GENERAL FEATURES

Description of components

External structure

. Basement, supporting structure and lateral 

panels are made of galvanized and painted sheet-steel (colour 

RAL 7035) to guarantee good resistance to atmospheric agents. 

Accessibility  to  internal  parts  is  possible  removing  the  frontal 

panel. For extraordinary manteinances also the rear panel can 

be removed.

Refrigerant  circuit

.  It  is  contained  inside  a  compartment 

separated from the air flow to simplify maintenance and control 

operations.
The  hermetic  scroll 

compressor

  (1)  is  mounted  on  damper 

supports  and  is  protected  against  overtemperatures  and 

overcurrents.  It  is  equipped  with  an  electrcal  heater,  that  is 

activated when the compressor turns off, to keep the compressor 

crankcase oil temperature high enough to prevent migration of 

the refrigerant during winter stops and to evaporate any liquid 

present  in  the  crankcase,  in  order  to  prevent  possible  liquid 

rushes on starting (only heat pump models).

The 

plant side heat exchanger

 (2) is a brazed stainless steel 

plate  heat  exchanger,  properly  insulated  to  avoid  condensate 

generation and to minimize thermal losses, and protected by a 

differential pressure switch that detects whatever water flow lack. 

It is moreover protected against freeze danger by an antifreeze 

electrical heater.

The 

source side heat exchanger

 (3) is a finned coil realized with 

grooved copper pipes and aluminium fins with notched profile to 

increase the heat exchange coefficient. A tray is obtained in the 

basement to collect the condensate generated in heating mode.

The 

expansion device

 (4), a thermostatic expansion valve with 

external equalizer, allows the unit to adjust itself to the different 

operating conditions keeping steady the set superheating.

The  refrigerant  circuit  of  each  unit  contains  moreover  solid 

core hermetic 

filter dryer

 (5) to restrain impurity and moisture 

residuals  that  could  be  present  in  the  circuit, 

high  and  low 

pressure  switches

  in  order  to  assure  the  compressor  to 

operate inside the permitted limits, 

4 way reverse cycle valve 

(6) to allow operating mode change reversing the refrigerant flow 

(only heat pump models), 

liquid receiver

 (7) to compensate the 

different  refrigerant  charge  required  in  heating  and  in  cooling 

mode  (only  heat  pump  models)  and 

pressure  connections

 

SAE  5/16”  -  UNF  1/2”  -  20    equipped  with  pin,  gasket  and 

blind  nut,  as  required  for  the  use  of  R410A  refrigerant  (they 

allow the complete check of the refrigerant circuit: compressor 

inlet  pressure,  compressor  outlet  pressure  and  thermostatic 

expansion valve upstream pressure).

The 

fans

  (8)  are  plug  fan  type  fans  equipped  with  EC  direct 

current motor and embedded inverter. The fans rotational speed 

is modulated continuosly to control the condensation pressure 

(in cooling) and the evaporation pressure (in heating) in order to 

optimize the operating conditions of the unit and to reduce noise 

emissions. The maximum rotational speed can be modified by 

parameter in order to set the available static head of the fan to 

the plant requirements.

Hydraulic circuit

. All the pipes are thermally insulated to avoid 

condensate generation and minimize thermal losses. The circuit 

can be equipped with different kind of circulation pump (option). 

In that case the circuit is also equipped with expansion vessel 

and air vents. It is also possible to integrate inside the unit a buffer 

tank arranged as buffer on the flow towards the plant (option). In 

that case the circuit is equipped not only with expansion vessel 

and air vents, but also with safety valve, automatic air vent and 

drain cock.

Electrical panel

. It contains all the power, control and security 

components necessary to guarantee the unit to work properly. 

The unit is managed by a microprocessor controller to which all 

the electrical loads and the control devices are connected. The 

user interface, placed on the frontal panel, allows to view and to 

modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor, 

already  installed  on  the  unit,  in  order  to  realize  the  climatic 

control.

3

7

2

6

4

5

1

8

3

7

2

6

4

5

1

8

Содержание RMP series

Страница 1: ...RMP AIR WATER CHILLERS AND HEAT PUMPS FOR INDOOR INSTALLATION TECHNICAL MANUAL R E F R I G E R A N T G A S E C O FRIEND L Y...

Страница 2: ...s all the responsabilities regarding inaccuracies contained in this manual if due to printing or typing mi stakes The manufacturer reserves the right to apply changes and improvements to the products...

Страница 3: ...ng up VB Standard plants 11 NOMINAL performances Base setting up VB Radiant plants 12 NOMINAL performances Low noise setting up AS Standard plants 13 NOMINAL performances Low noise setting up AS Radia...

Страница 4: ...4...

Страница 5: ...emissions in such operating conditions The low noise acoustic setting up AS is obtained starting from the base setting up AB reducing the rotational speed of the fans and mounting sound jackets on th...

Страница 6: ...switches in order to assure the compressor to operate inside the permitted limits 4 way reverse cycle valve 6 to allow operating mode change reversing the refrigerant flow only heat pump models liqui...

Страница 7: ...mpressor and pump operating hours recording serial communication through Modbus protocol remote stand by remote cooling heating general alarm digital output Versions Each model can be supplied in thre...

Страница 8: ...tee a more stable flow temperature Tank and modulating pump Allows the circulation of the water on the plant side with the possibility to set the rotational speed of the pump in order to get the reque...

Страница 9: ...he operating conditions of the unit through Modbus communication protocol The RS485 serial line ensures the signal quality up to distances of about 1200 meters that can be extended by means of proper...

Страница 10: ...nd embedded inverter plug fan with EC motor and embedded inverter plug fan with EC motor and embedded inverter plug fan with EC motor and embedded inverter Quantity 1 1 1 1 1 1 n Diameter 630 630 630...

Страница 11: ...Pressure drops plant side 19 23 19 27 23 28 kPa IR Cooling A35W7 source air in 35 C d b plant water in 12 C out 7 C Cooling capacity 20 0 22 2 25 9 31 0 35 8 40 4 kW EER 2 97 3 00 2 99 2 92 2 96 2 95...

Страница 12: ...7 33 2 38 4 43 3 kW Power input 5 48 6 03 7 03 8 71 9 91 11 3 kW COP 3 91 3 95 3 94 3 81 3 87 3 83 Water flow rate plant side 3651 4063 4731 5657 6549 7371 l h Pressure drops plant side 29 35 29 40 3...

Страница 13: ...ure drops plant side 17 21 17 24 21 26 kPa Frame 1 2 Model 19 1 22 1 26 1 30 1 35 1 40 1 U M Power supply 400 3N 50 400 3N 50 400 3N 50 400 3N 50 400 3N 50 400 3N 50 V ph Hz IR Cooling A35W7 source ai...

Страница 14: ...31 6 36 5 41 2 kW Power input 5 24 5 77 6 73 8 34 9 49 10 9 kW COP 3 87 3 92 3 91 3 79 3 85 3 78 Water flow rate plant side 3463 3857 4491 5383 6223 7011 l h Pressure drops plant side 26 32 26 37 31 3...

Страница 15: ...e graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions The reference nominal condition is...

Страница 16: ...allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions The reference nominal condition is A7W35 sou...

Страница 17: ...to units operating with water at the temperature of 10 C density 1000 kg m3 Flow rate l h Pressure drops kPa 0 40 80 120 160 200 240 280 320 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 Available s...

Страница 18: ...0 3000 4000 5000 6000 7000 8000 9000 Available static head unit with option Storing and pumping module Modulating pump or Tank and modulating pump The graphs are referred to units operating with water...

Страница 19: ...tion must guarantee that the medium air velocity does not exceed 2 5 m s in order to avoid noise problems and to keep the pressure drops lower as possible Source side aeraulic performances Available s...

Страница 20: ...0 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 HEATING Inlet air temperature d b C Outlet temperature plant side C The graphs reported below show the operating area inside which the cor...

Страница 21: ...ctrical heaters standard in the tank option TECHNICAL DATA AND PERFORMANCES Noise levels Model Sound power levels dB by octave bands Hz Sound power level Sound pressure level at 1 metre at 5 metres at...

Страница 22: ...pump 12 12 12 14 16 16 kg Tank and standard pump 31 31 31 31 33 33 kg Tank and high head pump 34 34 34 34 35 35 kg Tank and modulating pump 34 34 34 36 38 38 kg Integrative electrical heaters Standar...

Страница 23: ...1453 24 53 576 131 614 215 G F 73 368 74 F 73 368 24 1 2 1 2 B C A Plant return Plant flow Frame 1 2 Model 19 1 22 1 26 1 30 1 35 1 40 1 1 1 1 4 F 1 1 4 F 1 1 4 F 1 1 4 F 1 1 4 F 1 1 4 F 2 1 1 4 M 1 1...

Страница 24: ...Cod 3QE29590...

Отзывы: