background image

Assembly instructions (Translation: en) 
755130 
1206NH 

 

 

 

†‡

 

Electric sub-base 
CAPC-F1-E-M12 

Festo AG & Co. KG 

 
Postfach 
D-73726 Esslingen 
+49 (0)711 347 0 
www.festo.com 

 

 

 

 

 

 

1.

 

Parts list 

1a.

 

CAPC-F1-E-M12 

17381d_1 

 

Elec. sub-base 

Moulded seal 

(1x) 
(1x) 

The intended purpose of the 
elec. sub-base 

1

 is the decen-

tralised installation of CTEU 
bus nodes and the connection 
of devices with an I-port inter-
face. 

 

17381d_11 

Not included in scope of 
delivery: 

M4 screws 

 
 
(4x) 

1b.

 

CAFM-F1-H 

17381d_2 

 

4

 H-rail 

mounting 

(1x) 

The intended purpose of the  
H-rail mounting 

4

 is the  

installation of the elec. sub-
base 

1

 on a top-hat rail. 

2.

 

Technical data

1)

 

CAPC-F1-E-M12 

Protection class

2)

 

 

 

IP65/IP67 (

 Chapter 5) 

Storage temperature 

 

[°C] 

20 … +70 

 

Note 

In order to avoid material damage and operating malfunctions. 

 

Observe the permissible tightening torques. 

3.

 

Mounting 

 

1738

1d_4 

 

Remove the sealing plug (A) 
from the bus node (B) with, 
for example, a screwdriver. 
For this use the recesses on 
the side (C) of the sealing 
plug (A). 

 

1738

1d_1

 

Press the moulded seal 

2

 

together on the sides. 

 

1738

1d_5 

 

 

Note 

In order to ensure that the 
moulded seal 

2

 functions  

correctly: 

 

Fit the moulded seal 

2

 in 

the groove (D) 

 

without any undulations 

 

parallel to the surface (E) 

 

undamaged. 

 

                                                                            

1)

 Further technical data can be found in the documentation on the CTEU-... bus node. 

2)

 Protection provided by housing in accordance with IEC/EN 60529. 

 

1738

1d_6 

 

Note 

In order to avoid damage to 
the pin contacts (F): 

 

Mount the bus node (B) 
straight and without the use 
of any high force. 

 

 

Tighten the self-cutting 
screws (G). 
If it has to be mounted 
again, use the available 
threads. 

 

4.

 

Fastening 

 

 
1738

1d_7 

4a.

 

Using the screws 

3

The elec. sub-base 

1

 is  

intended to be fastened to the 
wall by means of 
for example a mounting rail  
or mounting plate. 

 

Place the elec. sub-base 

1

 

on a mounting rail (H) for 
example (20 mm grid). 

 

Fasten the elec. sub-base 

1

 

with suitable screws 

3

 and 

slot nuts. 

 

1738

1d_8 

4b.

 

Using the H-rail  

mounting 

4

 

Place the H-rail clip (I) on 
the drill hole of the elec. 
sub-base 

1

 

Tighten the self-cutting 
screw (J) with a 
T10 screwdriver. 

 

5.

 

I-port interface 

Bush M12 

Pin 

Allocation 

Function 

5-pin, A-coded 

1 24 

V

EL/SEN

 (PS) Operating voltage supply 

 

 

 

2 24 

V

VAL/OUT

 (PL) Load 

voltage 

supply 

3 0 

V

EL/SEN

 (PS) 

Operating 

voltage 

supply 

4 C/Q 

I-PORT

  

Data 

communication

3)

 

5 0 

V

VAL/OUT

 (PL) Load 

voltage 

supply 

Housing FE 

 

Functional 

earth 

17381d_9 

 

 

1738

1d_1

 

Note 

To comply with protection class 
IP65/IP67: 

 

Plug the unused connections 
with the enclosed cover 
caps (K). 

 

 

Mount a connecting cable (L) to the elec. sub-base 

1

 

6.

 

Earthing 

 

1738

1d_1

 

Note 

 

Connect the earthing con-
nection (M) with low imped-
ance to the earth potential. 

 

Use suitable cable lugs (N). 

 

Tighten the screw (O) with a T10 screwdriver. 

                                                                            

3)

 Voltage supply via pin 4 (two-conductor system PHY1) is not permissible. 

0.6 Nm 

_

 20 % 

1 Nm 

_

 10 % 

0.1 Nm 

_

 10 % 

0.4 Nm 

_

 20 % 

Отзывы: