 = 0x2A3

TPDO3

0x380 + 0x23 = 0x3A3

TPDO4

0x480 + 0x23 = 0x4A3

TPDO5

0x180 + 0x23 +1 = 0x1A4

TPDO6

0x280 + 0x23 +1 = 0x2A4

TPDO7

0x380 + 0x23 +1 = 0x3A4

TPDO8

0x480 + 0x23 +1 = 0x4A4

Tab. 2

Calculation of COB-IDs

If you would like, you can change the COB-IDs of the TPDOs by altering the desired values in the corres-

ponding positions of the OD.

Содержание CMGA-E1-CO

Страница 1: ...Description Installation manual CANopen extension module 761724 1201NH Extension module CMGA E1 CO...

Страница 2: ...avoid them Warning Dangers which can lead to death or serious injuries Caution Dangers which can lead to slight injuries or to serious material damage Other symbols Note Material damage or loss of fu...

Страница 3: ...isation of the backplane communication 5 4 Parametrisation of the CANopen communication 5 5 Device specific OD entries 7 6 TPDOs 9 7 SDO 9 8 Heartbeat producer 9 9 Connection 10 10 DiagData 10 11 LEDs...

Страница 4: ...vels 2 Safety regulations 2 1 Operation and service The module must always be de energized before installation and removal or before disconnecting signal lines or supply lines When installing or remov...

Страница 5: ...1st mapped device or 0 if not used 0x6200 2 CAN ID of the 2nd mapped device or 0 if not used 0x6200 3 CAN ID of the 3rd mapped device or 0 if not used 0x6200 4 CAN ID of the 4th mapped device or 0 if...

Страница 6: ...ddress as 127 the device sees this as 126 If you want to generate heartbeat messages with the CMGA E1 CO you can configure the Producer Heartbeat Time as described below under Heartbeat Producer Examp...

Страница 7: ...agData of the 2nd mapped device 0x6002 0x00 UINT8 Number of the sub indices used const 8 0x6002 0x01 UINT8 1st byte DiagData of the 3rd mapped device 0x6002 0x02 UINT8 2nd byte DiagData of the 3rd map...

Страница 8: ...0x6006 0x05 UINT8 5th byte DiagData of the 7th mapped device 0x6006 0x06 UINT8 6th byte DiagData of the 7th mapped device 0x6006 0x07 UINT8 7th byte DiagData of the 7th mapped device 0x6006 0x08 UINT...

Страница 9: ...t be altered but it can be read from the OD index 0x1A00 to 0x1A07 A TPDO telegram is always generated if there is a change in the received DiagData of the assigned device Example if there is a change...

Страница 10: ...1201NH 9 Connection CANopen interface CMGA E1 CO CMGA B1 M CAN backplane bus CMGA B1 M max 8 devices Fig 2 Connection principle 10 DiagData Configuration of the internal data frame see installation ha...

Страница 11: ...ERATIONAL status green flashes 1 time CANopen STOPPED status The device is in STOPPED status permanently green CANopen in operation XB permanently red No device mapping con figured Write the assignmen...

Страница 12: ...A CANopen specific term Each CANopen sub scriber has its own object directory as a central data structure An entry in the OD is addressed with an index and a sub index There are a series of standard...

Страница 13: ...odules is modified the safety function can be lost Speak to the company which installed or delivered the CMGA modules or to the person who issued the safety test report 15 Maintenance 15 1 Replacement...

Страница 14: ...CMGA E1 CO 14 Festo GDCP CMGA E1 CO EN 1201NH...

Страница 15: ...CMGA E1 CO Festo GDCP CMGA E1 CO EN 1201NH 15...

Страница 16: ...t express authorization is prohibited Offenders will be liable for damages All rights reserved in the event that a patent utility model or design patent is registered Copyright Festo AG Co KG Postfach...

Отзывы: