Clean Design individual valve

en

. . . . . . . . . . . . . . . . . . .

1 Scope of application

The Clean Design individual valve (CDSV) from Festo has
been specially designed for the splash range in the food
and packaging industry. Special attention has been given
to:
– Increased resistance to corrosion
– resistance to acid and alkaline cleaning agents
– Protection: IP 65 and IP 67

2 Requirements for product use

Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation and commissioning to be carried out only
by qualified personnel in accordance with the operating
instructions.

Warning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

The CDSV with 3/2-way valves can be used in a pressu-
re range of 3 … 10 bar; it is therefore

not

vacuum-com-

patible.

General conditions for the correct and safe use of the
product, which must be observed at all times:
• Observe the specified limit values (e.g. for pressures,

torques, temperatures, etc.).

• Please observe the prevailing environmental conditions.
• Please comply with national and local safety laws and

regulations.

• Pressurize your entire system slowly. There will then be

no uncontrolled movements.

• This product should only be used in its original status

without unauthorised modifications. Only the conver-
sions or modifications described in this product docu-
mentation are permitted.

3 Mounting

Warning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Contamination of the CDSV through the production
process:
• Seal any unused mounting holes in the manifold

block with the supplied blanking plugs.

Doing this will prevent bacterial contamination from
occurring at open mounting holes.

4 Electrical connection

The wires of the multi-pin cable are assigned as follows:

Wire colour

Allocation

Brown

Coil 14 of the valve

Black

Coil 12 of the valve
(not 5/2-way valve, monostable)

Blue

COM

*)

*)

0 V with positive switching control signal; with negative swit-
ching control signal connect 24 V.

5 Pneumatic connection

Either operate the CDSV:
– with auxiliary pilot air branched from port 1 (use

connector type: QSY-F-6 for this purpose). The opera-
ting pressure of the CDSV is then 3 … 6 bar, or

– with separately supplied and regulated auxiliary pilot

air (3 … 6 bar). The operating pressure is then
–0.9 … 10 bar or 3 … 10 bar for 3/2-way valves.

Warning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Under certain circumstances, excess pressure can build
up under the valve cover of the CDSV:
• Do not on any account seal the hole for pressure

compensation (port L on the sub-base).

• Discharge the excess pressure separately. Do

not

use a non-return valve in the line.

Operating medium

Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Too much residual oil content in the compressed air will
reduce the service life of the valve.
– When using bio-oils (oils that are based on synthetic

ester or native ester, e.g. rapeseed oil methyl ester),
the maximum residual oil content of 0.1 mg/m³
should not be exceeded
(see ISO 8573-1:2010 [7:4:2]).

6 Maintenance and care

Note

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Please note the following:
• Avoid using cleaning agents with a sodium hypochlo-

rite basis.

• Use aluminium-friendly cleaning agents.
• Use the cleaning agent in accordance with the con-

centration and processing temperature specified by
the manufacturer (see the corresponding data
sheet); however, the processing temperature should

not exceed

+50 °C.

• Do not disinfect the CDSV with UV light.
• Do not use any high-pressure cleaning agents.
• Please note that protection classes IP65 and IP67

refer to the surface tension of clear water. Cleaning
agents minimize this surface tension.

• After cleaning, rinse the CDSV with plenty of clean

water to flush away the cleaning agent and to pre-
vent it from drying out. Otherwise this could lead to
an increase in the concentration of the cleaning
agent. This can attack the surface of the CDSV under
certain circumstances.

7 Replacing valves

Ident.
code
(I.C.)

Type

Valve functions

H

CDVI5.0-MT2H-3OLS-3GLS

2x3/2-way valve,
1 x open, 1 x closed

K

CDVI5.0-MT2H-2x3/2GLS

2x3/2-way valve, closed

N

CDVI5.0-MT2H-2x3/2OLS

2x3/2-way valve, open

J

CDVI5.0-MT2H-5JS

5/2-way double pilot valve

M

CDVI5.0-MT2H-5LS

5/2-way valve, monostable

B

CDVI5.0-MT2H-5/3BS

5/3-way valve, pressurized

E

CDVI5.0-MT2H-5/3ES

5/3-way valve, exhausted

G

CDVI5.0-MT2H-5/3GS

5/3-way valve, closed

1.Clean the surface of the sub-base before replacing the

valve.

2.Loosen the mounting screws of the valve

(

1

in cover picture).

3.Carefully pull the valve from the sub-base.
4.When mounting, check to make sure the bottom of the

valve is flush with the bottom of the valve hood.

5.Insert the new valve carefully into the sub-base. When

doing this make sure the electrical terminal lugs are not
bent.

6.Tighten the mounting screws with 0.8 Nm (–0.1 Nm).

8 Technical data

Type

CDSV-…

Operating pressure:
– 5/2-, 5/3-way valve
– 3/2-way valves
Pilot pressure

–0.9 … 10 bar

3 … 10 bar
3 … 8 bar

Medium

Compressed air to
ISO 8573-1:2010 [7:4:4]

Permitted temperature range:
– Storage
– Medium

–20 °C … +40 °C

–5 °C … +50 °C

Mounting position

Any

Vibration

Shock

Tested according to
DIN/IEC 68/EN 60068 Part 2-6;
severity level 2
Tested according to
DIN/IEC 68/EN 60068 Part 2-27;
severity level 2

Corrosion resistance class

Designed for high corrosion
resistance, e.g. outdoor exposure
under moderate conditions and
typical industrial atmospheres

Tightening torque:
– Valve/cover hood on sub-

base

– Tubing fitting/mounting

fittings

M3:0.8 Nm (-0.1 Nm)

M5: 0.3 Nm (± 0.015 Nm)
G1/8" and M6: 1.0 Nm (+0.5 Nm)

Pneumatic ports:
– (2), (4), (3), (5) and (1)
– (12/14), (82/84) and (L)

G1/8"
M5

Material:

AlMgSiO,5 F25; PP-GF50; TPE-0; PP;
stainless steel; PVDF; PUR (cable
sheath)

Dimensions of the CDSV

34/207/67.6 mm (L/W/H),
Tolerance ± 1 mm

Protection

Protection to IP65 and IP67

Electromag. compatibility

1)

See declaration of conformity

www.festo.com

Non-overlapping

Yes, except for 3/2-way valves

Operating voltage

DC 24 V ± 10 %

Current consumption (at 24 V,
per solenoid coil with LEDs)
– High-current phase
– Holding current phase

120 mA (100 ms)
26 mA

Power consumption (with
LEDs)

3.1 W

– Valve switching times

[in ms]

– 2x 3/2-way valves
– 5/2-way valves, mono
– 5/2-way valves, pulse

2)

– 5/3-way valve

Ident. code
N, K and H
M
J
B, E and G

On
10
12

12

Change
over

10
17

Off
22
22

25

1)

The valve is intended for use in an industrial environment.
Outside of industrial environments, e.g. in commercial and mixed-
residential areas, measures to suppress interference may need to
be implemented.

2)

Duration of the switching pulse at least 7 ms.